IS200TBQGH2A GE

¥999.00

IS200TBQGH2A is a high-capacity Terminal Board within the GE Mark VIe Speedtronic control system, designed as a high-density field termination and signal conditioning interface for discrete output signals with enhanced contact rating and diagnostics. This board provides centralized termination for field actuators such as solenoids, contactors, motor starters, alarms, and trip actuators, connecting to the Mark VIe main VME-based controller processors via front-panel I/O cables. The IS200TBQGH2A features integrated termination points for discrete outputs with built-in signal conditioning including relay isolation, surge suppression, and diagnostics. It offers 48 isolated discrete output channels with high contact rating, built-in suppression, comprehensive diagnostics, and extended temperature range.

Category:

Description

Product Parameters

Parameter Specification
Brand / Series GE Mark VIe Speedtronic
Model IS200TBQGH2A
Discrete Outputs 48 isolated channels (Form C, SPDT)
Contact Rating 8A @ 250 VAC / 30 VDC (resistive load)
Switching Voltage 250 VAC / 30 VDC maximum
Switching Current 8A maximum per channel
Inrush Capability 15A for 50 ms (motor/inductive loads)
Coil Voltage 24 VDC (internally supplied from Mark VIe rack)
Coil Current 40 mA per relay (1.92 A total maximum)
Response Time < 8 ms (energize), < 4 ms (de-energize)
Electrical Life 150,000 operations at rated load
Mechanical Life 1,500,000 operations (no load)
Suppression Built-in flyback diodes (DC loads), RC snubbers (AC loads), and MOV (transient suppression)
Isolation 2000 VAC (channel-to-channel and field-to-system) — upgraded from 1500 VAC
Diagnostics Coil open-circuit detection, coil short-circuit detection, welded contact monitoring, contact wear monitoring
Status Indication 48 green LEDs (output energized), 48 red LEDs (fault per channel), 2 red summary fault LEDs
Operating Temperature –40°C to +70°C — upgraded from –30°C to +65°C
Storage Temperature –55°C to +85°C
Mounting VME rack-mount terminal board with front-panel I/O connectors
Backplane Interface VME64x (A24/A32, D16/D32/D64)
EMC Compliance IEC 61000-4 Level 4

Advantages & Key Features

  • Highest Channel Density + Contact Rating: 48 isolated discrete outputs with 8A contact rating—the best combination of channel density and current capability in the Mark VIe discrete output terminal family. Six times the channel count of competing modules.

  • Extended Temperature Range: –40°C to +70°C operation makes IS200TBQGH2A suitable for arctic, desert, and unheated turbine enclosures.

  • Enhanced Isolation: 2000 VAC isolation provides superior protection for the Mark VIe backplane from field wiring faults and surges.

  • High Inrush Capability: 15A for 50 ms enables direct control of large solenoids, contactors, and motor starters without external intermediate relays.

  • Enhanced Suppression: Integrated flyback diodes, RC snubbers, and MOVs protect relay contacts and driver circuits.

  • Fast Response: < 8 ms energize and < 4 ms de-energize times ensure precise control of high-speed turbine actuators.

  • Comprehensive Diagnostics: Coil open/short, welded contact, and contact wear monitoring per channel enable predictive maintenance.

  • High-Density Status Indication: 48 green/red LEDs per channel enable rapid on-site troubleshooting.

  • ToolboxST Integration: Full configuration, monitoring, and diagnostics via GE ToolboxST.

  • Drop-In Replacement: Direct replacement for IS200TBQGH1A and earlier discrete output terminal boards.

Application Fields

  • Gas & Steam Turbines (GE Frame 6B/7EA/9E/HA): Fuel gas shut-off valves, emergency stop solenoids, alarm annunciators, lube oil pump starters, generator breaker trip coils, cooling fan starters, auxiliary system actuators.

  • Combined Cycle Plants: Steam turbine extraction valves, bypass actuators, HRSG damper controls, condensate pump starters.

