Description
Product Parameters
| Parameter | Specification |
|---|---|
| Model | IS220YDIAS1A |
| Manufacturer | GE Energy / Baker Hughes |
| Platform | Mark VIe |
| Type | Terminal board (I/O interface) |
| Compatible Modules | IS220PDIAH1A, IS220PDIAH1B, IS220PDIOH1A, IS220PDIOH1B, IS220PDOAH1A |
| Discrete Input Channels | 32 (when used with input modules) |
| Discrete Output Channels | 32 (when used with output modules) |
| Terminal Type | Screw terminals (pluggable, 2-piece) |
| Wire Gauge | 0.2–2.5 mm² (AWG 24–14) |
| Voltage Rating | 250 VAC / 300 VDC |
| Current Rating | 10 A per terminal |
| Isolation | 1500 V (field-to-backplane via module) |
| LED Indicators | Power, Fuse Status (if applicable) |
| Operating Temperature | -30°C to +65°C |
| Storage Temperature | -40°C to +85°C |
| Humidity | 5% to 95% (non-condensing) |
| Dimensions | Standard Mark VIe terminal board form factor |
| Weight | Approx. 0.4 kg |
| MTBF | > 200,000 hours |
Advantages and Key Features
-
High-Density I/O Interface – The IS220YDIAS1A supports up to 32 discrete input or output channels per terminal board, providing a compact and organized interface for field wiring.
-
Versatile Compatibility – Compatible with multiple Mark VIe discrete I/O modules, including input-only (IS220PDIAH1A, IS220PDIAH1B), output-only (IS220PDOAH1A), and combined I/O (IS220PDIOH1A, IS220PDIOH1B) modules, providing maximum flexibility.
-
Pluggable Terminal Design – The IS220YDIAS1A features a 2-piece pluggable terminal block design, allowing field wiring to be disconnected from the board without removing individual wires, simplifying maintenance and module replacement.
-
Screw Terminal Connections – Provides reliable screw-clamp connections for field wiring, accepting wire gauges from AWG 24 to 14.
-
High Isolation – 1500 V isolation between field wiring and the control backplane (via the I/O module), protecting the control processor from field-side faults.
-
Visual Indication – LED indicators provide immediate visual confirmation of power and fuse status, simplifying troubleshooting.
-
Wide Temperature Range – Rated for -30°C to +65°C, suitable for outdoor and harsh industrial environments.
Application Fields and Use Cases
1. Valve Position Monitoring
The IS220YDIAS1A provides field wiring connections for limit switches on fuel valves, steam admission valves, drain valves, and trip valves. When paired with IS220PDIAH1A or IS220PDIAH1B, it delivers reliable position feedback for control and safety functions.
2. Motor Starter Feedback
Motor starter auxiliary contacts connect to the IS220YDIAS1A, providing status feedback for pumps, fans, compressors, and other auxiliary equipment.
3. Switch and Pushbutton Inputs
Local control stations, mode selectors, and emergency stop pushbuttons connect to the IS220YDIAS1A for operator interface and safety shutdown.
4. Solenoid Valve Control
When paired with output modules (IS220PDOAH1A, IS220PDIOH1A, IS220PDIOH1B), the IS220YDIAS1A provides field wiring for solenoid-operated valves, motor starters, and indicating lights.
5. Alarm Annunciation
The IS220YDIAS1A connects annunciator panels, horns, and indicating lights for operator notification of alarms and abnormal conditions.
6. Retrofit Projects
Used in Mark VIe upgrades from legacy systems to simplify field wiring transitions from older terminal boards.
Comparison with Competing Products
| Feature | IS220YDIAS1A (GE) | IS200YDIAS1A (GE Mark VI) | ABB TU830 (AC 800M) | Siemens 6ES7 392-1AJ00 (S7-400) |
|---|---|---|---|---|
| Platform | Mark VIe | Mark VI (VME) | AC 800M | S7-400 |
| Type | Terminal board | Terminal board | Terminal unit | Terminal block |
| Channels | 32 | 32 | 32 | 32 |
| Terminal Type | Screw, pluggable | Screw, fixed | Screw, pluggable | Screw, fixed |
| Wire Gauge | AWG 24–14 | AWG 22–14 | AWG 24–14 | AWG 24–12 |
| Voltage Rating | 250 VAC / 300 VDC | 250 VAC / 300 VDC | 250 VAC | 250 VAC |
| Isolation | Via module (1500 V) | Via module (1500 V) | Via module (1500 V) | Via module (500 V) |
| LED Indicators | Power, Fuse | Power, Fuse | Limited | None |
| Hot-Swap Support | Yes (via module) | No | Yes | No |
| Pluggable Wiring | Yes | No | Yes | No |
Key Differentiators: The IS220YDIAS1A offers pluggable screw terminal connections, simplifying maintenance compared to the fixed terminal design of the legacy IS200YDIAS1A. It provides similar channel density (32 channels) and is fully compatible with the Mark VIe platform’s hot-swap functionality. The pluggable design allows quick module replacement without rewiring, reducing downtime during maintenance.
Selection Suggestions and Precautions
Selection Criteria
-
Choose the IS220YDIAS1A for Mark VIe discrete I/O applications requiring high-density field wiring connections (32 channels).
-
Ensure compatibility with the specific I/O module type (input, output, or combined I/O) being used. The IS220YDIAS1A is designed to support all Mark VIe discrete modules.
-
Verify the terminal board is correctly matched to the application voltage (24–125 VDC).
Critical Precautions
-
Wiring Connections – Ensure proper wire stripping length (approximately 7–8 mm) for screw terminals. Over-tightening may damage terminals; under-tightening may cause intermittent connections. Recommended torque: 0.5–0.6 N·m.
-
Polarity – For DC applications, observe proper polarity on the IS220YDIAS1A to prevent damage to field devices and incorrect logic states.
-
Common Grounding – Ensure all field devices share a common reference ground to prevent incorrect logic levels. Use the common return terminals on the IS220YDIAS1A as specified in the wiring diagram.
-
Wire Sizing – Use appropriate wire gauge (AWG 24–14) for the IS220YDIAS1A. For long cable runs, use thicker gauge wire to minimize voltage drop.
-
Shielding – Use shielded cables for input signals to prevent noise pickup. Terminate shields at the field device end, not at the IS220YDIAS1A.
-
Fuse Replacement – If the IS220YDIAS1A includes fuses, replace only with the specified type and rating. Do not bypass fuses, as this may damage the module and equipment.
-
Terminal Labeling – Label all field wiring at the IS220YDIAS1A for future maintenance and troubleshooting. Use the terminal designation labels provided with the board.
-
Module Compatibility – Verify the IS220YDIAS1A is compatible with the specific I/O module revision (e.g., IS220PDIAH1A vs. IS220PDIAH1B). While generally intercompatible, confirm with the terminal board documentation.
-
Hot-Swap – When using the IS220YDIAS1A with hot-swappable modules, ensure the module is properly seated before applying field power. Do not force module insertion.
-
Obsolescence – The IS220YDIAS1A is in active production with long-term support. For future projects requiring additional features, evaluate the IS220YDIAS1B or newer variants when available. Keep spare terminal boards for critical installations.

GE IC200ALG630
Schneider LC1-D410M7C
Schneider 140DDI85300
EMERSON PCM-11


Reviews