Description

Product Parameters
- Brand: Woodward
- Model: 5501-381
- Product type: MicroNet TMR AC power supply module
- Input: 220VAC, 47–63Hz
- Max input power: 1250VA
- Output: +5V, ±12V, +24V DC bus
- Compatibility: 5453-277 power chassis
- Redundancy: Dual module load sharing, automatic failover
- Indicators: 4 LEDs: Input Fault, PS Fault, Overtemperature, OK
- Protection: Overvoltage, overload, short-circuit, overtemperature
- Operating temperature: 0°C ~ +60°C
- Storage temperature: -40°C ~ +85°C
- Certification: CE, UL, SIL suitable for turbine safety control
Advantages and Features
The Woodward 5501-381 is the dedicated AC power module for MicroNet TMR safety racks, delivering clean and stable power for triple redundant control hardware. Hot-swap design allows online replacement during system running without turbine trip. Front panel LED status simplifies fast fault diagnosis. Conformal coated circuit board resists moisture, dust and vibration, adapting to power plant and petrochemical cabinet environments. Dual redundant configuration greatly improves the availability of critical gas turbine, steam turbine and compressor control racks. The Woodward 5501-381 is an essential spare part for legacy MicroNet TMR maintenance.
Application Fields and Application Cases
The Woodward 5501-381 is widely used in gas turbine, steam turbine, centrifugal compressor and generator set safety control systems. In a power plant turbine control cabinet, the Woodward 5501-381 is installed in the 5453-277 chassis to supply power for the TMR main rack. In refinery compressor TMR racks, two Woodward 5501-381 modules are deployed for redundant power feeding to avoid power loss shutdown risk. It is a common spare part for old MicroNet TMR system maintenance and renovation.
Comparisons with Competing Products
Compared with RPS6U series DC power modules, the Woodward 5501-381 is 220VAC input version, different power circuit and pin definition. It must be matched with 5453-277 power chassis and cannot be used in 5453-279 main chassis directly. Ordinary general industrial AC-DC power modules cannot match the power sequence, fault reporting signal and backplane interface of MicroNet TMR. For existing TMR racks using 5453-277 chassis with this AC power module, the original Woodward 5501-381 is the designated matching power supply module.
Selection Suggestions and Precautions
Before ordering, confirm chassis 5453-277, backplane revision and AC input specification to verify compatibility of Woodward 5501-381. Confirm hardware revision consistency. Take anti-static protection during disassembly and replacement. After installation, test DC output rails, load sharing and fault switching function. Back up control program and parameters before replacement. AC and DC TMR power modules cannot be interchanged. Keep the cabinet ventilated and dust-free to avoid overheating and poor contact.