Description
Product Parameters
| Parameter | Specification |
|---|---|
| Brand / Series | GE Mark VIe Speedtronic |
| Model | IS200TBAOH1A |
| Analog Outputs | 16 channels (4–20 mA or 0–10 V, software-selectable per channel) |
| Output Range | 0–20 mA, 4–20 mA, 0–5 V, 0–10 V |
| DAC Resolution | 16-bit with programmable update rate (1–1000 SPS) |
| Accuracy | ±0.1% of full scale (25°C), ±0.2% over full temperature range |
| Load Impedance | 0–750 Ω (current mode), > 2 kΩ (voltage mode) |
| Current Limit | 25 mA per channel (short-circuit protected) |
| Filtering | Programmable low-pass filter (1–50 Hz) |
| Isolation | 1500 VAC (field-to-system) |
| Diagnostics | Open-circuit detection, short-circuit detection, over/under-range monitoring, loop power fault monitoring |
| Status Indication | 16 green LEDs (channel active), 2 red LEDs (diagnostic fault summary) |
| Operating Temperature | –30°C to +65°C |
| Storage Temperature | –55°C to +85°C |
| Mounting | VME rack-mount terminal board with front-panel I/O connector |
| Backplane Interface | VME64x (A24/A32, D16/D32/D64) |
Advantages & Key Features
-
High Channel Density: 16 analog outputs in a single VME slot—double the density of competing 8-channel modules, ideal for turbines with multiple control valves and actuators.
-
Flexible Output Configuration: Each channel supports 4–20 mA or 0–10 V outputs via GE ToolboxST software, accommodating a wide range of field actuators.
-
High Resolution: 16-bit DAC provides precise control for critical turbine parameters such as fuel valve position and steam bypass control.
-
Programmable Filtering: Onboard low-pass filter (1–50 Hz) smooths output signals to reduce mechanical wear on actuators.
-
Comprehensive Diagnostics: Real-time open-circuit, short-circuit, and over/under-range monitoring per channel enable predictive maintenance and fault detection.
-
Short-Circuit Protection: Each output is protected against short circuits and overcurrent conditions, safeguarding both the board and field devices.
-
ToolboxST Integration: Full configuration, calibration, and diagnostics via GE ToolboxST.
-
Drop-In Replacement: Direct replacement for earlier GE analog output terminal boards.
Application Fields
-
Gas & Steam Turbines (GE Frame 6B/7EA/9E/HA): Fuel gas control valves, steam admission valves, inlet guide vane positioners, bypass valves, actuator position control, and variable speed drive control.
-
Combined Cycle Plants: HRSG feedwater control valves, bypass valve positioning, steam temperature control actuators.
-
Compressor Stations: Anti-surge valve control, recycle valve positioning, variable speed compressor control.
-
Aeroderivative Turbines: Fuel control actuators, variable inlet guide vanes, bleed valve control.
Comparison with Competing Products
| Feature | GE IS200TBAOH1A | Competitor A (Emerson Analog) | Competitor B (Siemens Analog) |
|---|---|---|---|
| Analog Outputs | 16 | 8 | 8 |
| Output Types | 4–20 mA, 0–10 V | 4–20 mA only | 4–20 mA, 0–10 V |
| DAC Resolution | 16-bit | 14-bit | 16-bit |
| Accuracy | ±0.1% FS | ±0.2% FS | ±0.15% FS |
| Short-Circuit Protection | Yes | Yes | No |
| Isolation | 1500 VAC | 1000 VAC | 500 VDC |
| Operating Temp | –30°C to +65°C | 0°C to 50°C | 0°C to 60°C |
Key Advantage: IS200TBAOH1A provides double the channel density (16 vs. 8) of competing analog output modules, with flexible output configuration, 16-bit resolution, and comprehensive diagnostics—reducing rack space and simplifying system design for turbine control applications.
Selection Guidelines & Recommendations
-
Output Type: Configure 4–20 mA or 0–10 V per channel in GE ToolboxST to match your field actuators.
-
Load Verification: Ensure connected actuators do not exceed the board’s load impedance capability (0–750 Ω for current, > 2 kΩ for voltage).
-
Filtering: Use 1–10 Hz filtering for smooth actuator response, 20–50 Hz for faster dynamic control.
-
Controller Firmware: Requires Mark VIe processor firmware v6.5 or later.
-
Spare Strategy: Keep one spare per turbine; lead times 6–10 weeks.
-
Retrofit: Direct replacement—regenerate configuration in GE ToolboxST.
Important Cautions
-
No Hot-Swap: De-energize rack before insertion/removal.
-
Output Polarity: Observe correct polarity for current loops—reverse polarity prevents proper actuator operation.
-
Short-Circuit Protection: While protected, sustained short circuits may cause the board to enter thermal shutdown. Investigate wiring faults promptly.
-
Grounding: Connect AGND to Mark VIe system ground at single star point.
-
Shield Termination: Ground output cable shields only at cabinet end.
-
ESD Handling: Use grounded wrist straps; field repair not possible.
-
Filtering Trade-Off: Higher filtering provides smoother output but introduces signal delay—balance based on actuator response requirements.
-
Channel Mapping: Verify field wiring correctly maps to corresponding channel numbers in GE ToolboxST.
-
Power Supply: Ensure the Mark VIe rack power supply provides adequate current for all active output channels (typically 20 mA per current output × 16 channels = 320 mA max).

A-B 1769-OF8C
GE IC693CPU351
A-B 1769-OF8C


Reviews
There are no reviews yet.