Exact dimensions and weight are not provided in the search results. However, it is generally a compact module suitable for installation in a rack or panel.
Power supply: Powered by connection to the acquisition system or external battery
Output voltage adjustable range: 10 V to 50 V
Operating temperature range: **-18°C to +60°C (mentioned in the vibration monitor documentation) and -20 to +55°C** (mentioned in the power management device documentation)
Storage temperature range: -40°C to +85°C
Over voltage, over current, over temperature and short circuit protection: available
Input: The module may provide four sensor inputs and four temperature inputs. Each sensor input can be configured to support 2-wire and 3-wire accelerometers, speed sensors, or proximity sensors. Each temperature input supports type E, J, K, and T thermocouples and 2 – or 3-wire thermal resistors.
Output: Six relay outputs, four 4-20 mA recorder outputs, and one dedicated buffer output are available.
System environment: applies to normal system environment.
System capability: strong.
Output frequency: 150 (This parameter may be related to the specific module model or purpose).
Parameters and specifications
Input power:
Ac: 110 to 220 Vac (nominal), 85 to 264 Vac RMS, 120 to 373 Vac pk
Direct current (high voltage) : 88 to 140 Vdc
Dc (low voltage) : 20 to 30 Vdc
Output power supply:
Different models have different output power supplies, such as the BENTLY 3500/15 127610-01 with 24 VDC, 5.5 A, while the Bently 3500/15 133292-01 with 15V DC.
Frequency: Input frequency 47 to 63 Hz.
Current: Different models have different current specifications, such as the BENTLY 3500/15 127610-01 for 2 A.
Operating temperature: The range varies by model, for example the BENTLY 3500/15 127610-01 is 0°C to 60°C, while the Bently 3500/15 133292-01 is -20°C to 60°C.
Power input: Depending on the model, the input voltage may include AC (AC) 100-240 VAC, 50/60 Hz; Common AC voltage ranges from 110 to 220 Vac, 85 to 264 Vac RMS, or 120 to 373 Vac pk; Direct current (DC) 88 to 140 Vdc (high voltage) or 20 to 30 Vdc (low voltage).
Power output: The specific output depends on the model, for example, there are 24 VDC, 5.5A models, there are 15V DC, 2A models.
Operating temperature: May range from -30°C to +65°C, or from 0°C to 60°C, to -20°C to 60°C, depending on the model.
Input and output insulation resistance: 500 VDC, greater than 10 MΩ.
Function: Interface to software compatible with 3500 monitoring systems, including System 1 status monitoring and diagnostic software and 3500 system configuration software.
Communication: Combine 3500/20 rack interface modules (RIM capabilities) with communication processors (such as TDXnet) to collect data.
Function: Continuously collect steady-state and transient dynamic (waveform) data and transmit this data to the host software over an Ethernet link.