Description
Key Specifications
| Parameter | Specification |
|---|---|
| Speed Input Channels | 6 independent speed input channels (3 pairs for redundancy) |
| Sensor Types Supported | Magnetic pickups, proximity probes (eddy current), tachometers, hall-effect sensors |
| Input Signal Range | 100 mV to 100 V p-p (magnetic); 5–24 VDC (proximity/tacho/hall) |
| Frequency Range | 0.5 Hz to 30 kHz |
| Speed Measurement Range | 0 to 60,000 RPM (programmable) |
| Speed Accuracy | ±0.005% of reading |
| Redundancy Configuration | 3 pairs of redundant speed channels (2-out-of-3 voting per pair) |
| Protection Functions | Overspeed trip, under-speed detection, zero-speed detection, speed rate-of-change monitoring, speed mismatch detection |
| Response Time | <3 ms for overspeed trip detection |
| Dual Protection Logic | 2-out-of-3 voting for each speed measurement point |
| Isolation | 1500 VDC (channel-to-backplane) |
| Diagnostics | 750-event fault log with timestamps and waveform snapshots |
| Operating Temp | –25 °C to +70 °C (extended range) |
| Humidity | 5–95% non-condensing (with conformal coating) |
| Coating | Conformal coating (standard) — UV-traceable |
| Manufacturing | 120-hour burn-in, 100% X-Ray/AOI, military-grade components |
| Form Factor | 6U VME64x (160 × 233 mm), single-slot width |
| Power | 12 W (+5 V / +3.3 VDC) |
| Connectors | 48-pin terminal block with gold-plated contacts and captive washer screws |
| Built-in Test | Sensor health monitoring, signal quality analysis, low amplitude detection |
Advantages & Distinctive Features
-
Redundant Speed Measurement: 3 independent pairs of speed channels—ensures trip integrity while preventing false trips.
-
Fast Response: <3 ms overspeed trip detection meets the most stringent API 670 requirements.
-
High Accuracy: ±0.005% reading for precise speed measurement.
-
Dual Protection Logic: 2-out-of-3 voting for each speed measurement point.
-
Speed Mismatch Detection: Compares all 6 channels—alerts if any channel deviates >2% from median.
-
Signal Quality Analysis: Monitors amplitude and waveform integrity for predictive maintenance.
-
Expanded Sensor Support: Hall-effect sensor compatibility for noise immunity.
-
Conformal Coating Standard: Protects against humidity, salt spray, and chemicals.
-
Extended Temperature Range: –25 °C to +70 °C.
-
Expanded Diagnostic Log: 750-event fault log with waveform snapshots.
-
Military-Grade Manufacturing: 120-hour burn-in, military-grade components.
-
Gold-Plated Captive Washer Terminals: Corrosion-resistant and vibration-proof.
-
Hot-Swappable: No rack power-down for replacement.
-
Direct Retrofit: Replaces older DTUR series boards.
Application Fields
-
Gas Turbines: Redundant overspeed protection, speed governor control
-
Steam Turbines: Redundant overspeed protection, synchronization speed
-
Generators: Grid synchronization speed, redundant overspeed protection
-
Compressors: Speed monitoring for surge protection
-
Nuclear Power Plants: Safety-critical redundant overspeed protection
-
Offshore platforms: Salt-spray environments requiring conformal coating
Comparison with VTURH1BAA and Competitors
| Feature | GE IS210DTURH1AA | GE IS200VTURH1BAA | Competitor A | Competitor B |
|---|---|---|---|---|
| Speed Channels | 6 (3 pairs) | 3 (single) | 1 | 3 |
| Redundancy | 2-out-of-3 voting per pair | 2-out-of-3 voting | 1-out-of-1 | 1-out-of-1 |
| Response Time | <3 ms | <3 ms | <10 ms | <10 ms |
| Accuracy | ±0.005% | ±0.005% | ±0.02% | ±0.02% |
| Speed Mismatch Detection | Yes (6 channels) | Yes (3 channels) | No | No |
| Signal Quality Analysis | Yes | Yes | No | No |
| Coating | Standard | Standard | Optional | Optional |
| Temp Range | –25 to +70 °C | –25 to +70 °C | 0 to +55 °C | 0 to +55 °C |
| Fault Logging | 750 events + waveforms | 750 events + waveforms | 100 events | No |
Selection Guidelines
-
When to choose: Critical overspeed protection applications requiring redundant speed measurement with 2-out-of-3 voting per measurement point.
-
Redundancy Configuration: Use all 6 channels (3 pairs) with 2-out-of-3 voting per pair for maximum protection integrity.
-
Scaling Configuration: Enter correct pulses per revolution (gear teeth count) in Toolbox ST.
-
Trip Level Setting: Configure overspeed trip setpoint per turbine manufacturer specifications (typically 110–115% of rated speed).
-
Speed Mismatch Threshold: Default 2%—adjust based on sensor accuracy.
-
Coating Verification: Inspect under UV (365 nm) upon receipt.
-
Compatibility: Fits all Mark VIe VME64x racks. Requires ControlST v6.5 or higher.
Operational Precautions
-
Wiring: Follow GE wiring diagrams—correct polarity and shield grounding essential.
-
Sensor Gap Setting: For proximity probes, verify air gap and bias voltage are correct.
-
Speed Calibration: Verify speed reading against a known reference during commissioning.
-
Overspeed Testing: Perform simulated overspeed tests to verify <3 ms response and trip logic.
-
Voting Logic Verification: Simulate single-channel failures to verify 2-out-of-3 logic per pair.
-
Speed Mismatch Testing: Introduce a known offset on one channel to verify mismatch alarm generation.
-
Signal Quality Monitoring: Review amplitude trends in Toolbox ST—degrading amplitude indicates sensor/cable issues.
-
LED Diagnostics: Green = signal OK; Amber = marginal signal; Red = channel fault or overspeed condition.
-
Fault Log: Access 750-event log via Toolbox ST for post-event analysis.
-
Coating Care: Use GE-approved cleaner; inspect annually under UV.
-
Hot-Swap: Remove/insert slowly under power.
-
Spare Stock: Maintain 1 spare per 3–4 racks; “H1AA” backward-compatible with all DTUR/VTUR sockets.
-
Firmware Updates: Ensure the GE IS210DTURH1AA is in “standby” mode during updates.
-
ESD: Handle by edges with grounded wrist strap.
-
Storage: Anti-static bag with desiccant at –40 to +85 °C; rotate every 3 years.

GE IC200GBI001
GE IC200GBI001
YASKAWA SGDV-120A01A
A-B 1756-CNB/E


Reviews