IS210DTRTH1AA GE

¥999.00

The GE IS210DTRTH1AA is a VMEbus terminal board manufactured by General Electric for the Mark VIe distributed control system (DCS). This board is a dedicated Dual Thermocouple and RTD Input module, designed to provide high-precision temperature measurement from two independent thermocouples or RTDs per channel for turbine control applications. The GE IS210DTRTH1AA enables redundant temperature monitoring with dual inputs per measurement point—supporting both thermocouples and RTDs in a single module. The “H1AA” designation indicates a first-generation dual TC/RTD input module with the “AA” suffix denoting military-grade components, extended burn-in (120 hours), 100% X-ray/AOI inspection, and conformal coating as standard.

Category:

Description

Key Specifications

Parameter Specification
Input Channels 8 dual-sensor channels (16 total inputs) — each configurable as TC or RTD
Thermocouple Types Supported J, K, T, E, N, R, S, B — software-selectable
Thermocouple Accuracy ±0.08% of reading + ±0.4 °C
RTD Types Supported Pt100 (α = 0.00385), Pt500Pt1000Ni120
RTD Connection 3-wire or 4-wire (software-selectable)
RTD Accuracy ±0.08% of reading + ±0.3 °C
Cold Junction Compensation Integrated CJC sensors (±0.2 °C accuracy)
Dual-Sensor Redundancy Each channel supports two independent sensors (TC or RTD)
Redundancy Logic On-board averagedifferencemaximum, and minimum calculation
Resolution 0.05 °C
Sample Rate 10 Hz (sequential scanning)
Burnout Detection Open-circuit detection for TC and RTD faults
Lead-Wire Compensation Automatic compensation for 3-wire and 4-wire RTDs
Excitation Current Programmable (0.5 mA, 1 mA, 2 mA) for RTDs
Isolation 1500 VDC (I/O-to-backplane)
Diagnostics 750-event fault log with timestamps (expanded)
Operating Temp –25 °C to +70 °C (extended range)
Humidity 5–95% non-condensing (with conformal coating)
Coating Conformal coating (standard) — UV-traceable
Manufacturing 120-hour burn-in, 100% X-Ray/AOI, military-grade components
Form Factor 6U VME64x (160 × 233 mm), single-slot width
Power 12 W (+5 V / +3.3 VDC)
Connectors 48-pin terminal block with gold-plated contacts and captive washer screws

Advantages & Distinctive Features

  • Dual-Sensor Redundancy: Each channel supports two independent sensors (TC or RTD).

  • Versatile Input Support: Each channel configurable as TC or RTD—flexibility for mixed sensor types.

  • On-Board Redundancy Logic: Average, difference, maximum, and minimum calculations.

  • Integrated CJC: ±0.2 °C accuracy for TC measurements.

  • RTD Lead-Wire Compensation: Automatic for 3-wire and 4-wire RTDs.

  • Burnout Detection: Open-circuit detection for both TC and RTD faults.

  • Programmable RTD Excitation: 0.5 mA, 1 mA, 2 mA for optimal performance.

  • High Accuracy: ±0.08% TC + ±0.4 °C; ±0.08% RTD + ±0.3 °C.

  • Conformal Coating Standard: Protects against humidity, salt spray, and chemicals.

  • Extended Temperature Range: –25 °C to +70 °C.

  • Expanded Diagnostic Log: 750-event fault log.

  • Military-Grade Manufacturing: 120-hour burn-in, military-grade components.

  • Gold-Plated Captive Washer Terminals: Corrosion-resistant and vibration-proof.

  • Hot-Swappable: No rack power-down for replacement.

  • Direct Retrofit: Replaces older DTRT series boards.


Application Fields

  • Gas Turbines: Exhaust temperature (TC), bearing temperature (RTD), dual redundancy

  • Steam Turbines: Casing temperature (TC), bearing temperature (RTD)

  • Compressors: Inlet/discharge temperature (TC/RTD)

  • Generators: Stator winding temperature (RTD)

  • Offshore platforms: Salt-spray environments requiring conformal coating

  • Nuclear Power Plants: Redundant temperature monitoring for safety


Comparison with DTCIH1AA and Competitors

Feature GE IS210DTRTH1AA GE IS210DTCIH1AA Competitor A Competitor B
Channels 8 (dual) / 16 inputs 8 (dual) / 16 inputs 8 (single) 8 (dual)
Sensor Types TC or RTD (per channel) TC only + 4–20 mA TC only TC or RTD
TC Accuracy ±0.08% + ±0.4 °C ±0.08% + ±0.4 °C ±0.2% + ±1 °C ±0.1% + ±0.5 °C
RTD Accuracy ±0.08% + ±0.3 °C N/A N/A ±0.1% + ±0.5 °C
Redundancy Logic Average/Diff/Max/Min Average/Diff/Max/Min No No
Coating Standard Standard Optional Optional
Temp Range –25 to +70 °C –25 to +70 °C 0 to +55 °C –10 to +55 °C

Selection Guidelines

  • When to choose: Applications requiring redundant temperature monitoring with mixed TC and RTD sensors.

  • When to choose DTCIH1AA instead: Applications needing 4–20 mA inputs instead of RTD support.

  • Redundancy Logic: Configure average for normal operation; difference for fault detection.

  • Sensor Configuration: Configure per channel for TC or RTD type in Toolbox ST.

  • RTD Wiring: Use 4-wire for highest accuracy; 3-wire for standard applications.

  • Coating Verification: Inspect under UV (365 nm) upon receipt.

  • Compatibility: Fits all Mark VIe VME64x racks. Requires ControlST v6.0 or higher.


Operational Precautions

  1. Wiring: Follow GE wiring diagrams—correct polarity and shield grounding essential.

  2. Dual-Sensor Wiring: Ensure both sensors are correctly wired per channel.

  3. Redundancy Logic Testing: Simulate one sensor failure to verify redundancy logic.

  4. TC/RTD Configuration: Ensure correct sensor type is configured per channel.

  5. RTD Lead-Wire Compensation: Verify 3-wire or 4-wire configuration matches wiring.

  6. Calibration: Factory calibrated—verify against known references during commissioning.

  7. LED Diagnostics: Green = normal; Amber = sensor fault/difference; Red = module fault.

  8. Fault Log: Access 750-event log via Toolbox ST.

  9. Coating Care: Use GE-approved cleaner; inspect annually under UV.

  10. Hot-Swap: Remove/insert slowly under power.

  11. Spare Stock: Maintain 1 spare per 3–4 racks.

  12. ESD: Handle by edges with grounded wrist strap.

  13. Storage: Anti-static bag with desiccant at –40 to +85 °C; rotate every 3 years.

A-B 1756-PA75/A
A-B 1756-PA72/C
GE IC660BBA021
HONEYWELL 51202329-606

Reviews

There are no reviews yet.

Be the first to review “IS210DTRTH1AA GE”

Your email address will not be published. Required fields are marked *

Post comment