Description
Product Parameters
| Parameter | Specification |
|---|---|
| Model | IS220PAICH1B |
| Manufacturer | GE Energy / Baker Hughes |
| Platform | Mark VIe |
| Bus Interface | PCI Express (PCIe) via backplane |
| Analog Inputs | 8 channels (differential or single-ended) |
| Analog Outputs | 4 channels (isolated) |
| Input Range | 0–10 VDC, ±10 VDC, 4–20 mA, 0–20 mA (software configurable) |
| Output Range | 0–10 VDC, ±10 VDC, 4–20 mA (software configurable) |
| Resolution | 16-bit (input) / 14-bit (output) |
| Accuracy | ±0.05% of full scale (input) / ±0.15% (output) |
| Sampling Rate | 1 kHz per channel (configurable) |
| Isolation | 1500 V (channel-to-backplane) |
| Hot-Swap Support | Yes (compliant with Mark VIe platform) |
| LED Indicators | Power, Status (RUN/FAIL), Channel Activity, Communication Status |
| Operating Temperature | -30°C to +65°C |
| Storage Temperature | -40°C to +85°C |
| Humidity | 5% to 95% (non-condensing) |
| Power Consumption | +5 VDC @ 2.0 A, +24 VDC @ 0.5 A (field power) |
| Dimensions | Standard Mark VIe module form factor |
| MTBF | > 180,000 hours |
Advantages and Key Features
-
Enhanced Accuracy – The IS220PAICH1B offers improved input accuracy of ±0.05% (compared to ±0.1% on the IS220PAICH1A), providing more precise data for critical control algorithms.
-
Expanded Output Range – The IS220PAICH1B adds ±10 VDC output capability, offering greater flexibility for controlling valve positioners and actuators.
-
High-Density I/O – Provides 8 analog inputs and 4 analog outputs in a single module, reducing rack space requirements.
-
Flexible Input Configuration – Each input channel on the IS220PAICH1B is independently software-configurable for voltage or current, eliminating external signal conditioners.
-
Galvanic Isolation – 1500 V isolation between I/O channels and backplane protects the control processor from field-side faults.
-
Hot-Swap Capability – The IS220PAICH1B can be replaced in a running system without powering down, minimizing turbine downtime.
-
Enhanced Diagnostics – The IS220PAICH1B includes additional diagnostic features, including open-circuit detection and channel health monitoring.
-
Wide Temperature Range – Rated for -30°C to +65°C, suitable for outdoor and harsh industrial environments.
Application Fields and Use Cases
1. Gas Turbine Temperature Monitoring
The IS220PAICH1B reads thermocouple signals from exhaust gas temperature (EGT) sensors, providing critical data for combustion control.
2. Steam Turbine Pressure and Flow
Input channels connect to pressure transmitters and flow meters for steam pressure and extraction flow monitoring.
3. Valve Position Control
The IS220PAICH1B outputs 4–20 mA or ±10 V signals to control electro-hydraulic actuators and pneumatic positioners.
4. Vibration Monitoring
Accelerometer inputs provide vibration data for bearing health monitoring and overspeed protection.
5. Retrofit Projects
The IS220PAICH1B is used in Mark VIe upgrades from legacy systems, providing modern I/O with improved accuracy.
Comparison with Competing Products
| Feature | IS220PAICH1B (GE) | IS220PAICH1A (GE) | ABB AI845 + AO845 | Siemens 6ES7 331-7KF02 + 332-5HD01 |
|---|---|---|---|---|
| Platform | Mark VIe | Mark VIe | AC 800M | S7-400 |
| Analog Inputs | 8 channels | 8 channels | 8 channels | 8 channels |
| Analog Outputs | 4 channels | 4 channels | 4 channels | 4 channels |
| Accuracy (Input) | ±0.05% | ±0.1% | ±0.1% | ±0.1% |
| Output Range | 0–10 V, ±10 V, 4–20 mA | 0–10 V, 4–20 mA | 0–10 V, 4–20 mA | 0–10 V, 4–20 mA |
| Isolation | 1500 V | 1500 V | 1500 V | 500 V |
| Hot-Swap | Yes | Yes | Yes | No |
| Temp Range | -30°C to +65°C | -30°C to +65°C | -25°C to +60°C | 0°C to +60°C |
| MTBF | > 180,000 hrs | > 150,000 hrs | > 120,000 hrs | > 80,000 hrs |
Key Differentiators: The IS220PAICH1B offers superior accuracy (±0.05%), improved output range (±10 V), and the highest MTBF (180,000 hours) among compared products. It integrates seamlessly with GE’s Mark VIe Toolbox software, providing simplified configuration and diagnostics.
Selection Suggestions and Precautions
Selection Criteria
-
Choose the IS220PAICH1B for new Mark VIe installations requiring the highest accuracy.
-
Upgrade from IS220PAICH1A to IS220PAICH1B if ±10 V output or improved accuracy is needed.
-
Ensure Mark VIe Toolbox version supports the IS220PAICH1B (v8.0 or higher).
-
Verify adequate +24 VDC field power for loop-powered transmitters.
Critical Precautions
-
Field Wiring – Use shielded twisted-pair cables for all analog connections to the IS220PAICH1B to prevent noise pickup. Terminate shields at field device end.
-
Terminal Block – The IS220PAICH1B requires specific terminal blocks (e.g., IS200STAIH1B). Verify compatibility.
-
Loop Power – The IS220PAICH1B does not provide loop power for 4–20 mA inputs. Use external power supplies.
-
Output Loading – Ensure loads do not exceed drive capability: 500Ω for current, 2 kΩ for voltage.
-
ESD Handling – Use grounded wrist straps when handling the IS220PAICH1B to prevent static damage.
-
Hot-Swap – Verify system is properly configured for live insertion of the IS220PAICH1B.
-
Configuration – Use Mark VIe Toolbox to configure input/output ranges, filtering, and diagnostics for each channel.
-
Calibration – The IS220PAICH1B is factory-calibrated. Re-calibration is generally not required in the field.
-
Obsolescence – The IS220PAICH1B is in active production. For future-proofing, evaluate the IS220PAICH1C when available.

A-B 1756-OB16D
FOXBORO P0917XV
GE IC752DFT000-AA
A-B 1756-PA72


Reviews