  • Compressor Stations: Anti-surge valve solenoids, discharge blow-down valves, station shutdown relays.

  • Aeroderivative Turbines: Fuel control solenoids, bleed valve actuators, oil temperature control.

  • Arctic & Desert Installations: Extreme-environment turbine control cabinets.

  • Offshore Platforms: Marine enclosures with salt-spray and wide temperature swings.

Comparison with Competing Products

Feature GE IS200TBQGH2A GE IS200TBQGH1A GE IS200TBQGH1AAA (10A) Competitor A (Emerson) Competitor B (Siemens)
Discrete Outputs 48 isolated 48 isolated 48 isolated 8 isolated 8 isolated
Contact Rating 8A (15A inrush) 8A (15A inrush) 10A (20A inrush) 2A 5A
Suppression Flyback, RC, MOV Flyback, RC, MOV Flyback, RC, enhanced MOV External External
Diagnostics Coil open/short, welded, wear Coil open/short, welded, wear Coil open/short, welded, wear, reference Coil open only None
Isolation 2000 VAC 1500 VAC 2000 VAC 1000 VAC 500 VDC
Operating Temp –40°C to +70°C –30°C to +65°C –40°C to +70°C 0°C to 50°C 0°C to 60°C
Reference Validation No No Yes No No

Key AdvantageIS200TBQGH2A delivers 48 isolated discrete outputs with 8A contact rating, 2000 VAC isolation, and extended –40°C to +70°C temperature range—providing the ideal balance of channel density, current capability, and environmental robustness for large turbine systems in extreme conditions. It offers enhanced isolation and temperature range over the IS200TBQGH1A while maintaining the same channel count and contact rating.

Selection Guidelines & Recommendations

  • Contact Rating: Confirm load requirements do not exceed 8A @ 250 VAC or 8A @ 30 VDC. For inductive loads, de-rate to 5A to account for inrush.

  • Inrush Capability: 15A for 50 ms handles motor/inductive startup currents—verify your load’s inrush does not exceed this.

  • Load Protection: For highly inductive DC loads, add external varistors at the load side to further reduce voltage spikes.

  • Diagnostic Configuration: Enable welded contact and wear monitoring for critical safety circuits.

  • Controller Firmware: Requires Mark VIe processor firmware v8.0 or later.

  • Spare Strategy: Keep one spare per turbine; lead times 8–12 weeks.

  • Retrofit: Direct replacement for IS200TBQGH1A—regenerate configuration in GE ToolboxST to access enhanced isolation and extended temperature calibration.

Important Cautions

  1. No Hot-Swap: De-energize rack before insertion/removal.

  2. Wiring Polarity: For DC loads, observe correct polarity—reverse polarity shorts through the flyback diode and may damage the driver circuit.

  3. Contact Protection: For loads exceeding 8A or highly inductive loads, use external contactors to protect relay contacts.

  4. Grounding: Connect chassis ground at single star point to avoid ground loops.

  5. Shield Termination: Ground output cable shields only at cabinet end.

  6. ESD Handling: Use grounded wrist straps; field repair not possible.

  7. Temperature Rating: Verify cabinet ambient does not exceed +70°C or fall below –40°C.

  8. Channel Mapping: With 48 channels, verify field wiring maps to correct ToolboxST channel numbers.

  9. Welded Contact Detection: Requires proper wiring configuration—refer to GE wiring diagram IS200TBQGH2A-DWG.

  10. Wear Monitoring: Set appropriate operational thresholds in GE ToolboxST to receive maintenance alerts before contacts reach end-of-life.

  11. Power Supply: Ensure rack power supply provides adequate current for all active outputs (40 mA × 48 channels = 1.92 A max).

A-B 1756-PA75
SCHNEIDER TSXAEY420
FOXBORO FBM201
A-B 1756-IF8

Reviews

There are no reviews yet.

Be the first to review “IS200TBQGH2A GE”

Your email address will not be published. Required fields are marked *