IS200TDBTH6A

¥999.00

IS200TDBTH6A is a high-density Terminal Board within the GE Mark VIe Speedtronic control system, designed as a field termination and signal conditioning interface for thermocouple and analog input signals with mixed channel configuration, enhanced diagnostics, and extended temperature range. This board provides centralized termination for both thermocouple sensors and analog transmitters in a single board, making it ideal for applications requiring both temperature and process variable monitoring. The IS200TDBTH6A features integrated termination points with built-in cold-junction compensation (CJC) for thermocouple inputs and signal conditioning for analog inputs, all with enhanced isolation and comprehensive diagnostics.

Category:

Description

Product Parameters

Parameter Specification
Brand / Series GE Mark VIe Speedtronic
Model IS200TDBTH6A
Total Channels 32 mixed inputs (configurable)
Thermocouple Inputs Up to 16 channels (J, K, T, E, R, S, B)
Analog Inputs Up to 16 channels (4–20 mA, 0–10 V, ±10 V selectable)
Thermocouple Range ±100 mV
Analog Range 0–20 mA, 4–20 mA, 0–5 V, 0–10 V, ±10 V
Cold-Junction Compensation Built-in CJC sensor (accuracy ±0.5°C)
ADC Resolution 24-bit delta-sigma (thermocouple), 16-bit SAR (analog)
Sampling Rate 4–200 SPS (thermocouple), 10–500 SPS (analog)
Accuracy TC: ±0.1% + ±1°C; Analog: ±0.1% FS
Loop Power 24 VDC (externally supplied only)
Isolation 2000 VAC (field-to-system)
CMRR >110 dB @ 50/60 Hz
Diagnostics Open-circuit, short-circuit, over/under-range, CJC fault monitoring, reference validation
Status Indication 32 green LEDs (channel active), 2 red LEDs (diagnostic fault summary), 1 yellow LED (reference status)
Operating Temperature –40°C to +70°C
Storage Temperature –55°C to +85°C
Mounting VME rack-mount terminal board with front-panel I/O connectors
Backplane Interface VME64x (A24/A32, D16/D32/D64)
EMC Compliance IEC 61000-4 Level 4

Advantages & Key Features

  • Mixed Input FlexibilityIS200TDBTH6A combines thermocouple and analog inputs on a single board with high channel density, eliminating the need for separate terminal boards for temperature and process variable monitoring.

  • Configurable Channel Allocation: The channel configuration is software-configurable via GE ToolboxST, allowing up to 16 thermocouple and 16 analog inputs to match specific application requirements.

  • High Channel Density: 32 total inputs in a single VME slot—four times the density of competing 8-channel modules.

  • Extended Temperature Range: –40°C to +70°C operation makes IS200TDBTH6A suitable for arctic, desert, and unheated turbine enclosures.

  • Enhanced Isolation: 2000 VAC isolation and >110 dB CMRR provide superior protection in high-EMI environments.

  • High-Precision CJC: Built-in CJC sensor with automatic compensation ensures thermocouple measurement accuracy.

  • 24-Bit Thermocouple Conversion: High-resolution ADC delivers stable, noise-free temperature readings.

  • Programmable Analog Inputs: Each analog channel supports 4–20 mA, 0–10 V, or ±10 V inputs.

  • Comprehensive Diagnostics: Real-time open-circuit, short-circuit, over/under-range, CJC fault, and reference validation per channel.

  • ToolboxST Integration: Full configuration, calibration, and diagnostics via GE ToolboxST.

  • Drop-In Replacement: Direct replacement for earlier GE mixed input terminal boards.

Application Fields

  • Gas & Steam Turbines (GE Frame 6B/7EA/9E/HA): Exhaust gas temperature (thermocouple) combined with fuel gas pressure (4–20 mA), steam pressure (4–20 mA), valve position feedback (0–10 V), and bearing temperature (thermocouple).

  • Combined Cycle Plants: HRSG superheater temperature (thermocouple) plus feedwater flow (4–20 mA), steam drum pressure (4–20 mA), and condensate temperature (thermocouple).

  • Compressor Stations: Discharge temperature (thermocouple) combined with suction pressure (4–20 mA) and vibration monitoring.

  • Aeroderivative Turbines: Exhaust temperature (thermocouple) plus fuel flow (4–20 mA), oil pressure (4–20 mA), and guide vane position (0–10 V).

  • Arctic & Desert Installations: Extreme-environment turbine control cabinets requiring mixed input monitoring.

Comparison with Competing Products

Feature GE IS200TDBTH6A GE IS200TCATH1A (32-ch) Competitor A (Mixed I/O) Competitor B (Separate TC + Analog)
Total Inputs 32 mixed 32 mixed 8 mixed 16 (8 TC + 8 analog)
CJC Accuracy ±0.5°C ±0.5°C ±1.2°C ±0.5°C
Accuracy (TC) ±0.1% + ±1°C ±0.1% + ±1°C ±0.2% + ±2°C ±0.1% + ±1°C
Accuracy (Analog) ±0.1% FS ±0.1% FS ±0.2% FS ±0.1% FS
Isolation 2000 VAC 1500 VAC 1000 VAC 1500 VAC
CMRR >110 dB >100 dB >80 dB >100 dB
Operating Temp –40°C to +70°C –30°C to +65°C 0°C to 50°C –30°C to +65°C
Reference Validation Yes No No No

Key AdvantageIS200TDBTH6A delivers 32 mixed thermocouple and analog inputs with extended –40°C to +70°C temperature range, 2000 VAC isolation, and comprehensive diagnostics including reference validation—making it an ideal solution for turbine applications requiring both temperature and process variable monitoring in extreme environments.

Selection Guidelines & Recommendations

  • Channel Configuration: Determine the required mix of thermocouple and analog inputs—configure in GE ToolboxST.

  • Thermocouple Type: Verify your thermocouple types. IS200TDBTH6A supports J, K, T, E, R, S, and B.

  • Analog Input Type: Configure 4–20 mA, 0–10 V, or ±10 V per analog channel.

  • Loop Power: External 24 VDC supplies required—plan cabinet power distribution.

  • CJC Sensor Placement: Maintain adequate airflow around the CJC sensor on the terminal block.

  • Controller Firmware: Requires Mark VIe processor firmware v8.5 or later.

  • Spare Strategy: Keep one spare per turbine; lead times 8–12 weeks.

  • Retrofit: Direct replacement for IS200TCATH1A—regenerate configuration in GE ToolboxST.

Important Cautions

  1. No Hot-Swap: De-energize rack before insertion/removal.

  2. Thermocouple Polarity: Reverse connection produces negative readings.

  3. Analog Polarity: Observe correct polarity for 4–20 mA loops and voltage inputs.

  4. CJC Protection: Do not apply conformal coating or tape over the terminal block area.

  5. Loop Power: External 24 VDC required—ensure supplies are connected.

  6. Grounding: Connect AGND to Mark VIe system ground at single star point.

  7. Shield Termination: Ground shields only at cabinet end.

  8. ESD Handling: Use grounded wrist straps; field repair not possible.

  9. Temperature Rating: Verify cabinet ambient does not exceed +70°C or fall below –40°C.

  10. Reference Validation: Yellow LED indicates reference drift—schedule factory recalibration if illuminated.

  11. Channel Mapping: With 32 mixed channels, verify field wiring maps to correct ToolboxST assignments.

A-B 1747-SN
BENTLY 330180-51-00
FANUC A05B-2452-C900

Reviews

There are no reviews yet.

Be the first to review “IS200TDBTH6A”

Your email address will not be published. Required fields are marked *

Post comment