The DS3800NFEE1E1E is a high-specification revision of General Electric’s Mark V series Fan/Exhaust Control board, part of the Speedtronic™ turbine control system. The suffix “1E1E” signifies Revision E firmwaremilitary-grade component selection (extended temperature and vibration tolerance), and enhanced relay output drivers rated at 8A continuous—the highest current capacity among Mark V fan control boards. This board manages thermal conditions within the turbine control cabinet by monitoring thermocouple inputs and switching exhaust fans via high-current mechanical relays.

Unlike the solid-state DS3800NFEC1B1B or the standard DS3800NFEE, the DS3800NFEE1E1E is built for extreme environments, featuring ruggedized connectors, conformal coating, and relays with silver-alloy contacts for superior arc suppression. The “E” revision firmware includes advanced diagnostic routines that continuously monitor relay contact resistance, predicting end-of-life wear before failure occurs—a feature unique to the DS3800NFEE1E1E.

Category:

Description

Key Technical Parameters

Parameter Specification
Manufacturer General Electric (GE)
Series Mark V (Speedtronic)
Full Model DS3800NFEE1E1E
Power Supply +5V DC @ 4A, +15V DC @ 0.8A, -15V DC @ 0.5A (via backplane)
Temperature Inputs 8 differential thermocouple channels (Type J/K/T, with 24-bit ADC for high precision)
RTD Inputs 4 channels (Pt100, 3-wire, with lead-wire compensation)
Fan Outputs 8 mechanical relays, 8A continuous @ 250VAC or 30VDC (surge rating 15A for 200ms)
Tachometer Inputs None (on/off control only)
Communication Mark V proprietary parallel backplane bus
Operating Temperature -40°C to +75°C (extended military-grade range)
Storage Temperature -55°C to +100°C
Vibration Resistance 5g RMS, 10–500 Hz (tested per MIL-STD-810G)
LED Indicators Power (green), Fan Run (8x amber), Over-Temp Alarm (red), Relay Degradation Warning (yellow), Bus Fault (red)

Advantages and Distinctive Features

  • High-Current 8A Relays: The DS3800NFEE1E1E delivers 8A continuous output capability, making it the only Mark V fan board capable of driving 1HP 115VAC fans directly—without external motor contactors. This reduces cabinet complexity and wiring costs.

  • Predictive Relay Maintenance: Unique to the DS3800NFEE1E1E, the Revision E firmware performs real-time contact resistance measurement. When resistance rises above 100mΩ (indicating wear), the board illuminates a yellow “Relay Degradation” LED, allowing scheduled maintenance before a complete relay failure occurs.

  • Extended Environmental Tolerance: Rated for -40°C to +75°C with 5g vibration tolerance, the DS3800NFEE1E1E is ideal for oil & gas platforms, desert installations, and arctic environments where other boards would fail.

  • High-Precision Temperature Inputs: The 24-bit ADC on the DS3800NFEE1E1E provides ±0.5°C accuracy, enabling tighter temperature control and reducing unnecessary fan cycling.

  • Silver-Alloy Relay Contacts: The relays on the DS3800NFEE1E1E feature silver-cadmium-oxide contacts, offering superior resistance to welding and pitting under high-inrush conditions—extending relay life by up to 50% compared to standard models.


Typical Application Fields

  • Offshore Oil & Gas Platforms: The DS3800NFEE1E1E withstands high humidity, salt spray, and vibration from drilling operations, ensuring reliable cooling in generator turbine cabinets.

  • Desert Power Plants: Extended 75°C upper operating temperature allows the DS3800NFEE1E1E to function in un-air-conditioned shelters where ambient temperatures exceed 55°C.

  • Arctic Compressor Stations: -40°C low-temperature tolerance ensures startup reliability even after extreme cold soak.

  • Marine Propulsion Turbines: Vibration-resistant design makes the DS3800NFEE1E1E suitable for shipboard applications.

  • Nuclear Auxiliary Turbines: The high reliability and predictive diagnostics of the DS3800NFEE1E1E meet the stringent maintenance requirements of nuclear facilities.


Comparison with Related Models

Feature DS3800NFEE1E1E DS3800NFEE1C1B DS3800NFEE (Base) DS3800NFEC1B1B
Relay Rating 8A continuous 5A continuous 3A continuous Solid-state, 2A
Firmware Revision E (predictive maintenance) C (enhanced CJC) A/B (basic) B (PID + tach)
ADC Resolution 24-bit (±0.5°C) 16-bit (±1°C) 12-bit (±2°C) 16-bit (±1°C)
Operating Temp -40°C to +75°C -20°C to +65°C 0°C to +60°C -20°C to +65°C
Vibration Rating 5g RMS 2g RMS 1g RMS 2g RMS
Relay Degradation Warning Yes (unique) No No No
Tachometer/PID No No No Yes
Cost (Used) Very High Medium Low High

Selection Recommendations

  • Choose the DS3800NFEE1E1E if:

    • Your fans draw >5A (up to 8A) or are 1HP-class blowers.

    • Your cabinet is in extreme temperatures (<-20°C or >60°C) or high-vibration environments.

    • You need predictive maintenance alerts to avoid unplanned downtime.

    • High-precision temperature control (±0.5°C) is required to reduce fan cycling.

    • You prefer simple on/off relay control without tachometer complexity.

  • Choose the DS3800NFEC1B1B if: Variable speed control and tachometer feedback are mandatory.

  • Choose the DS3800NFEE1C1B if: You need up to 5A relays with moderate temperature range but don’t require the extreme capabilities or cost of the DS3800NFEE1E1E.


Critical Precautions

  • ESD Protection: Despite rugged construction, the DS3800NFEE1E1E contains sensitive 24-bit ADC components. Always wear a grounded ESD wrist strap. Static damage to the ADC will degrade temperature accuracy to >5°C, rendering the board unsuitable for precise control.

  • Relay Inductive Load Derating: The 8A rating applies to resistive loads. For inductive fan motors, derate to 6A continuous or use an external RC snubber across each relay output. The DS3800NFEE1E1E provides dedicated terminals for external snubber connection—do not omit this for motor loads.

  • Silver-Alloy Relay Contact Welding: Under severe short-circuit conditions (e.g., fan motor locked rotor), contacts may weld. The DS3800NFEE1E1E‘s degradation warning circuit will detect increased contact resistance post-weld. Always test fan rotation after a power surge or lightning strike.

  • Thermocouple Wiring: Use thermocouple-grade extension wire with correct polarity. The 24-bit ADC on the DS3800NFEE1E1E is sensitive to ground loops—ensure thermocouple shields are grounded only at the board side per GE installation guidelines.

  • Slot Assignment: Install the DS3800NFEE1E1E only in auxiliary I/O slots (typically slots 8–10). Do not install in slots reserved for analog input boards, as the 8A relay switching transients can couple noise into sensitive analog circuits sharing the same backplane.

  • No Hot-Swap: Always depower the Mark V rack before inserting or removing the DS3800NFEE1E1E. The backplane connectors are not rated for live insertion/removal.

  • Firmware Compatibility: The Revision E firmware on the DS3800NFEE1E1E requires Mark V CPU firmware v5.0 or higher for full predictive diagnostic functionality. If your CPU runs v4.x, the board will function but the degradation warning feature will be disabled.

  • Surge Current Handling: The DS3800NFEE1E1E can handle 15A for 200ms. For fans with higher inrush, install a soft-start device or use an external motor starter triggered by the relay output (derated to 1A control signal).

Schneider MA-0185-100(C)