Description
Key Technical Parameters
| Parameter | Specification |
|---|---|
| Manufacturer | General Electric (GE) |
| Series | Mark V (Speedtronic) |
| Full Model | DS3800NPOC1C1A |
| Power Supply | +5V DC @ 4.5A, +15V DC @ 0.8A, -15V DC @ 0.6A |
| Temperature Inputs | 8 thermocouple channels (Type J/K/T, 16-bit ADC, ±1°C accuracy) |
| SS Outputs | 8 solid-state relays, 3A continuous @ 24–48VDC |
| Relay Outputs | 4 mechanical relays, 5A continuous @ 115VAC/30VDC (surge 10A) |
| Tachometer Inputs | None |
| Communication | Mark V proprietary parallel backplane bus |
| Operating Temperature | 0°C to +60°C |
| LED Indicators | Power, SS Run (8x green), Relay Run (4x amber), Over-Temp Alarm, Backplane Active |
Advantages and Distinctive Features
-
Solid-State-Primary Hybrid Architecture: 8 solid-state DC outputs (3A) + 4 high-current relays (5A) on a single board.
-
Full 8 Thermocouple Inputs: Comprehensive temperature monitoring.
-
Improved Temperature Accuracy (16-bit ADC): ±1°C accuracy—double the precision of the base 12-bit (±2°C) model.
-
Enhanced Cold-Junction Compensation (Revision C): Improved temperature measurement reliability.
-
Higher Solid-State Current (3A): Supports larger DC fans compared to 2A boards.
-
Higher Relay Current (5A): Supports larger AC/DC auxiliary loads compared to 3A boards.
-
Silent, Maintenance-Free Solid-State Outputs: Unlimited cycle life for DC fans.
-
Relay Auxiliary Outputs: 2500V galvanic isolation for AC/DC auxiliary loads.
-
Low EMI Emissions: Solid-state outputs minimize interference with sensitive cards.
Typical Application Fields
-
Mixed Fan Cabinets: Where larger DC fans and high-power AC/DC auxiliary devices coexist.
-
Climate-Controlled Indoor Installations: 0°C to +60°C range.
-
Upgrade from Base NPOC: For improved temperature accuracy.
Comparison with Related Models
| Feature | DS3800NPOC1C1A | DS3800NPOC (Base) | DS3800NPDA | DS3800NPID1D1E |
|---|---|---|---|---|
| SS Outputs | 8 × 3A | 8 × 3A | 8 × 3A | 8 × 3A |
| Relay Outputs | 4 × 5A | 4 × 5A | 4 × 5A | 4 × 5A |
| T/C Inputs | 8 | 8 | 8 | 4 |
| Tach Inputs | None | None | 2 channels | 2 channels |
| ADC Resolution | 16-bit (±1°C) | 12-bit (±2°C) | 12-bit (±2°C) | 24-bit (±0.5°C) |
| Predictive Maintenance | No | No | No | Yes |
| Operating Temp | 0°C to +60°C | 0°C to +60°C | 0°C to +60°C | -40°C to +85°C |
| Firmware | C | A/B | A/B | D |
| Cost | Medium-High | Medium | High | Ultra-Premium |
Selection Recommendations
-
Choose the DS3800NPOC1C1A if:
-
You need 8 solid-state DC outputs (3A) for larger main fans.
-
You also need 4 high-current mechanical relay outputs (5A) for auxiliary devices.
-
Your cabinet uses 8 thermocouple sensors for temperature monitoring.
-
You want improved temperature accuracy (±1°C).
-
You do not require tachometer feedback or RTD inputs.
-
You have a climate-controlled environment (0°C to +60°C).
-
-
Choose the DS3800NPDA if: You need tachometer feedback with the same outputs.
-
Choose the DS3800NPID1D1E if: You need 24-bit ADC, predictive maintenance, tachometer feedback, and extreme temperature range (-40°C to +85°C).
Critical Precautions
-
ESD Protection: Always wear a grounded wrist strap.
-
DC Polarity (SS): Solid-state outputs are DC-only and polarity-sensitive—reverse polarity destroys the MOSFET.
-
SS Voltage Limit: Do not exceed 48VDC—AC voltages cause catastrophic failure.
-
SS Current Limitation: Rated at 3A continuous. Verify fan current does not exceed this limit.
-
High-Voltage/Current Hazard (Relay): Relay outputs switch 115VAC/5A—lethal. Use proper insulation.
-
Relay Inductive Derating: For inductive loads, derate from 5A to 3.5A or use RC snubbers.
-
No Tachometer Inputs: Do not connect speed sensors.
-
No Hot-Swap: Always depower the rack before insertion/removal.
-
Slot Assignment: Install in slots 8–10 (auxiliary I/O).
-
CPU Dependency: If backplane communication is lost, the board defaults to 100% fan speed.
-
Firmware Compatibility: Revision C firmware is compatible with Mark V CPU firmware v4.0 and above. For v3.x, the enhanced ADC features may be partially disabled—confirm compatibility before purchasing.

ABB 3HAC044075-001/01
A-B 1746-IB16
A-B 1769-ECL