Description
Product Parameters
| Parameter | Specification |
|---|---|
| Model | IS230TRLSH1 |
| Manufacturer | GE Energy / Baker Hughes |
| Platform | Mark VIe |
| Type | Relay output termination board |
| Compatible Modules | IS220PDOAH1A, IS220PDIOH1A, IS220PDIOH1B |
| Output Channels | 8 relay outputs (dry contacts) |
| Contact Type | Form A (SPST, normally open) |
| Contact Rating | 5 A at 250 VAC / 30 VDC (resistive) |
| Contact Material | Silver alloy (AgSnO₂) |
| Switching Voltage | 250 VAC / 30 VDC (max) |
| Switching Current | 5 A (max) |
| Inrush Capability | 10 A (for 100 ms) |
| Coil Voltage | 24 VDC (provided by I/O module) |
| Surge Suppression | Integrated RC snubber and flyback diode |
| Terminal Type | Screw-clamp (pluggable, 2‑piece) |
| Number of Positions | 16 positions (field wiring side) |
| Wire Gauge | 0.2–2.5 mm² (AWG 24–14) |
| LED Indicators | Individual per-channel LED (ON status) |
| Isolation | 1500 V (coil-to-contacts, contacts-to-backplane via module) |
| Operating Temperature | -30°C to +70°C |
| Storage Temperature | -40°C to +85°C |
| Humidity | 5% to 95% (non‑condensing) |
| Dimensions | Standard Mark VIe terminal board form factor |
| Weight | Approx. 0.45 kg |
| MTBF | > 150,000 hours |
Advantages and Key Features
-
Isolated Dry Contact Outputs – The IS230TRLSH1 provides 8 Form A (SPST) relay outputs, offering complete electrical isolation between the control system and field devices. This protects the Mark VIe processor from field-side faults and transients.
-
High Current Capacity – Each relay contact on the IS230TRLSH1 is rated for 5 A continuous, with 10 A inrush capability, enabling direct control of motor starters, solenoid valves, and other high-current loads without interposing devices.
-
Integrated Surge Suppression – Built-in RC snubbers and flyback diodes on the IS230TRLSH1 protect contacts from inductive load switching transients, extending relay life and ensuring reliable field device operation.
-
Per-Channel Status LEDs – Individual LEDs for each relay output on the IS230TRLSH1 provide immediate visual confirmation of output status, simplifying field troubleshooting without requiring software access.
-
Pluggable Terminal Design – The IS230TRLSH1 features a 2‑piece pluggable terminal block design, allowing field wiring to be disconnected without removing individual wires, simplifying maintenance and module replacement.
-
Silver Alloy Contacts – AgSnO₂ contact material provides superior resistance to welding and arcing, ensuring long service life even in demanding industrial applications.
-
Wide Temperature Range – Rated for -30°C to +70°C, suitable for outdoor and harsh turbine environments.
-
Flame‑Retardant Housing – UL 94 V‑0 rated material provides safety in the event of electrical faults.
Application Fields and Use Cases
1. Motor Starter Control
The IS230TRLSH1 provides isolated relay outputs for controlling motor starters for pumps, fans, and compressors, with contact rating sufficient for direct starter coil actuation.
2. Solenoid Valve Actuation
Provides dry contact outputs for controlling solenoid-operated valves (fuel trip valves, steam admission valves, drain valves), with integrated surge suppression for inductive loads.
3. Alarm Annunciation
The IS230TRLSH1 controls annunciator panels, horns, and strobe lights, providing electrically isolated outputs for alarm notification.
4. Trip and Shutdown Actuation
Provides isolated relay outputs for safety trip solenoids, ensuring complete electrical separation between control logic and safety-critical field devices.
5. Status Indication
Controls indicating lamps, panel lights, and remote status displays, providing visual feedback to operators and external systems.
6. Retrofit Projects
The IS230TRLSH1 is a cost‑effective relay output termination solution for Mark VIe upgrades from legacy systems requiring external relay interface.
