Description
Technical Specifications
-
Product Type: Digital Servo Amplifier Board (Revision 1A1A)
-
Part Number: DS3800DSAB1A1A
-
Manufacturer: General Electric (GE)
-
System Compatibility: GE Speedtronic Mark IV Turbine Control Systems
-
Output Channels: 4 independent servo valve drive channels
-
Output Type: Differential current output (±20mA, ±40mA, ±80mA selectable via jumpers)
-
Input Signal: ±10Vdc analog command from Mark IV processor
-
Feedback Input: 4 LVDT/RVDT feedback channels per output
-
Power Supply: +24Vdc (external) + +15Vdc/-15Vdc (backplane)
-
Dither Frequency: Fixed 200Hz (factory-set; limited adjustment via trimmer)
-
Protection: Over-current and short-circuit protection per channel
-
Isolation: 1500Vrms opto-isolation (logic-to-power)
-
Temperature Range: 0°C to +60°C
-
MTBF: > 100,000 hours (MIL-HDBK-217F)
Key Features & Advantages
-
Proven Reliability: The GE DS3800DSAB1A1A uses discrete, through-hole components with a long field-proven track record in thousands of turbines worldwide. This revision is known for its robustness and field-repairability.
-
Hardware PID: The GE DS3800DSAB1A1A implements PID control using discrete analog circuits, ensuring < 5ms response time without software latency.
-
Integrated LVDT Conditioning: Each channel provides carrier excitation and demodulation for LVDT/RVDT feedback, enabling closed-loop position control without external signal conditioners.
-
Fixed Dither: Factory-set 200Hz dither (adjustable via trimmer) prevents servo valve spool sticking while maintaining simplicity.
-
Diagnostic LEDs: Front-panel LEDs indicate output status, current limit, and feedback presence for each of the 4 channels.
-
Jumper-Configurable: Output current range and feedback scaling are set via DIP switches and jumpers.
Typical Application Cases
-
Fuel Control Valves: Drives servo valves for gas turbine fuel metering; precise current control ensures stable combustion.
-
Steam Admission Valves: Positions main stop and control valves in steam turbines for HP, IP, and LP steam flow regulation.
-
Inlet Guide Vanes (IGV): Controls IGV actuators in gas turbine compressors for optimized airflow.
-
Bypass Valves: Drives bypass valves in combined-cycle plants during startup and trip conditions.
Competitive Comparison
| Feature | GE DS3800DSAB1A1A | GE DS3800DSAB (Base) | Modern PLC Servo Module |
|---|---|---|---|
| Dither Control | Fixed 200Hz (trimmer adj.) | Adjustable 50-400Hz | Software-programmable |
| PID Implementation | Discrete analog hardware | Discrete analog hardware | Software-based (digital) |
| Response Time | < 5ms | < 5ms | 10-50ms |
| Output Range | ±20/40/80mA | ±20/40/80mA | ±10V or 4-20mA |
| LVDT Feedback | Integrated | Integrated | Requires external module |
| Isolation | 1500Vrms | 1500Vrms | 500Vrms |
| Compatibility | Mark IV backplane | Mark IV backplane | Universal fieldbus |
The GE DS3800DSAB1A1A is virtually identical to the base DS3800DSAB but with a fixed dither configuration. Modern servo modules offer greater flexibility but lack the hardware speed and integrated feedback conditioning of this dedicated board.
Selection Guidelines & Precautions
-
Current Setting Verification: Verify your servo valve drive current. Configure jumpers on GE DS3800DSAB1A1A accordingly. Incorrect settings cause saturation or inadequate stroke.
-
Dither Adjustment: The dither is fixed at 200Hz but can be adjusted via a trimmer. Only adjust if the servo valve manufacturer specifies a different optimal frequency.
-
LVDT/RVDT Matching: Confirm feedback device impedance and range match the GE DS3800DSAB1A1A conditioning circuits to prevent position oscillation.
-
Coil Resistance Check: Measure servo valve coil resistance (minimum 50Ω). Lower resistance triggers over-current protection.
-
Cable Shielding: Use shielded twisted-pair cables for all connections. Ground shield at board end only.
-
ESD Handling: Use ESD-safe practices; contains sensitive CMOS op-amps.
-
Commissioning: Start in open-loop mode, gradually increase gain. Use diagnostic LEDs to confirm feedback before engaging closed-loop.
-
Sourcing: Obsolete. Request functional test report including:
-
All 4 channels tested with servo valve simulator
-
Current linearity verification
-
LVDT conditioning test
-
Over-current protection validation
-
-
Spare Strategy: Keep one spare GE DS3800DSAB1A1A on-site. For critical applications, consider redundant servo amplifier configuration if rack supports it.

A-B 1756-IB16I/A
FOXBORO P0916CC
A-B 1734-OE4C


Reviews
There are no reviews yet.