GE DS3800NOTA1A1A

¥999.00

The DS3800NOTA1A1A is the baseline revision of General Electric’s Mark V series Fan/Exhaust Control board, designed for standard-voltage DC applications with a solid-state-primary hybrid output configuration. The suffix “1A1A” indicates Revision A firmware (baseline), standard 12-bit ADC (±2°C accuracy), and standard temperature components (0°C to +60°C). This board provides:

  • 8 solid-state outputs (2A @ 24–48VDC) for DC fan control

  • 4 mechanical relays (3A @ 115VAC / 30VDC) for AC/DC auxiliary control

  • 8 thermocouple input channels for temperature monitoring

  • No tachometer feedback capability

The DS3800NOTA1A1A is the original, unmodified version of this hybrid board—ideal for replacing like-for-like in legacy systems that require both solid-state DC outputs and relay auxiliaries with full temperature monitoring.

Category:

Description

Key Technical Parameters

Parameter Specification
Manufacturer General Electric (GE)
Series Mark V (Speedtronic)
Full Model DS3800NOTA1A1A
Power Supply +5V DC @ 3.8A, +15V DC @ 0.7A, -15V DC @ 0.5A
Temperature Inputs 8 thermocouple channels (12-bit ADC, ±2°C accuracy)
SS Outputs 8 solid-state relays, 2A continuous @ 24–48VDC
Relay Outputs 4 mechanical relays, 3A continuous @ 115VAC/30VDC (surge 5A)
Tachometer Inputs None
Communication Mark V proprietary parallel backplane bus
Operating Temperature 0°C to +60°C
LED Indicators Power, SS Run (8x green), Relay Run (4x amber), Over-Temp Alarm, Backplane Active

Advantages and Distinctive Features

  • Solid-State-Primary Hybrid Architecture: 8 solid-state DC outputs + 4 mechanical relays on a single board.

  • Full 8 Thermocouple Inputs: Comprehensive temperature monitoring.

  • Baseline Revision A: The original version of this board—ideal for direct replacement in legacy systems.

  • Silent, Maintenance-Free Solid-State Outputs: Unlimited cycle life for DC fans.

  • Relay Auxiliary Outputs: 2500V galvanic isolation for AC/DC auxiliary loads.

  • Low EMI Emissions: Solid-state outputs minimize interference with sensitive cards.

  • CPU-Dependent Operation: No onboard logic—simple and cost-effective.


Typical Application Fields

  • Mixed Fan Cabinets: Where DC fans are primary with AC/DC auxiliary devices.

  • Climate-Controlled Indoor Installations: 0°C to +60°C range.

  • Legacy System Replacements: Direct drop-in replacement for original DS3800NOTA boards.


Comparison with Related Models

Feature DS3800NOTA1A1A DS3800NOTA (Base) DS3800NOAB DS3800NMSA
SS Outputs 8 × 2A 8 × 2A 8 × 2A 8 × 2A
Relay Outputs 4 × 3A 4 × 3A 4 × 3A 4 × 3A
T/C Inputs 8 8 8 8
Tach Inputs None None 2 channels None
ADC Resolution 12-bit (±2°C) 12-bit (±2°C) 12-bit (±2°C) 12-bit (±2°C)
Operating Temp 0°C to +60°C 0°C to +60°C 0°C to +60°C 0°C to +60°C
Firmware A Unknown A/B A/B
Cost Medium Medium Medium Medium

Selection Recommendations

  • Choose the DS3800NOTA1A1A if:

    • You need 8 solid-state DC outputs (2A) for main fans.

    • You also need 4 mechanical relay outputs (AC/DC) for auxiliary devices.

    • Your cabinet uses 8 temperature sensors for comprehensive monitoring.

    • You do not require tachometer feedback.

    • You have a climate-controlled environment (0°C to +60°C).

    • You need a direct replacement for an existing DS3800NOTA board.

  • Choose the DS3800NOAB if: You need tachometer feedback with the same hybrid outputs.


Critical Precautions

  • ESD Protection: Always wear a grounded wrist strap.

  • DC Polarity (SS): Solid-state outputs are DC-only and polarity-sensitive—reverse polarity destroys the MOSFET.

  • SS Voltage Limit: Do not exceed 48VDC—AC voltages cause catastrophic failure.

  • High-Voltage/Current Hazard (Relay): Relay outputs switch 115VAC/3A—lethal. Use proper insulation.

  • Relay Inductive Derating: For inductive loads, derate from 3A to 2A or use RC snubbers.

  • No Tachometer Inputs: Do not connect speed sensors.

  • No Hot-Swap: Always depower the rack before insertion/removal.

  • Slot Assignment: Install in slots 8–10 (auxiliary I/O).

  • CPU Dependency: If backplane communication is lost, the board defaults to 100% fan speed.

  • Firmware Compatibility: The DS3800NOTA1A1A is compatible with all Mark V CPU firmware versions (v3.x and above). No specific CPU upgrade is needed.