Description
Technical Parameters
Manufacturer: GE
Series: Mark V / Mark VIe
Channels: 16 differential
Input Range: -10 mV to +100 mV (Type J/K/T/E)
Cold Junction: Single onboard standard sensor
Isolation: 1500V AC
Accuracy: ±0.12% at 25°C, ±0.20% across full temperature range
Sampling: 5 Hz sequential
Temp Range: -25°C to +60°C (operating), -40°C to +85°C (storage)
Mounting: VME rack
Suffix “G1ABC”: Basic accuracy (0.12%) + G1 wiring + “ABC” coating package (typically indicates a specific conformal coating formulation or combination – often enhanced acrylic or silicone blend with improved moisture/chemical resistance over standard, but not full PTFE or military-grade)
Key Features
Standard accuracy – ±0.12% for general-purpose temperature monitoring
Specialized “ABC” coating – enhanced conformal coating offering improved moisture and mild chemical resistance compared to standard acrylic, suitable for moderately harsh environments
G1 wiring configuration – standard channel-to-terminal mapping matching most GE cabinets
Basic self-diagnostics – open-circuit and short-circuit detection per channel
Simple swap – no firmware changes required in most Mark V systems
LED status per channel + board health
Backward compatible with Mark V and Mark VIe (hot-swap only on VIe Rev D+)
Applications
Coastal power plants with moderate salt exposure – where standard coating may not be sufficient but full military-grade is unnecessary
Industrial environments with occasional chemical fumes – moderate protection against mild corrosives
High-humidity indoor installations – where moisture resistance is a priority
Paper and pulp mills – moderate chemical and moisture protection
Food processing plants – where cleaning chemicals are used but not aggressively
Comparison with Competitors
| Feature | DS200TCEBG1ABC |
ABB TTH300 | Siemens 7KG7750 |
|---|---|---|---|
| Channels | 16 | 8 | 12 |
| Accuracy | ±0.12% | ±0.10% | ±0.12% |
| Sampling | 5 Hz | 10 Hz (simultaneous) | 8 Hz (simultaneous) |
| Temp Range | -25°C to +60°C | -25°C to +65°C | -20°C to +60°C |
| Coating Type | “ABC” enhanced (mid-grade) | Standard acrylic | Standard acrylic |
| Chemical Resistance | Moderate | Low | Low |
| Moisture Resistance | Good (better than standard) | Moderate | Moderate |
| Hot-Swap | No (V) / Yes (VIe) | No | Yes |
| GE Native Integration | Yes | No | No |
Selection Tips
Choose the DS200TCEBG1ABC if you need moderate environmental protection (better than standard acrylic but not PTFE or military-grade) with basic accuracy in a G1 cabinet
For standard environments, the DS200TCEBG1 is more economical
For severe chemical exposure, consider the DS200TCEAG1BTF (PTFE) or DS200TCEAG1BJE (military-grade)
For high accuracy needs with the same coating, upgrade to the DS200TCEAG1B with the ABC coating (if available)
Verify the exact coating specification – “ABC” may indicate specific GE internal coating codes; confirm with your supplier
Source refurbished units with coating inspection verification
Precautions
ESD sensitive – use wrist strap
Power down for Mark V removal (no hot-swap)
Torque terminals to 0.5 N·m max
Do not exceed -25°C to +60°C operating range
Avoid damaging the coating – scratches compromise protection
Do not use aggressive solvents for cleaning – the “ABC” coating may be vulnerable to acetone or MEK; use isopropyl alcohol only
Calibrate every 24 months – accuracy spec depends on valid calibration
Ground shields only at the board end
Verify thermocouple type – hardware optimized for J/K (T/E reduces accuracy to ±0.20%)
Label clearly – mark board and slot as “G1ABC – ENHANCED COATING” to ensure proper handling

CUTLER-HAMMER E511A12X3N
ALSTOM ESA-700
A-B 1756-CNBR
Schneider 140CRA93200


Reviews
There are no reviews yet.