IS200SPIDG1ABA GE

¥999.00

IS200SPIDG1ABA is a Power Distribution Board within the GE Mark VIe Speedtronic control system, designed to distribute and condition DC power to VME-based turbine control modules. This board provides regulated +5V, +12V, -12V, and +24V outputs to multiple backplane slots, with built-in overvoltage, overcurrent, and thermal protection. It includes input filtering, surge suppression, and status monitoring for reliable power delivery to critical GE turbine control components.

Category:

Description

Product Parameters

Parameter Specification
Brand / Series GE Mark VIe Speedtronic
Model IS200SPIDG1ABA
Input Voltage 125 VDC or 240 VDC (jumpered)
Output Rails +5V @ 20A, +12V @ 5A, -12V @ 3A, +24V @ 2A (isolated)
Total Output Power 250W continuous
Protection Overvoltage, overcurrent, short-circuit, overtemperature
Status Indicators 4 LED indicators per rail (OK/FAULT), input power LED
Voltage Regulation ±1% (all rails)
Ripple/Noise < 50 mV peak-to-peak
Isolation 1500 VAC (input-to-output)
Operating Temperature –30°C to +65°C
Mounting VME 6U rack-mount with backplane connectors

Advantages & Key Features

  • Multiple Isolated Outputs: Provides all necessary voltages for Mark VIe modules in a single board, reducing cabling and external power supplies.

  • Comprehensive Protection: Overvoltage crowbar, current limiting, and thermal shutdown protect expensive processor and I/O boards from power faults.

  • Status Monitoring: Each output rail has dedicated OK/FAULT LEDs and backplane-accessible status registers via GE ToolboxST.

  • High Efficiency: >85% conversion efficiency reduces heat generation within the Mark VIe cabinet.

  • Backplane Integration: Directly powers VME backplane slots without external wiring, simplifying installation.

  • Drop-In Replacement: Direct mechanical/electrical replacement for earlier GE power boards such as IS200SPIDH1A and IS200SPIDG1A.


Application Fields

  • Gas & Steam Turbines (GE Frame 6B/7EA/9E/HA): Supplies power to VME processors (IS420UCSBH1AIS420UCSCH1A), I/O boards (IS200SCTLG1ABAIS200SCTTG1AAA), and communication modules.

  • Combined Cycle Plants: Powers HRSG control system components.

  • Oil & Gas: Provides reliable DC power for compressor station control panels.

  • Offshore Platforms: Used in marine turbine enclosures where compact power distribution is essential.


Comparison with Competing Products

Feature GE IS200SPIDG1ABA Competitor A (Emerson PWR Supply) Competitor B (Siemens PS Module)
Output Rails 4 (isolated) 2 (non-isolated) 3 (non-isolated)
Total Power 250W 150W 192W
Voltage Regulation ±1% ±3% ±2%
Protection OV, OC, OT, short OV, OC only OV, OC only
Backplane Direct Power Yes No No
Status Monitoring Per-rail via ToolboxST External LED only External LED only

Key AdvantageIS200SPIDG1ABA provides more isolated output rails and higher total power than competitors, with direct backplane integration and per-rail status monitoring via the Mark VIe system.


Selection Guidelines & Recommendations

  • Input Voltage: Select 125 VDC or 240 VDC via onboard jumper. Verify plant battery voltage before setting.

  • Load Calculation: Ensure total load on each rail does not exceed specified limits (e.g., +5V @ 20A max). Use GE ToolboxST to monitor rail currents.

  • Controller Firmware: Use Mark VIe firmware v6.0 or later for full status register readback from IS200SPIDG1ABA.

  • Spare Strategy: Keep one spare per turbine cabinet; lead times typically 6–10 weeks.

  • Retrofit: Direct replacement for IS200SPIDH1A and IS200SPIDG1A—no cabling changes required.


Important Cautions

  1. No Hot-SwapIS200SPIDG1ABA is not hot-swappable. Always de-energize the Mark VIe rack before insertion/removal.

  2. Jumper Setting: Input voltage jumper (JP1) must be set before power-on. Incorrect setting will damage the board.

  3. Load Balance: Do not exceed per-rail current ratings. Distribute loads across rails evenly where possible.

  4. Cooling: Ensure adequate airflow around IS200SPIDG1ABA as it dissipates up to 40W of heat.

  5. Grounding: Connect system ground at a single star point to avoid ground loops.

  6. ESD Handling: Use grounded wrist straps during handling; field repair not possible due to conformal coating.