The DS3800NPOC1C1A is a revision of General Electric’s Mark V series Fan/Exhaust Control board, designed for standard-voltage DC applications with a solid-state-primary hybrid output configuration. The suffix “1C1A” indicates Revision C firmware with enhanced 16-bit ADC (±1°C accuracy), standard temperature components (0°C to +60°C), 3A solid-state outputs5A mechanical relay outputs, and 8 thermocouple input channels—with no tachometer feedback.

The DS3800NPOC1C1A builds upon the base model with improved temperature accuracy (16-bit vs. 12-bit ADC) and Revision C firmware enhancements, while maintaining the higher-current solid-state outputs (3A), 5A relay outputs, and full thermocouple monitoring.

Category:

Description

Key Technical Parameters

Parameter Specification
Manufacturer General Electric (GE)
Series Mark V (Speedtronic)
Full Model DS3800NPOC1C1A
Power Supply +5V DC @ 4.5A, +15V DC @ 0.8A, -15V DC @ 0.6A
Temperature Inputs 8 thermocouple channels (Type J/K/T, 16-bit ADC, ±1°C accuracy)
SS Outputs 8 solid-state relays, 3A continuous @ 24–48VDC
Relay Outputs 4 mechanical relays, 5A continuous @ 115VAC/30VDC (surge 10A)
Tachometer Inputs None
Communication Mark V proprietary parallel backplane bus
Operating Temperature 0°C to +60°C
LED Indicators Power, SS Run (8x green), Relay Run (4x amber), Over-Temp Alarm, Backplane Active

Advantages and Distinctive Features

  • Solid-State-Primary Hybrid Architecture: 8 solid-state DC outputs (3A) + 4 high-current relays (5A) on a single board.

  • Full 8 Thermocouple Inputs: Comprehensive temperature monitoring.

  • Improved Temperature Accuracy (16-bit ADC): ±1°C accuracy—double the precision of the base 12-bit (±2°C) model.

  • Enhanced Cold-Junction Compensation (Revision C): Improved temperature measurement reliability.

  • Higher Solid-State Current (3A): Supports larger DC fans compared to 2A boards.

  • Higher Relay Current (5A): Supports larger AC/DC auxiliary loads compared to 3A boards.

  • Silent, Maintenance-Free Solid-State Outputs: Unlimited cycle life for DC fans.

  • Relay Auxiliary Outputs: 2500V galvanic isolation for AC/DC auxiliary loads.

  • Low EMI Emissions: Solid-state outputs minimize interference with sensitive cards.


Typical Application Fields

  • Mixed Fan Cabinets: Where larger DC fans and high-power AC/DC auxiliary devices coexist.

  • Climate-Controlled Indoor Installations: 0°C to +60°C range.

  • Upgrade from Base NPOC: For improved temperature accuracy.


Comparison with Related Models

Feature DS3800NPOC1C1A DS3800NPOC (Base) DS3800NPDA DS3800NPID1D1E
SS Outputs 8 × 3A 8 × 3A 8 × 3A 8 × 3A
Relay Outputs 4 × 5A 4 × 5A 4 × 5A 4 × 5A
T/C Inputs 8 8 8 4
Tach Inputs None None 2 channels 2 channels
ADC Resolution 16-bit (±1°C) 12-bit (±2°C) 12-bit (±2°C) 24-bit (±0.5°C)
Predictive Maintenance No No No Yes
Operating Temp 0°C to +60°C 0°C to +60°C 0°C to +60°C -40°C to +85°C
Firmware C A/B A/B D
Cost Medium-High Medium High Ultra-Premium

Selection Recommendations

  • Choose the DS3800NPOC1C1A if:

    • You need 8 solid-state DC outputs (3A) for larger main fans.

    • You also need 4 high-current mechanical relay outputs (5A) for auxiliary devices.

    • Your cabinet uses 8 thermocouple sensors for temperature monitoring.

    • You want improved temperature accuracy (±1°C).

    • You do not require tachometer feedback or RTD inputs.

    • You have a climate-controlled environment (0°C to +60°C).

  • Choose the DS3800NPDA if: You need tachometer feedback with the same outputs.

  • Choose the DS3800NPID1D1E if: You need 24-bit ADC, predictive maintenance, tachometer feedback, and extreme temperature range (-40°C to +85°C).


Critical Precautions

  • ESD Protection: Always wear a grounded wrist strap.

  • DC Polarity (SS): Solid-state outputs are DC-only and polarity-sensitive—reverse polarity destroys the MOSFET.

  • SS Voltage Limit: Do not exceed 48VDC—AC voltages cause catastrophic failure.

  • SS Current Limitation: Rated at 3A continuous. Verify fan current does not exceed this limit.

  • High-Voltage/Current Hazard (Relay): Relay outputs switch 115VAC/5A—lethal. Use proper insulation.

  • Relay Inductive Derating: For inductive loads, derate from 5A to 3.5A or use RC snubbers.

  • No Tachometer Inputs: Do not connect speed sensors.

  • No Hot-Swap: Always depower the rack before insertion/removal.

  • Slot Assignment: Install in slots 8–10 (auxiliary I/O).

  • CPU Dependency: If backplane communication is lost, the board defaults to 100% fan speed.

  • Firmware Compatibility: Revision C firmware is compatible with Mark V CPU firmware v4.0 and above. For v3.x, the enhanced ADC features may be partially disabled—confirm compatibility before purchasing.

ABB 3HAC044075-001/01
A-B 1746-IB16
A-B 1769-ECL