Description
Key Specifications
| Parameter | Specification |
|---|---|
| Output Channels | 16 discrete outputs (high-side or low-side configurable) |
| Output Type | Solid-state (MOSFET) |
| Output Voltage Rating | 24 VDC nominal (18–32 VDC) |
| Output Current | 2 A per channel (continuous), 5 A per channel (inrush, 100 ms) |
| Total Output Current | 16 A maximum (module total) |
| Output Protection | Short-circuit, overcurrent, over-temperature, inductive load clamp |
| Diagnostic Feedback | Load current monitoring per channel (open/short detection), output state feedback |
| Inductive Load Support | Built-in flyback diodes for inductive loads |
| Isolation | 1500 VDC (output-to-backplane) |
| Diagnostics | 750-event fault log with timestamps (expanded) |
| Operating Temp | –25 °C to +70 °C (extended range) |
| Humidity | 5–95% non-condensing (with conformal coating) |
| Coating | Conformal coating (standard) — UV-traceable |
| Manufacturing | 120-hour burn-in, 100% X-Ray/AOI, military-grade components |
| Form Factor | 6U VME64x (160 × 233 mm), single-slot width |
| Power | 10 W (+5 V / +3.3 VDC) + external 24 VDC field power |
| Connectors | 32-pin terminal block with gold-plated contacts and captive washer screws |
Advantages & Distinctive Features
-
16 High-Capacity Outputs: Controls up to 16 solenoids, valves, or contactors.
-
High Inrush Capability: 5 A per channel for 100 ms handles solenoid inrush.
-
Per-Channel Load Monitoring: Detects open/short circuits and solenoid degradation.
-
Output State Feedback: Provides actual output state to the processor.
-
Inductive Load Clamping: Built-in flyback diodes protect outputs.
-
Short-Circuit Protection: Auto-shutdown with auto-retry.
-
Conformal Coating Standard: Protects against humidity, salt spray, and chemicals.
-
Extended Temperature Range: –25 °C to +70 °C.
-
Expanded Diagnostic Log: 750-event fault log.
-
Military-Grade Manufacturing: 120-hour burn-in, military-grade components.
-
Gold-Plated Captive Washer Terminals: Corrosion-resistant and vibration-proof.
-
Hot-Swappable: No rack power-down for replacement.
-
Direct Retrofit: Replaces older DSVO series boards.
Application Fields
-
Gas Turbines: Trip solenoids, fuel shut-off valves, purge/drain valves, bleed valves
-
Steam Turbines: Emergency stop valves, control valve trip solenoids, drain valves
-
Compressors: Anti-surge blow-off valves, suction/discharge isolation valves
-
Generators: H2 supply shut-off valves, seal oil system valves
-
Offshore platforms: Salt-spray environments requiring conformal coating
-
Nuclear Power Plants: Safety-critical solenoid control
Comparison with DSVOH1A and Competitors
| Feature | GE IS210DSVOH1AA | GE IS210DSVOH1A | Competitor A | Competitor B |
|---|---|---|---|---|
| Output Channels | 16 | 16 | 16 | 16 |
| Continuous Current | 2 A | 2 A | 0.5 A | 2 A |
| Inrush Current | 5 A (100 ms) | 5 A (100 ms) | No | No |
| Load Monitoring | Per-channel | Per-channel | No | No |
| Coating | Standard | Optional | Optional | Optional |
| Temp Range | –25 to +70 °C | 0 to +60 °C | 0 to +55 °C | 0 to +55 °C |
| Fault Logging | 750 events | 500 events | No | No |
Selection Guidelines
-
When to choose: Critical solenoid and valve control requiring environmental protection and expanded diagnostics.
-
When to choose “H1A” instead: For clean, controlled environments where conformal coating is not required.
-
Load Verification: Verify solenoid inrush ≤5 A, holding ≤2 A per channel.
-
Field Power Supply: Provide dedicated 24 VDC field power supply with capacity for all solenoids.
-
Coating Verification: Inspect under UV (365 nm) upon receipt.
-
Compatibility: Fits all Mark VIe VME64x racks. Requires ControlST v6.0 or higher.
Operational Precautions
-
Wiring: Follow GE wiring diagrams—correct polarity for external field power.
-
Field Power: Properly size and fuse external 24 VDC supply (20 A fuse recommended).
-
Load Monitoring: Use Toolbox ST to view per-channel current readings—trending increasing current indicates solenoid wear.
-
Short-Circuit Testing: Simulate short to verify auto-shutdown and auto-retry.
-
LED Diagnostics: Green = output on; Amber = output off with fault; Red = module fault.
-
Fault Log: Access 750-event log via Toolbox ST.
-
Coating Care: Use GE-approved cleaner; inspect annually under UV.
-
Hot-Swap: Remove/insert slowly under power.
-
Spare Stock: Maintain 1 spare per 3–4 racks.
-
Firmware Updates: Ensure the GE IS210DSVOH1AA is in “standby” mode during updates.
-
ESD: Handle by edges with grounded wrist strap.
-
Storage: Anti-static bag with desiccant at –40 to +85 °C; rotate every 3 years.

TRICONEX 9563-810
LEM LC1000-S/SP7
FOXBORO P0926MX


Reviews