GE Mark VIe IS200TPIMG1A

¥999.00

IS200TPIMG1A is a Terminal Board within the GE Mark VIe Speedtronic control system, designed as a field termination and signal conditioning interface for pulse input signals in turbine control applications. This board provides centralized termination for pulse-generating sensors such as speed probes, magnetic pickups, proximity probes, flow meters, and other frequency-output devices, connecting to the Mark VIe main VME-based controller processors via front-panel I/O cables. The IS200TPIMG1A features integrated termination points for pulse inputs with built-in signal conditioning including filtering, isolation, and surge protection. It offers 16 isolated pulse input channels with programmable scaling, frequency measurement, and comprehensive diagnostics.

Category:

Description

Product Parameters

Parameter Specification
Brand / Series GE Mark VIe Speedtronic
Model IS200TPIMG1A
Pulse Inputs 16 isolated channels
Input Signal Types Magnetic pickups, proximity probes (NPN/PNP), TTL, 5–24 VDC logic, dry contact
Frequency Range 0.5 Hz – 20 kHz
Input Voltage Range ±30 VDC maximum
Input Impedance > 10 kΩ
Trigger Level Programmable (0.5–24 VDC, hysteresis configurable)
Scaling Programmable (RPM, Hz, flow rate, etc.) via GE ToolboxST
Accuracy ±0.01% of reading
Isolation 1500 VAC (channel-to-channel and field-to-system)
Diagnostics Open-circuit detection, signal loss detection, frequency out-of-range monitoring
Status Indication 16 green LEDs (channel active), 2 red LEDs (diagnostic fault summary)
Operating Temperature –30°C to +65°C
Storage Temperature –55°C to +85°C
Mounting VME rack-mount terminal board with front-panel I/O connectors
Backplane Interface VME64x (A24/A32, D16/D32/D64)
EMC Compliance IEC 61000-4 Level 4

Advantages & Key Features

  • High Channel Density: 16 isolated pulse inputs in a single VME slot—double the density of competing 8-channel modules, ideal for turbines with multiple speed probes and flow meters.

  • Versatile Signal Compatibility: Supports magnetic pickups, proximity probes, TTL, logic-level signals, and dry contacts, accommodating a wide range of pulse-generating sensors.

  • Programmable Trigger Levels: Per-channel programmable trigger voltage and hysteresis ensure reliable signal detection across different sensor types.

  • Wide Frequency Range: 0.5 Hz to 20 kHz covers low-speed flow meters to high-speed turbine speed probes.

  • High Accuracy: ±0.01% reading accuracy provides precise speed and frequency measurements.

  • Programmable Scaling: Direct scaling to engineering units (RPM, Hz, flow rate) via GE ToolboxST.

  • Comprehensive Diagnostics: Open-circuit, signal loss, and frequency out-of-range monitoring per channel enables predictive maintenance.

  • Opto-Isolation: 1500 VAC isolation protects the Mark VIe backplane from field wiring faults and surges.

  • ToolboxST Integration: Full configuration, monitoring, and diagnostics via GE ToolboxST.

  • Drop-In Replacement: Direct replacement for earlier GE pulse input terminal boards.

Application Fields

  • Gas & Steam Turbines (GE Frame 6B/7EA/9E/HA): Speed probes (turbine shaft speed), overspeed detection, flow meters for fuel gas, and vibration frequency monitoring.

  • Compressor Stations: Shaft speed monitoring, flow metering, and vibration frequency monitoring.

  • Combined Cycle Plants: Speed monitoring for steam turbines and flow metering for feedwater.

  • Aeroderivative Turbines: Speed probes and overspeed detection.

  • Flow Measurement: Pulse output flow meters for gas, liquid, and steam applications.

Comparison with Competing Products

Feature GE IS200TPIMG1A Competitor A (Pulse Input Module) Competitor B (Counter Module)
Pulse Inputs 16 isolated 8 isolated 8 non-isolated
Frequency Range 0.5 Hz – 20 kHz 1 Hz – 10 kHz 0.1 Hz – 50 kHz
Signal Types Mag pickup, proximity, TTL, logic, dry contact TTL, logic only Mag pickup, TTL
Trigger Level Programmable (per-channel) Fixed Programmable
Accuracy ±0.01% ±0.1% ±0.02%
Scaling Programmable (RPM, Hz, flow) Fixed (Hz only) Programmable
Isolation 1500 VAC 1000 VAC 500 VDC
Operating Temp –30°C to +65°C 0°C to 50°C 0°C to 60°C

Key AdvantageIS200TPIMG1A provides 16 isolated pulse inputs—double the density of competing modules—with wide signal compatibility, programmable trigger levels, high accuracy (±0.01%), and programmable scaling, making it ideal for turbine speed monitoring and flow measurement applications.

Selection Guidelines & Recommendations

  • Signal Type: Verify your pulse sensor type (magnetic pickup, proximity probe, TTL, etc.) and configure trigger levels accordingly.

  • Frequency Range: Confirm the expected frequency range of your application and select appropriate scaling in GE ToolboxST.

  • Scaling Configuration: Program scaling factors for RPM, flow rate, or other engineering units in GE ToolboxST.

  • Controller Firmware: Requires Mark VIe processor firmware v7.5 or later.

  • Wiring Guidelines: Use shielded twisted-pair cables for pulse inputs, especially for magnetic pickups and long cable runs. Maintain shield grounding only at the Mark VIe cabinet end.

  • Spare Strategy: Keep one spare per turbine; lead times 6–8 weeks.

  • Retrofit: Direct replacement—regenerate configuration in GE ToolboxST.

Important Cautions

  1. No Hot-Swap: De-energize rack before insertion/removal.

  2. Signal Polarity: For magnetic pickups and proximity probes, observe correct polarity for proper signal detection.

  3. Trigger Level: Incorrect trigger level settings can cause missed pulses or false triggering—verify with sensor specifications.

  4. Cable Length: For magnetic pickups, cable capacitance affects signal quality. Use low-capacitance cables for runs exceeding 50 meters.

  5. Grounding: Connect AGND to Mark VIe system ground at single star point—multiple grounds degrade signal quality.

  6. Shield Termination: Ground pulse input cable shields only at cabinet end to avoid ground loops.

  7. ESD Handling: Use grounded wrist straps; field repair not possible.

  8. Frequency Out-of-Range: Monitor diagnostic alerts for frequency out-of-range conditions—investigate sensor or wiring faults.

  9. Channel Mapping: With 16 channels, verify field wiring maps to correct ToolboxST channel numbers.

A-B 1747-L542
Schneider 171CCC96020
Schneider 140CRA93200
Honewell CC-TAID11

Reviews

There are no reviews yet.

Be the first to review “GE Mark VIe IS200TPIMG1A”

Your email address will not be published. Required fields are marked *