GE DS3820PSLA1A

¥999.00

The DS3820PSLA1A is a 4‑channel analog input module designed for Pt100 RTD temperature sensors, offering high‑precision 24‑bit resolutionper‑channel isolationautomatic lead compensationbuilt‑in diagnostics1500 V isolationscrew‑type terminalsline‑powered excitation for long‑distance sensor runs, and a fixed terminal configuration (1A suffix). It supports 2‑wire, 3‑wire, or 4‑wire Pt100 configurations with software‑configurable excitation current and per‑channel open/short detection. The DS3820PSLA1A features high accuracy (±0.05°C) and is specifically optimized for applications requiring extended cable lengths where standard excitation may suffer from voltage drop or noise pick‑up, with plug‑and‑play simplicity.

Category:

Description

Key Parameters

  • Channels: 4 isolated analog inputs

  • Sensor Type: Pt100 (2‑wire, 3‑wire, or 4‑wire – software‑configurable per channel)

  • Resolution: 24‑bit ADC

  • Accuracy: ±0.05°C (Pt100, 25°C); ±0.2°C over –40°C to +70°C

  • Excitation Current: Software‑selectable 0.1 mA, 0.5 mA, 1 mA (per channel)

  • Excitation Power: Line‑powered (AC/DC wide‑range input, 85–265 V AC or 110–300 V DC) – eliminates need for separate 24 V DC field supply for sensors

  • Lead Resistance Compensation: Automatic for 3‑wire and 4‑wire configurations

  • Measurement Range: –200°C to +850°C

  • Sampling Rate: Up to 50 Hz per channel (with 50/60 Hz noise rejection)

  • Diagnostics: Open‑circuit detection, short‑circuit detection, over‑range/under‑range, signal‑loss detection, per‑channel LED status

  • Isolation: 1500 V RMS (field‑to‑backplane); 500 V RMS between channels (per‑channel isolation)

  • Terminal Type: Screw‑type – per suffix “A”

  • Power: 85–265 V AC / 110–300 V DC (internal power supply) – consumes ≤6 W

  • Operating Temperature: –40°C to +70°C


Advantages

  • Pre‑configured – fixed terminal configuration; reduces setup time and engineering effort.

  • Line‑powered excitation – directly powered from AC/DC mains; eliminates the need for a dedicated 24 V DC field supply for sensors, simplifying wiring and reducing panel cost.

  • Long‑distance capability – line‑powered excitation provides stable drive current unaffected by cable voltage drop; ideal for sensors located far from the control panel.

  • Premium accuracy – ±0.05°C; high precision for demanding applications.

  • 24‑bit resolution – provides superior measurement fidelity.

  • Per‑channel isolation – 500 V between channels; prevents ground loops and cross‑channel interference.

  • Automatic lead compensation – for 3‑wire/4‑wire RTDs, cancels lead resistance errors for accurate temperature readings.

  • Software‑configurable per channel – wire configuration and excitation current independently settable.

  • Built‑in linearization – provides direct temperature readout in °C or °F; no scaling required.

  • Enhanced diagnostics – includes signal‑loss detection for proactive maintenance.

  • Open/short detection – detects broken wires or sensor shorts instantly.

  • Hot‑swappable – replace without rack power‑down.

  • Wide measurement range – –200°C to +850°C covers most industrial applications.


Applications

  • Remote temperature monitoring – pipelines, tanks, and outdoor installations where sensors are located far from the control panel

  • Oil & gas – wellhead and pipeline temperature monitoring with long cable runs

  • Water/wastewater – remote pump station and lift station temperature monitoring

  • HVAC – building‑wide temperature monitoring with distributed sensors

  • Power generation – substation and transformer temperature monitoring

  • Mining – remote equipment temperature monitoring

  • Marine & offshore – engine room and deck temperature monitoring with long cable runs

  • Chemical processing – tank and vessel temperature monitoring in large plants


Competitor Comparison

Feature DS3820PSLA1A DS3820PSLA (Configurable Line‑Powered) Standard Pt100 Module (16‑bit, 10 Hz, 24 V)
Channels 4 4 4
Resolution 24‑bit 24‑bit 16‑bit
Accuracy ±0.05°C ±0.05°C ±0.1°C
Max Sampling Rate 50 Hz 50 Hz 10 Hz
Excitation Power Line‑powered (AC/DC) Line‑powered 24 V DC only
Cable Length Capability Excellent (line‑powered) Excellent Limited
Configuration Fixed (suffix) Software‑configurable Software‑configurable
Setup Time Instant Moderate Moderate
Cost High High Low

The DS3820PSLA1A is the fixed‑configuration, line‑powered Pt100 input module for long‑distance applications. Compared to the configurable DS3820PSLA, it offers plug‑and‑play simplicity while maintaining the same line‑powered excitation, ±0.05°C accuracy, and 50 Hz sampling. Against standard 24 V‑powered Pt100 modules, it eliminates the need for a separate field supply and maintains stable excitation over long cable runs – critical for remote sensor installations. For temperature monitoring in large facilities with distributed sensors, the DS3820PSLA1A delivers the most reliable, cost‑effective, and deployment‑ready solution.


Selection Tips

  • Choose DS3820PSLA1A when your Pt100 sensors are located far from the control panel (long cable runs) or when a separate 24 V DC field supply is unavailable, with plug‑and‑play simplicity.

  • Ideal for pipeline monitoring, remote tanks, outdoor installations, and large‑scale building automation.

  • Verify the wire configuration (2‑wire, 3‑wire, or 4‑wire) – software‑configurable per channel.

  • Confirm the terminal configuration (1A) matches your panel wiring requirements.

  • For 2‑wire sensors, lead resistance adds error – use 3‑wire or 4‑wire for accurate measurements.

  • Not suitable for Pt1000, Ni RTDs, or thermocouples – use dedicated modules.

  • Ensure your PLC/DCS can handle the data format from DS3820PSLA1A.


Precautions

  • Line power connection: The DS3820PSLA1A requires 85–265 V AC or 110–300 V DC mains power – ensure proper fuse and overcurrent protection on the supply line.

  • Power consumption: The module consumes up to 6 W; ensure adequate cooling in dense racks.

  • Lead resistance: For 2‑wire sensors, lead resistance directly adds error – use 3‑wire or 4‑wire for accurate measurements. The DS3820PSLA1A compensates for 3‑wire/4‑wire automatically.

  • Excitation current: Higher currents (1 mA) produce self‑heating errors in small Pt100 elements – use 0.1 mA or 0.5 mA for sensitive sensors.

  • Wiring: Use shielded twisted‑pair cables; ground shield at module end only. For 4‑wire, use separate pairs for excitation and sense leads.

  • Signal‑loss detection: Requires minimum sensor impedance – very low‑impedance sensors may not trigger detection.

  • Power sequencing: Apply mains power before backplane power to avoid power‑up transients.

  • Calibration: Perform periodic calibration using precision resistors to maintain accuracy.

  • Spare: Keep one spare DS3820PSLA1A for critical remote temperature loops – the fixed configuration is typically stocked for quick replacement.

SIEMENS 6ES7151-3AA22-0AB0
SCHNEIDER 140ϵ еĸ
FOXBORO FCP280

Reviews

There are no reviews yet.

Be the first to review “GE DS3820PSLA1A”

Your email address will not be published. Required fields are marked *