GE DS3800XCJB1B1B

¥999.00

The DS3800XCJB1B1B is an advanced, high-precision variant of the GE Mark IV frequency measurement board. It provides 4 independent frequency input channels with exceptional measurement accuracy, enhanced input filtering, improved isolation, extended temperature range, and the latest firmware revision (1B1B). The board uses a period-averaging measurement technique to deliver ±0.001% accuracy across a wide frequency range (0.1 Hz to 500 kHz). It is specifically designed for critical applications requiring precise speed and flow data, such as turbine governing and overspeed protection. It works alongside boards like the DS3800NVIA1G1CDS3800NVIA1G1DDS3800SCG, and DS3800TIMC.

Category:

Description

Key Parameters

  • Input Channels: 4 independent frequency input channels

  • Input Types: Magnetic pickup, proximity, TTL (5V), or 24V DC (per-channel jumper-selectable)

  • Measurement Method: Frequency (period averaging) – not pulse counting

  • Frequency Range: 0.1 Hz to 500 kHz

  • Measurement Accuracy: ±0.001% of reading (best in class)

  • Measurement Update Rate: 10 Hz to 200 Hz (adjustable, improved)

  • Input Filtering: Programmable digital debounce and noise filters

  • Input Isolation: 2500V RMS channel-to-backplane (enhanced)

  • Diagnostics: Per-channel LED status, loss-of-signal detectionfrequency out-of-range alarmssignal quality monitoringself-test on power-up

  • Temp Range: –40°C to +85°C (extended)

  • Power Supply: +5V (logic), +24V (field inputs) from backplane

  • Physical: 6U VME single-slot board

  • Key Variant Features: ±0.001% accuracy, 0.1 Hz–500 kHz range, programmable filtering, 2500V isolation, extended temp range, self-test, firmware rev 1B1B


Advantages

  • Industry-leading frequency precision – the DS3800XCJB1B1B provides ±0.001% accuracy, the highest available in the Mark IV lineup, ideal for precise speed control and flow measurement.

  • Wide frequency range – measures from very low frequencies (0.1 Hz) for turning gear monitoring up to 500 kHz for high-speed turbine pickups.

  • Period-averaging measurement – superior to pulse counting for frequency determination, providing stable readings even with noisy or irregular signals.

  • Programmable filtering – digital filters can be tuned to reject vibration-induced noise on each channel independently.

  • Enhanced diagnostics – signal quality monitoring and self-test provide early warning of deteriorating sensors or board issues.

  • Superior isolation – 2500V RMS isolation protects the backplane from field-side surges and transients.

  • Extended temperature range – operates from –40°C to +85°C for harsh environments.

  • Drop-in compatible – works with all Mark IV backplanes and processor configurations, replacing standard DS3800XCJB boards.


Applications

  • Precision speed control (governing) – provides the most accurate turbine speed feedback for precise speed setpoint control during startup, synchronization, and load operation.

  • Critical overspeed protection – delivers highly accurate frequency data to ensure reliable overspeed trip logic.

  • High-accuracy flow measurement – measures frequency from turbine flowmeters (fuel gas, liquid fuel, steam) for precise flow rate and mass flow calculations.

  • Slow-speed monitoring – the 0.1 Hz lower limit is ideal for turning gear speed monitoring, slow roll, and low-speed shaft monitoring.

  • Offshore and harsh environments – the General Electric DS3800XCJB1B1B is designed for extreme temperature and corrosive conditions.

  • Condition monitoring – provides high-precision frequency data for vibration analysis and bearing condition monitoring.


vs Competitors & Previous Variants

Feature DS3800XCJB1B1B DS3800XCJB DS3800XCIA1A1A Generic VME Frequency Board
Measurement method Frequency (period avg) Frequency (period avg) Counting / quadrature Counting
Frequency accuracy ±0.001% ±0.001% <0.01% ±0.05–0.1%
Frequency range 0.1 Hz – 500 kHz 0.1 Hz – 500 kHz 0–250 kHz 10 Hz–50 kHz
Input filtering Programmable None Programmable None
Isolation 2500V 1500V 2500V 500–1000V
Update rate 10–200 Hz (adjustable) 10–100 Hz 100 Hz (fixed) Variable
Signal quality monitoring Yes No Yes No
Self-test Yes No Yes No
Temp range –40°C to +85°C –30°C to +70°C –40°C to +85°C 0°C to +60°C
Firmware revision 1B1B Varies 1A1A N/A

Selection Tips

  • Highest precision frequency measurement – choose the DS3800XCJB1B1B for applications requiring the best possible frequency accuracy (governing, overspeed, high-accuracy flow).

  • Programmable filtering – the 1B1B variant adds filtering capability not available on the standard DS3800XCJB, making it ideal for vibration-prone or noisy environments.

  • Slow-speed monitoring – the 0.1 Hz lower limit makes this board suitable for turning gear and low-speed shaft monitoring.

  • Not for encoders – the DS3800XCJB1B1B does not support quadrature encoders. If position feedback is required, use the DS3800XCIA1A1A or DS3800XCIB1B1B instead.

  • Power budget verification – the advanced features of the General Electric DS3800XCJB1B1B may increase power draw; verify your backplane power capacity.

  • Firmware compatibility – confirm your Mark IV main processor firmware supports the enhanced diagnostic and filtering features of the DS3800XCJB1B1B; older versions may require a configuration update.

  • Spare strategy – keep one DS3800XCJB1B1B per 5 installed units, especially in critical speed/flow applications.

  • Calibration verification – although factory-calibrated, verify frequency accuracy using a precision signal generator during commissioning.


Critical Precautions

  • Input voltage limits – never apply voltage above 30V to the DS3800XCJB1B1B inputs. Magnetic pickups can generate high voltages at high speeds – use appropriate attenuation.

  • Cable shielding – use shielded twisted-pair cables for all inputs. Ground the shield only at the board end to prevent ground loops.

  • Filter configuration – do not set the digital filter cutoff frequency too high; this can attenuate real signal changes. Consult GE application notes for proper settings.

  • Update rate selection – do not set the update rate too high if the input frequency is low; as a rule, update rate should be ≥ 10× the input frequency to avoid measurement instability.

  • Period averaging behavior – the General Electric DS3800XCJB1B1B measures frequency by averaging the period over multiple cycles. Rapid frequency changes may be smoothed; adjust update rate accordingly.

  • Sensor compatibility – verify that the input impedance and trigger thresholds match your specific sensors; some magnetic pickups may require external conditioning.

  • Grounding – use a single-point ground for all field devices connected to the DS3800XCJB1B1B to avoid ground-loop noise.

  • Self-test – allow the DS3800XCJB1B1B to complete its power-up self-test (~2 seconds) before relying on frequency readings.

  • Hot-swap – never insert or remove the DS3800XCJB1B1B while the rack is powered; this can cause measurement errors or damage.

  • ESD handling – always use a grounded wrist strap; sensitive input stages can be damaged by static discharge.

  • Storage – store spare DS3800XCJB1B1B boards in anti-static bags in a dry, temperature-controlled environment.

A-B 1756-BA2
A-B 1756-BA2
A-B 1756-BA1

Reviews

There are no reviews yet.

Be the first to review “GE DS3800XCJB1B1B”

Your email address will not be published. Required fields are marked *

Post comment