PROSOFT MVI56E-MCM

¥9,999.00

The ProSoft MVI56E-MCM is an enhanced Modbus communication module for the Allen-Bradley ControlLogix platform, manufactured by ProSoft Technology (now part of Belden). As a member of the MVI56E “Enhanced” family, the ProSoft MVI56E-MCM installs in a single ControlLogix chassis slot and provides two independent serial ports configurable as Modbus RTU/ASCII Master or Slave, enabling the ControlLogix controller to communicate with Modbus devices such as drives, meters, flow computers, and legacy PLCs. The MVI56E-MCM exchanges data with the ControlLogix processor through the backplane, presenting Modbus register data as controller tags for direct use in ladder logic. The ProSoft MVI56E-MCM features an on-board web server and ProSoft Discovery Service for simplified configuration and diagnostics, along with a removable Compact Flash card for configuration storage and transfer. Widely deployed in oil and gas, water treatment, and manufacturing facilities, the MVI56E-MCM is the practical choice for integrating Modbus serial devices into a modern ControlLogix architecture.

Category:

Description

Product Parameters

Parameter Specification
Model MVI56E-MCM
Brand ProSoft Technology (Belden)
Platform Allen-Bradley ControlLogix
Function Modbus serial communication module
Chassis Slots 1 slot
Serial Ports 2 independent ports (RS-232 / RS-422 / RS-485)
Protocol Support Modbus RTU and Modbus ASCII, Master or Slave per port
Backplane Interface ControlLogix backplane, tag-based data exchange
Configuration Storage Removable Compact Flash card
Diagnostics On-board web server, ProSoft Discovery Service, LED indicators
Configuration Tool ProSoft Configuration Builder (PCB)
Operating Temperature Industrial range
Design Intent Modbus serial device integration into ControlLogix

Advantages and Features

The ProSoft MVI56E-MCM provides two fully independent serial ports, each configurable as Modbus Master or Slave, allowing simultaneous connection to multiple Modbus networks with different baud rates and protocols. The MVI56E-MCM supports up to 10,000 16-bit registers of Modbus data exchange, with flexible data mapping to ControlLogix tags through the backplane. The enhanced on-board web server on the MVI56E-MCM enables remote diagnostics, status monitoring, and configuration review from any browser, reducing troubleshooting time. The removable Compact Flash card allows configuration backup and rapid module replacement without reconfiguration. ProSoft Configuration Builder software simplifies setup, and the module’s diagnostic LEDs and status data provide clear visibility into communication health. The MVI56E-MCM is backward compatible with earlier MVI56-MCM installations, easing upgrades.

Application Cases and Fields

The ProSoft MVI56E-MCM is commonly applied in:

  • Oil and gas facilities integrating Modbus flow computers, RTUs, and drives

  • Water and wastewater plants connecting Modbus meters, analyzers, and pump controllers

  • Manufacturing lines interfacing Modbus VFDs, servo drives, and power meters

  • Power generation and utility substations linking Modbus protection relays and meters

  • Legacy system migration projects replacing older Modbus interfaces with ControlLogix

In these applications, the MVI56E-MCM performs Modbus polling and data concentration, presenting clean tag data to the ControlLogix controller for use in control and SCADA logic.

Comparison with Competing Products

Compared with fixed-function Modbus modules, the ProSoft MVI56E-MCM offers dual independent ports, enhanced web-based diagnostics, and removable configuration storage, providing greater flexibility and faster maintenance. Competing Modbus gateways typically require external hardware and separate power supplies, whereas the MVI56E-MCM installs directly in the ControlLogix chassis and exchanges data over the backplane without external wiring. Against earlier MVI56-MCM modules, the enhanced MVI56E-MCM adds web server diagnostics, faster processors, and improved configuration tools, making it the preferred choice for new installations and upgrades.

Selection Suggestions and Precautions

  • Confirm the ControlLogix chassis, firmware revision, and ProSoft module compatibility before specifying the MVI56E-MCM.

  • Verify the serial interface type (RS-232, RS-422, or RS-485) and termination requirements for each Modbus network.

  • Plan Modbus register mapping and ControlLogix tag structures in advance to streamline commissioning.

  • Follow ProSoft installation and configuration manuals and observe ESD precautions when inserting the MVI56E-MCM into the chassis.

  • Procure the ProSoft MVI56E-MCM through authorized channels to ensure authenticity and access to firmware and support.

  • Back up the configuration to the Compact Flash card and retain a copy, so a replacement MVI56E-MCM can be restored quickly.

  • Test Modbus polling rates and timeouts in a staging environment to confirm network performance before production deployment.

Reviews

There are no reviews yet.

Be the first to review “PROSOFT MVI56E-MCM”

Your email address will not be published. Required fields are marked *

Post comment