Description
Technical Parameters
Manufacturer: GE
Series: Mark V / Mark VIe
Channels: 16 differential
Input Range: -10 mV to +100 mV (Type J/K/T/E)
Cold Junction: Single onboard sensor with enhanced linearization and improved thermal isolation
Isolation: 1500V AC
Accuracy: ±0.08% at 25°C, ±0.15% across full temperature range
Sampling: 10 Hz sequential
Operating Temp: -30°C to +65°C
Storage Temp: -40°C to +85°C
Mounting: VME rack
Suffix “G2A”: High accuracy + advanced diagnostics (drift, degradation, sense-lead) + E2 wiring configuration + enhanced cold-junction compensation + standard conformal coating
Key Features
High accuracy – ±0.08% for critical temperature monitoring
Advanced diagnostics – drift monitoring, degradation prediction, sense-lead integrity, and open/short detection
Enhanced cold-junction compensation – better linearization across ambient variations than standard E2 variants
Faster sampling – 10 Hz for responsive monitoring
E2-specific wiring configuration – unique channel-to-terminal mapping matching specific GE cabinet wiring standards; direct drop-in for E2-configured systems
Simple swap – no firmware changes required in most Mark V systems
LED status per channel + board health with diagnostic indicators
Standard conformal coating for moisture/dust resistance
Backward compatible with Mark V and Mark VIe (hot-swap only on VIe Rev D+)
Applications
Legacy gas turbine retrofits with E2 wiring – where existing field wiring uses E2 terminal assignments and high accuracy with diagnostics and improved compensation is required
Steam turbine bearing monitoring in E2 cabinets – critical protection with drift anticipation and enhanced ambient stability
Pipeline compressor stations with E2-configured cabinets – precision monitoring with predictive maintenance
Industrial cogeneration plants – where OEM specified E2 wiring for thermocouple terminations
Facilities with E2-standard cabinets requiring diagnostic insights
Comparison with Competitors
| Feature | DS200TCQEG2A |
ABB TTH300 | Siemens 7KG7750 |
|---|---|---|---|
| Channels | 16 | 8 | 12 |
| Accuracy | ±0.08% | ±0.10% | ±0.12% |
| Sampling | 10 Hz | 10 Hz (simultaneous) | 8 Hz (simultaneous) |
| Diagnostics | Drift + degradation + open/short | Group-level | Per-channel + HART |
| Cold Junction Comp. | Enhanced | Standard | Standard |
| Temp Range | -30°C to +65°C | -25°C to +65°C | -20°C to +60°C |
| Wiring Config | E2-specific | Standard | Standard |
| GE Native Integration with E2 Cabs | Yes (direct fit) | No | No |
| Hot-Swap | No (V) / Yes (VIe) | No | Yes |
Selection Tips
Choose the DS200TCQEG2A only if your cabinet uses E2 wiring configuration and you require high accuracy (±0.08%) with advanced diagnostics and enhanced cold-junction compensation – this board combines precision, predictive maintenance, improved stability, and E2 pinout compatibility
For E2 systems with the same features but standard cold-junction compensation, consider DS200TCQEG2 (if available)
For E2 systems with high accuracy but no diagnostics, consider DS200TCEAEG2B (if available)
For extended temperature (70°C) with similar features, consider DS200TCQEG2B (if available)
For enhanced coating protection with similar specs, consider DS200TCQEG2A with specialized coating suffix (e.g., DS200TCQEG2AEB or similar)
For G1 systems requiring similar features, use DS200TCQBG1A
For C1 systems requiring similar features, use DS200TCQCG1A
If you are rewiring the cabinet, consider converting to G1 for broader board availability
Verify existing wiring pinout against E2 standard – using the wrong terminal block or miswiring will scramble channel readings
Source refurbished units with E2 pinout verification and diagnostic test validation in the test report
Precautions
ESD sensitive – use wrist strap
Power down for Mark V removal (no hot-swap)
Torque terminals to 0.5 N·m max
Do not exceed -30°C to +65°C operating range – exceeding 65°C reduces component life
Pinout critical – E2 mapping differs from G1/G2/C1; verify cabinet wiring before installation
Calibrate every 24 months – diagnostics, enhanced accuracy, and cold-junction compensation depend on a valid baseline calibration
Ground shields only at the board end
Verify thermocouple type – optimized for J/K (T/E reduces accuracy to ±0.15%)
Monitor diagnostic logs – drift warnings indicate sensor aging; plan proactive replacement
Label clearly – mark board and slot as “TCQEG2A – DIAG/ENH CJC/E2” to ensure proper handling and prevent future miswiring with G1/G2/C1 boards
Do not mix E2, E1, C1, G1, and G2 boards without verifying terminal block compatibility in the same rack

HONEYWELL MC-PDOY22
SCHNEIDER 140MSB10100
SCHNEIDER 140MSB10100
PHOENIX ILB BT ADIO 2/2/16/16 2884282