Description
Key Specifications
| Parameter | Specification |
|---|---|
| Output Channels | 16 Form A (normally open) relay outputs |
| Contact Rating | 6 A @ 250 VAC / 30 VDC (resistive load) — improved over WROBH1A |
| Inrush Capability | 12 A for 150 ms (inductive/capacitive loads) — improved over WROBH1A |
| Coil Voltage | 24 VDC nominal (module powered) |
| Switching Frequency | Maximum 10 Hz (mechanical life limitation) |
| Mechanical Life | >10,000,000 operations (no load) |
| Electrical Life | >150,000 operations at rated load — improved over WROBH1A |
| Protection | Built-in flyback diodes (DC inductive loads), integrated snubber circuits (AC loads) — improved over WROBH1A |
| Diagnostic Feedback | Output state feedback (auxiliary contact), contact resistance monitoring (new) |
| Isolation | 1500 VDC (coil-to-contacts), 1000 VDC (contact-to-contact) |
| Diagnostics | 750-event fault log with timestamps (expanded over WROBH1A) |
| Communication | I/O Net (dual Ethernet ports for redundancy) |
| Form Factor | 6U VME64x (160 × 233 mm), single-slot width |
| Indicators | Per-channel LED (output state/command), module health, communication status |
| Operating Temp | –25 °C to +70 °C (extended range) |
| Humidity | 5–95% non-condensing (with conformal coating) |
| Coating | Conformal coating (standard) — UV-traceable |
| Manufacturing | 96-hour burn-in, 100% X-Ray/AOI, premium component selection |
| Power Draw | 8 W (+5 V / +3.3 VDC) |
| Connectors | Front-panel 32-pin terminal block with captive washer screws |
Advantages & Distinctive Features
-
Higher Contact Rating: 6 A continuous (versus 5 A on WROBH1A) — handles larger loads.
-
Higher Inrush Capability: 12 A for 150 ms (versus 10 A for 100 ms) — supports larger solenoids and motors.
-
Integrated AC Snubbers: Built-in snubber circuits for AC inductive loads—eliminates external components, reduces wiring, and extends contact life.
-
Contact Resistance Monitoring: Tracks contact resistance over time—identifies pitted or worn contacts before failure.
-
Longer Electrical Life: 150,000 operations at rated load (versus 100,000) — reduces maintenance frequency.
-
Conformal Coating Standard: Protects against humidity, salt spray, and chemical vapors.
-
Extended Temperature Range: –25 °C to +70 °C operation.
-
Expanded Fault Logging: 750-event log with timestamps.
-
Captive Washer Terminals: Prevents screw loosening due to vibration.
-
Hot-Swappable: No rack power-down for replacement.
-
Direct Retrofit: Replaces WROBH1A series boards with enhanced capabilities.
Application Fields
-
Gas Turbines: Solenoid control, motor starters, valve actuation, alarm annunciation
-
Steam Turbines: Trip solenoid control, motor starters, drain valve control
-
Compressors: Motor starters, solenoid control, surge control valves
-
Generators: Alarm annunciation, motor starters, synchronizing control
-
Balance of Plant: Pump control, fan starters, filter differential pressure alarms
-
Offshore platforms: Salt-spray environments requiring conformal coating
Comparison with WROBH1A and Competitors
| Feature | GE IS2020DRLYH1A | GE IS200WROBH1A | Competitor A | Competitor B |
|---|---|---|---|---|
| Output Channels | 16 | 16 | 8 | 8 |
| Contact Rating | 6 A | 5 A | 2 A | 2 A |
| Inrush Capability | 12 A (150 ms) | 10 A (100 ms) | No | No |
| AC Snubbers | Integrated | External required | External | External |
| Contact Resistance Monitoring | Yes | No | No | No |
| Electrical Life | 150,000 operations | 100,000 operations | 50,000 | 50,000 |
| Coating | Standard | Optional | Optional | Optional |
| Temp Range | –25 to +70 °C | 0 to +60 °C | 0 to +55 °C | 0 to +55 °C |
| Fault Logging | 750 events | 500 events | No | No |
The GE IS2020DRLYH1A offers superior contact rating, inrush capability, integrated AC snubbers, and contact resistance monitoring—making it the ideal relay output solution for demanding turbine control applications.
Selection Guidelines
-
When to choose: Any Mark VIe application requiring high-current relay outputs—especially where 6 A rating, AC inductive loads, or contact resistance monitoring is beneficial.
-
Load Verification: Verify each load ≤6 A continuous; ≤12 A inrush. Integrated AC snubbers handle most inductive loads—verify compatibility with large motors.
-
Contact Resistance Monitoring: Use Toolbox ST to track contact resistance trends—increasing resistance indicates contact wear.
-
Wiring: Use appropriate wire gauge (14–18 AWG) for load currents.
-
Compatibility: Fits all Mark VIe VME64x racks. Requires ControlST v6.5 or higher for full features.
Operational Precautions
-
Wiring: Follow GE wiring diagrams—correct polarity for DC loads. AC loads use integrated snubbers—no external components needed.
-
Load Testing: Test each output with actual load during commissioning—verify contact resistance baseline.
-
Contact Resistance Monitoring: Review contact resistance trends in Toolbox ST—replace relays when resistance doubles from baseline.
-
Inrush Current: Ensure inrush current does not exceed 12 A per channel—excessive inrush can weld contacts.
-
LED Diagnostics: Green = commanded ON; Amber = commanded OFF; Red = fault. Refer to GEH-6920 for blink codes.
-
Fault Log: Access 750-event log via Toolbox ST for post-event analysis.
-
Coating Care: Use GE-approved cleaner; inspect annually under UV.
-
Hot-Swap: Remove/insert slowly under power—processor auto-recognizes new module.
-
Spare Stock: Maintain 1 spare per 3–4 racks.
-
Annual Verification: Cycle relays during outages; verify switching times and contact resistance.
-
Firmware Updates: Ensure the GE IS2020DRLYH1A is in “standby” mode during updates.
-
ESD: Handle by edges only with grounded wrist strap—coating does not protect connectors.
-
Storage: Anti-static bag with desiccant at –40 to +85 °C; rotate every 3 years for coating inspection.

GE IC695PSA040
LENEL LNL-1320
A-B 1746-HSCE
honeywell MC-TDOY22


Reviews