Comparison with Competing Products
| Feature | IS230TRLSH1 (GE) | IS220PDOAH1A (GE) | IS230TBTCH1B (GE) | ABB DO880 + TU830 | Siemens 6ES7 392-1AJ00 |
|---|---|---|---|---|---|
| Platform | Mark VIe | Mark VIe | Mark VIe | AC 800M | S7-400 |
| Type | Relay output TB | Output module | Universal TB | Output + terminal | Terminal block |
| Output Channels | 8 relays | 32 solid‑state | Up to 32 | 16 relays | 8 relays |
| Contact Rating | 5 A | 0.5 A | Via module | 2 A | 2 A |
| Inrush Capability | 10 A | N/A | Via module | N/A | N/A |
| Surge Suppression | Integrated | N/A | Via module | External | External |
| LED Indicators | Per‑channel | Per‑channel | No | Per‑channel | No |
| Isolation | 1500 V | 1500 V | Via module | 1500 V | 500 V |
| Pluggable | Yes | N/A | Yes | Yes | No |
| MTBF | > 150,000 hrs | > 180,000 hrs | > 200,000 hrs | > 120,000 hrs | > 80,000 hrs |
Key Differentiators: The IS230TRLSH1 is a dedicated relay output termination board providing high-current (5 A) isolated dry contact outputs with integrated surge suppression. Unlike direct solid‑state outputs (IS220PDOAH1A), it offers complete coil-to-contact isolation and handles higher inrush currents. Compared to universal terminal boards (IS230TBTCH1B), the IS230TRLSH1 provides built‑in relays with per‑channel LED status indication, simplifying field troubleshooting. It is the preferred solution for applications requiring isolated, high-current switching.
Selection Suggestions and Precautions
Selection Criteria
-
Choose the IS230TRLSH1 for applications requiring isolated dry contact relay outputs with high current capacity (up to 5 A) for controlling motors, solenoids, and alarm devices.
-
For high‑density solid‑state outputs without isolation requirements, consider the IS220PDOAH1A with IS220YDIAS1A.
-
Verify the number of relay outputs (8 channels) meets application requirements.
-
Ensure the contact rating (5 A) is sufficient for the connected field loads.
Critical Precautions
-
Load Rating – Ensure field device current does not exceed the IS230TRLSH1 contact rating (5 A continuous, 10 A inrush). For inductive loads, apply appropriate derating (typically 50% of resistive rating).
-
Surge Suppression – While the IS230TRLSH1 includes integrated suppression, for high-inductance loads (large solenoids, motors), consider additional external suppression to further protect relay contacts.
-
Wiring – Use appropriate wire gauge for the IS230TRLSH1 based on load current. For 5 A loads, use minimum AWG 18 (0.75 mm²). Keep relay output wiring separated from signal wiring.
-
Terminal Connections – Recommended torque: 0.5–0.6 N·m. Over‑tightening may damage terminals; under‑tightening may cause arcing and overheating.
-
Polarity – For DC loads, observe proper polarity to ensure the integrated flyback diode provides effective suppression. Reverse polarity may damage the suppression circuit.
-
LED Indication – Per‑channel LEDs on the IS230TRLSH1 indicate relay coil status, not contact status. Verify actual contact continuity during commissioning.
-
ESD Handling – Use grounded wrist straps when handling the IS230TRLSH1 to prevent static damage.
-
Relay Life – The IS230TRLSH1 relays are rated for mechanical life > 10 million operations and electrical life > 100,000 operations at rated load. Consider maintenance intervals for high‑cycle applications.
-
Obsolescence – The IS230TRLSH1 is in active production with long‑term support. For future projects requiring higher channel density, evaluate the IS230TRLSH1A when available. Keep spare boards for critical relay output applications.

SIEMENS 6ES5470-7LA12
AB 802R-HF
COMTROL 97590-8


Reviews