GE IS210DSVOH1AA

¥999.00

The GE IS210DSVOH1AA is a VMEbus terminal board manufactured by General Electric for the Mark VIe distributed control system (DCS). This board is a dedicated Discrete Solenoid and Valve Output module, designed to provide high-current discrete outputs for controlling solenoids, valves, contactors, and actuators in turbine control applications. The GE IS210DSVOH1AA combines the robust output capabilities of the “H1A” series with the “AA” suffix enhancements—typically indicating military-grade components, extended burn-in (120 hours), 100% X-ray/AOI inspection, and conformal coating as standard for maximum reliability in harsh environments. This board is designed for critical solenoid and valve control applications requiring absolute reliability.

Category:

Description

Key Specifications

Parameter Specification
Output Channels 16 discrete outputs (high-side or low-side configurable)
Output Type Solid-state (MOSFET)
Output Voltage Rating 24 VDC nominal (18–32 VDC)
Output Current 2 A per channel (continuous), 5 A per channel (inrush, 100 ms)
Total Output Current 16 A maximum (module total)
Output Protection Short-circuit, overcurrent, over-temperature, inductive load clamp
Diagnostic Feedback Load current monitoring per channel (open/short detection), output state feedback
Inductive Load Support Built-in flyback diodes for inductive loads
Isolation 1500 VDC (output-to-backplane)
Diagnostics 750-event fault log with timestamps (expanded)
Operating Temp –25 °C to +70 °C (extended range)
Humidity 5–95% non-condensing (with conformal coating)
Coating Conformal coating (standard) — UV-traceable
Manufacturing 120-hour burn-in, 100% X-Ray/AOI, military-grade components
Form Factor 6U VME64x (160 × 233 mm), single-slot width
Power 10 W (+5 V / +3.3 VDC) + external 24 VDC field power
Connectors 32-pin terminal block with gold-plated contacts and captive washer screws

Advantages & Distinctive Features

  • 16 High-Capacity Outputs: Controls up to 16 solenoids, valves, or contactors.

  • High Inrush Capability: 5 A per channel for 100 ms handles solenoid inrush.

  • Per-Channel Load Monitoring: Detects open/short circuits and solenoid degradation.

  • Output State Feedback: Provides actual output state to the processor.

  • Inductive Load Clamping: Built-in flyback diodes protect outputs.

  • Short-Circuit Protection: Auto-shutdown with auto-retry.

  • Conformal Coating Standard: Protects against humidity, salt spray, and chemicals.

  • Extended Temperature Range: –25 °C to +70 °C.

  • Expanded Diagnostic Log: 750-event fault log.

  • Military-Grade Manufacturing: 120-hour burn-in, military-grade components.

  • Gold-Plated Captive Washer Terminals: Corrosion-resistant and vibration-proof.

  • Hot-Swappable: No rack power-down for replacement.

  • Direct Retrofit: Replaces older DSVO series boards.


Application Fields

  • Gas Turbines: Trip solenoids, fuel shut-off valves, purge/drain valves, bleed valves

  • Steam Turbines: Emergency stop valves, control valve trip solenoids, drain valves

  • Compressors: Anti-surge blow-off valves, suction/discharge isolation valves

  • Generators: H2 supply shut-off valves, seal oil system valves

  • Offshore platforms: Salt-spray environments requiring conformal coating

  • Nuclear Power Plants: Safety-critical solenoid control


Comparison with DSVOH1A and Competitors

Feature GE IS210DSVOH1AA GE IS210DSVOH1A Competitor A Competitor B
Output Channels 16 16 16 16
Continuous Current 2 A 2 A 0.5 A 2 A
Inrush Current 5 A (100 ms) 5 A (100 ms) No No
Load Monitoring Per-channel Per-channel No No
Coating Standard Optional Optional Optional
Temp Range –25 to +70 °C 0 to +60 °C 0 to +55 °C 0 to +55 °C
Fault Logging 750 events 500 events No No

Selection Guidelines

  • When to choose: Critical solenoid and valve control requiring environmental protection and expanded diagnostics.

  • When to choose “H1A” instead: For clean, controlled environments where conformal coating is not required.

  • Load Verification: Verify solenoid inrush ≤5 A, holding ≤2 A per channel.

  • Field Power Supply: Provide dedicated 24 VDC field power supply with capacity for all solenoids.

  • Coating Verification: Inspect under UV (365 nm) upon receipt.

  • Compatibility: Fits all Mark VIe VME64x racks. Requires ControlST v6.0 or higher.


Operational Precautions

  1. Wiring: Follow GE wiring diagrams—correct polarity for external field power.

  2. Field Power: Properly size and fuse external 24 VDC supply (20 A fuse recommended).

  3. Load Monitoring: Use Toolbox ST to view per-channel current readings—trending increasing current indicates solenoid wear.

  4. Short-Circuit Testing: Simulate short to verify auto-shutdown and auto-retry.

  5. LED Diagnostics: Green = output on; Amber = output off with fault; Red = module fault.

  6. Fault Log: Access 750-event log via Toolbox ST.

  7. Coating Care: Use GE-approved cleaner; inspect annually under UV.

  8. Hot-Swap: Remove/insert slowly under power.

  9. Spare Stock: Maintain 1 spare per 3–4 racks.

  10. Firmware Updates: Ensure the GE IS210DSVOH1AA is in “standby” mode during updates.

  11. ESD: Handle by edges with grounded wrist strap.

  12. Storage: Anti-static bag with desiccant at –40 to +85 °C; rotate every 3 years.