IS200TPROH1A GE

¥999.00

IS200TPROH1A is a Terminal Board within the GE Mark VIe Speedtronic control system, designed as a field termination and signal conditioning interface for speed probe and proximity probe inputs in turbine control applications. This board provides centralized termination for speed sensors such as magnetic pickups, proximity probes, and other frequency-output devices used for turbine shaft speed monitoring, overspeed detection, and speed control. The IS200TPROH1A features integrated termination points for speed inputs with built-in signal conditioning including filtering, isolation, and surge protection. It offers up to 4 independent speed input channels with programmable scaling, frequency measurement, and comprehensive diagnostics.

Category:

Description

Product Parameters

Parameter Specification
Brand / Series GE Mark VIe Speedtronic
Model IS200TPROH1A
Speed Inputs Up to 4 independent channels (configurable)
Input Signal Types Magnetic pickups, proximity probes (passive/active), TTL, 5–24 VDC logic
Frequency Range 0.5 Hz – 20 kHz
Input Voltage Range ±30 VDC maximum
Input Impedance > 10 kΩ
Trigger Level Programmable per channel (0.5–24 VDC, hysteresis configurable)
Scaling Programmable (RPM, Hz, etc.) via GE ToolboxST
Accuracy ±0.01% of reading
Isolation 1500 VAC (field-to-system)
Diagnostics Open-circuit detection, signal loss detection, frequency out-of-range monitoring
Status Indication 4 green LEDs (channel active), 4 red LEDs (channel fault), 2 red summary fault LEDs
Operating Temperature –30°C to +65°C
Storage Temperature –55°C to +85°C
Mounting VME rack-mount terminal board with front-panel I/O connectors
Backplane Interface VME64x (A24/A32, D16/D32/D64)
EMC Compliance IEC 61000-4 Level 4

Advantages & Key Features

  • High-Density Speed Monitoring: Up to 4 independent speed inputs in a single VME slot, ideal for multi-shaft turbine applications.

  • Versatile Signal Compatibility: Supports magnetic pickups, proximity probes, TTL, and logic-level signals.

  • Programmable Trigger Levels: Per-channel programmable trigger voltage and hysteresis ensure reliable signal detection across different sensor types.

  • Wide Frequency Range: 0.5 Hz to 20 kHz covers turbine startup to overspeed conditions.

  • High Accuracy: ±0.01% reading accuracy provides precise speed and frequency measurements.

  • Programmable Scaling: Direct scaling to engineering units (RPM) via GE ToolboxST.

  • Comprehensive Diagnostics: Open-circuit, signal loss, and frequency out-of-range monitoring per channel.

  • Opto-Isolation: 1500 VAC isolation protects the Mark VIe backplane from field wiring faults.

  • ToolboxST Integration: Full configuration, monitoring, and diagnostics via GE ToolboxST.

  • Drop-In Replacement: Direct replacement for earlier GE speed probe terminal boards.

Application Fields

  • Gas & Steam Turbines (GE Frame 6B/7EA/9E/HA): Shaft speed monitoring, overspeed detection, speed control.

  • Aeroderivative Turbines: Speed monitoring and overspeed protection.

  • Compressor Stations: Compressor speed monitoring.

  • Generator Speed Monitoring: Turbine-generator speed measurement.

  • Multi-Shaft Applications: Speed monitoring of multiple turbine sections.

Comparison with Competing Products

Feature GE IS200TPROH1A Competitor A (Speed Probe Module) Competitor B (Speed Monitor)
Speed Inputs Up to 4 2 1
Frequency Range 0.5 Hz – 20 kHz 1 Hz – 10 kHz 1 Hz – 15 kHz
Accuracy ±0.01% ±0.1% ±0.05%
Diagnostics Open, loss, out-of-range Open only Loss only
Isolation 1500 VAC 1000 VAC 500 VDC
Operating Temp –30°C to +65°C 0°C to 50°C 0°C to 60°C

Key AdvantageIS200TPROH1A provides up to 4 independent speed inputs—double the density of competing modules—with wide signal compatibility, programmable trigger levels, high accuracy (±0.01%), and comprehensive diagnostics, making it ideal for multi-shaft turbine speed monitoring applications.

Selection Guidelines & Recommendations

  • Input Count: Determine the number of speed inputs required (up to 4 per board).

  • Sensor Type: Verify speed sensor type and configure trigger levels in GE ToolboxST.

  • Scaling Configuration: Program scaling factors for RPM or other engineering units.

  • Controller Firmware: Requires Mark VIe processor firmware v7.5 or later.

  • Wiring Guidelines: Use shielded twisted-pair cables for speed probes. Maintain shield grounding only at the Mark VIe cabinet end.

  • Spare Strategy: Keep one spare per turbine; lead times 6–8 weeks.

  • Retrofit: Direct replacement—regenerate configuration in GE ToolboxST.

Important Cautions

  1. No Hot-Swap: De-energize rack before insertion/removal.

  2. Signal Polarity: For magnetic pickups, observe correct polarity for reliable zero-crossing detection.

  3. Trigger Level: Incorrect trigger level can cause missed pulses or false triggering—verify with sensor specifications.

  4. Cable Length: For magnetic pickups, use low-capacitance cables for runs exceeding 50 meters.

  5. Grounding: Connect AGND to Mark VIe system ground at single star point.

  6. Shield Termination: Ground speed probe cable shields only at cabinet end.

  7. ESD Handling: Use grounded wrist straps; field repair not possible.

  8. Frequency Out-of-Range: Monitor diagnostic alerts for out-of-range conditions—investigate sensor or wiring faults.

  9. Channel Mapping: With up to 4 channels, verify field wiring maps to correct ToolboxST channel numbers.