IS200WEMAH1APR2 GE

¥999.00

The GE IS200WEMAH1APR2 is a VMEbus terminal board manufactured by General Electric for the Mark VIe distributed control system (DCS). This board is a dedicated Ethernet and I/O Network Communication Interface module, designed to provide redundant, high-speed communication between the Mark VIe controller, I/O racks, and external networks. The GE IS200WEMAH1APR2 serves as a key communication backbone for turbine control systems, enabling seamless data exchange between processor boards (VPRO series), I/O terminal boards, and plant-level DCS or HMI systems. The “H1APR2” designation indicates a specific hardware revision of the Ethernet communications module, with the “PR2” typically denoting enhanced performance, updated firmware, or improved component selection for extended reliability and compatibility with the latest Mark VIe firmware versions.

Category:

Description

Key Specifications

Parameter Specification
Ethernet Ports 2 independent Gigabit Ethernet ports (10/100/1000Base-T)
Protocol Support I/O Net (GE proprietary real-time protocol), Modbus TCPEtherNet/IPCIMPLICITY HMI
Port Configuration Redundant (active/standby) with automatic failover (<10 ms)
Data Rate 10/100/1000 Mbps (auto-negotiating)
Network Redundancy Dual-star or ring topology support
Communication Processor-to-I/O rack data exchange, plant-level integration
Isolation 1500 VDC (Ethernet ports to backplane)
Form Factor 6U VME64x (160 × 233 mm), single-slot width
Indicators Port status (link/activity), module health, redundant path status, diagnostic blink codes
Operating Temp 0 °C to +60 °C
Power Draw 8 W (+5 V / +3.3 VDC)
Connectors Front-panel RJ45 ports with gold-plated contacts
Diagnostic Memory Non-volatile fault logging — stores last 750 events with timestamps (expanded over base H1AEA)
Manufacturing Enhanced component selection, extended burn-in (72 hours)
Firmware Pre-loaded with latest PR2 firmware revision for improved performance and compatibility

Advantages & Distinctive Features

  • Redundant Communication: Dual Ethernet ports provide active/standby redundancy—ensures continuous communication if one port or network path fails (<10 ms failover).

  • Versatile Protocol Support: Supports I/O Net for real-time turbine control, Modbus TCP for plant DCS integration, and EtherNet/IP for third-party device communication.

  • High-Speed Data Exchange: Gigabit Ethernet ensures fast I/O data updates and minimal communication latency.

  • PR2 Firmware Enhancements: Updated firmware improves network stack performance, reduces latency, and enhances interoperability with newer Mark VIe software versions (ControlST v6.5+).

  • Expanded Fault Logging: 750-event fault log with timestamps for comprehensive troubleshooting.

  • Diagnostic Blink Codes: Expanded LED blink patterns for rapid fault identification without a laptop.

  • Hot-Swappable: Supports removal and replacement without powering down the rack.

  • Direct Retrofit: Replaces older WEMA H1AEA and H1APR1 series boards.


Application Fields

  • Gas Turbines: Communication between I/O racks, processor, and DCS

  • Steam Turbines: Plant-level data exchange

  • Compressors: Remote I/O communication

  • Combined Cycle: Inter-turbine coordination

  • HMI Integration: CIMPLICITY visualization

  • Retrofit Projects: Upgrading older WEMA boards to PR2 firmware


Comparison with H1AEA and Competitors

Feature GE IS200WEMAH1APR2 GE IS200WEMAH1AEA Competitor A (Siemens CP 343-1) Competitor B (Rockwell 1788-EN2FFR)
Ethernet Ports 2 (redundant) 2 1 2
Failover Time <10 ms <20 ms N/A <20 ms
Protocol Support I/O Net, Modbus, EtherNet/IP I/O Net, Modbus, EtherNet/IP Profinet EtherNet/IP
Firmware Revision PR2 (latest) Base N/A N/A
Fault Logging 750 events 500 events No No
Diagnostic Blink Codes Yes (expanded) Basic No No
Hot-Swappable Yes Yes No Yes

The GE IS200WEMAH1APR2 offers faster failover, expanded diagnostics, and updated firmware compared to the base H1AEA variant—making it the preferred choice for new installations and retrofits requiring the latest Mark VIe compatibility.


Selection Guidelines

  • When to choose: Any Mark VIe application requiring Ethernet communication—especially when using ControlST v6.5 or higher, or when upgrading from older WEMA boards.

  • When to upgrade from H1AEA: Replace H1AEA boards with GE IS200WEMAH1APR2 when improved failover speed (<10 ms), expanded fault logging, or the latest firmware is required.

  • Network Topology: Configure dual-star or ring redundancy based on plant requirements.

  • Protocol Selection: Select I/O Net for Mark VIe internal communication; Modbus TCP for DCS integration; EtherNet/IP for third-party devices.

  • Compatibility: Fits all Mark VIe VME64x racks. Requires ControlST v6.5 or higher for full PR2 features (v6.0 operates in base compatibility mode).

  • Firmware: PR2 firmware is pre-loaded—no field update required.


Operational Precautions

  1. Wiring: Use shielded CAT5e or CAT6 cables; avoid routing near high-power cables.

  2. Port Status: Green = link/active; Amber = activity; Blink codes indicate specific fault conditions—refer to GEH-6701 for PR2-specific codes.

  3. Redundancy Testing: Simulate port failure to verify <10 ms automatic failover during commissioning.

  4. Diagnostic Blink Codes: Refer to GEH-6701 for expanded blink code table (PR2-specific codes added for firmware-related faults).

  5. Fault Log: Access 750-event log via Toolbox ST for post-event analysis.

  6. Hot-Swap: Remove/insert slowly under power—processor auto-recognizes new module.

  7. Spare Stock: Maintain 1 spare per 3–4 racks; “PR2” backward-compatible with all WEMA sockets.

  8. Firmware: No field firmware updates required—PR2 is factory-loaded. Do not attempt to downgrade firmware.

  9. ESD: Handle by edges only with grounded wrist strap.

  10. Storage: Anti-static bag at –40 to +85 °C; rotate every 3 years for inspection.

A-B 1746-NI8
A-B 1756-DNB
AGILENT E1458A

Reviews

There are no reviews yet.

Be the first to review “IS200WEMAH1APR2 GE”

Your email address will not be published. Required fields are marked *

Post comment