GE DS3800NOCB1B1B

¥999.00

The DS3800NOCB1B1B is a specialized revision of General Electric’s Mark V series Fan/Exhaust Control board, designed for standard-voltage DC applications with a solid-state-primary hybrid output configuration. The suffix “1B1B” indicates Revision B firmware with enhanced 16-bit ADC (±1°C accuracy), extended temperature components (-20°C to +65°C), 2A solid-state outputs5A mechanical relay outputs, and 4 thermocouple input channels—with no tachometer feedback.

The DS3800NOCB1B1B is distinguished from the “NOCA” series by its higher relay current capacity (5A vs. 3A), making it suitable for applications requiring more powerful AC/DC auxiliary loads.

Category:

Description

Key Technical Parameters

Parameter Specification
Manufacturer General Electric (GE)
Series Mark V (Speedtronic)
Full Model DS3800NOCB1B1B
Power Supply +5V DC @ 3.8A, +15V DC @ 0.7A, -15V DC @ 0.5A
Temperature Inputs 4 thermocouple channels (Type J/K/T, 16-bit ADC, ±1°C accuracy)
SS Outputs 8 solid-state relays, 2A continuous @ 24–48VDC
Relay Outputs 4 mechanical relays, 5A continuous @ 115VAC/30VDC (surge 10A)
Tachometer Inputs None
Communication Mark V proprietary parallel backplane bus
Operating Temperature -20°C to +65°C
LED Indicators Power, SS Run (8x green), Relay Run (4x amber), Over-Temp Alarm, Backplane Active

Advantages and Distinctive Features

  • Solid-State-Primary Hybrid Architecture: 8 solid-state DC outputs + 4 mechanical relays on a single board.

  • Higher Relay Current (5A): Supports larger AC/DC auxiliary loads compared to 3A hybrid boards.

  • Fan-Dense Design: 8 SS outputs + 4 relay outputs with only 4 temperature inputs—optimized for single-zone cooling.

  • Improved Temperature Accuracy (16-bit ADC): ±1°C accuracy—double the precision of the base 12-bit (±2°C) model.

  • Extended Temperature Range: -20°C to +65°C supports moderately harsh environments.

  • Silent, Maintenance-Free Solid-State Outputs: Unlimited cycle life for DC fans.

  • Relay Auxiliary Outputs: 2500V galvanic isolation for AC/DC auxiliary loads.

  • Low EMI Emissions: Solid-state outputs minimize interference with sensitive cards.


Typical Application Fields

  • Fan-Dense Mixed Fan Cabinets: Where DC fans are primary with higher-power AC/DC auxiliary devices.

  • Unheated Shelters & Outdoor Enclosures: -20°C to +65°C range.

  • Moderately Harsh Environments: Where climate control is limited.

  • High-Power Auxiliary Applications: 5A relay capacity for larger contactors or alarms.


Comparison with Related Models

Feature DS3800NOCB1B1B DS3800NOCA1B1B DS3800NOAA DS3800NMEC1B1A
SS Outputs 8 × 2A 8 × 2A 8 × 2A 4 × 2A
Relay Outputs 4 × 5A 4 × 3A 4 × 3A 8 × 5A
T/C Inputs 4 4 4 4
Tach Inputs None None 2 channels None
ADC Resolution 16-bit (±1°C) 16-bit (±1°C) 12-bit (±2°C) 16-bit (±1°C)
Operating Temp -20°C to +65°C -20°C to +65°C 0°C to +60°C 0°C to +60°C
Firmware B B A/B B
Cost Medium-High Medium Medium Medium

Selection Recommendations

  • Choose the DS3800NOCB1B1B if:

    • You need 8 solid-state DC outputs (2A) for main fans.

    • You also need 4 mechanical relay outputs (5A) for higher-power auxiliary devices.

    • You want improved temperature accuracy (±1°C).

    • Your installation requires extended temperature range (-20°C to +65°C).

    • Your cabinet uses 4 temperature sensors for 12 total outputs (fan-dense configuration).

    • You do not require tachometer feedback.

  • Choose the DS3800NOCA1B1B if: You need 3A relay outputs instead of 5A.

  • Choose the DS3800NOAA if: You need tachometer feedback with the same hybrid outputs.


Critical Precautions

  • ESD Protection: Always wear a grounded wrist strap.

  • DC Polarity (SS): Solid-state outputs are DC-only and polarity-sensitive—reverse polarity destroys the MOSFET.

  • SS Voltage Limit: Do not exceed 48VDC—AC voltages cause catastrophic failure.

  • High-Voltage/Current Hazard (Relay): Relay outputs switch 115VAC/5A—lethal. Use proper insulation.

  • Relay Inductive Derating: For inductive loads, derate from 5A to 3.5A or use RC snubbers.

  • Missing T/C Channels: Only 4 thermocouple inputs (channels 1–4). Channels 5–8 are physically absent.

  • No Tachometer Inputs: Do not connect speed sensors.

  • No Hot-Swap: Always depower the rack before insertion/removal.

  • Slot Assignment: Install in slots 8–10 (auxiliary I/O).

  • CPU Dependency: If backplane communication is lost, the board defaults to 100% fan speed.

  • Firmware Compatibility: Revision B firmware is compatible with Mark V CPU firmware v4.0 and above. For v3.x, the enhanced ADC accuracy may be partially disabled—confirm compatibility before purchasing.

HONEYWELL GLCC01A2B
HONEYWELL GLCC01E7B
A-B 1794-TB32A