GE IS210DSVOH2BA

¥999.00

The GE IS210DSVOH2BA is a VMEbus terminal board manufactured by General Electric for the Mark VIe distributed control system (DCS). This board is a high-performance Discrete Solenoid and Valve Output module, representing a significant upgrade over the DSVOH1A series. The GE IS210DSVOH2BA provides high-current discrete outputs for controlling solenoids, valves, contactors, and actuators with higher current capacity, improved diagnostics, and enhanced reliability. The “H2BA” designation indicates a second-generation discrete solenoid and valve output module with the “BA” suffix denoting military-grade components, extended burn-in (120 hours), 100% X-ray/AOI inspection, and conformal coating as standard.

Category:

Description

Key Specifications

Parameter Specification
Output Channels 16 discrete outputs (high-side or low-side configurable)
Output Type Solid-state (MOSFET)
Output Voltage Rating 24 VDC nominal (18–32 VDC)
Output Current 2.5 A per channel (continuous), 6 A per channel (inrush, 150 ms) — improved over H1A
Total Output Current 16 A maximum (module total)
Output Protection Short-circuit, overcurrent, over-temperature, inductive load clamp
Diagnostic Feedback Load current monitoring per channel (±5% accuracy), output state feedback, wire-break detection
Inductive Load Support Built-in flyback diodes for inductive loads
Isolation 1500 VDC (output-to-backplane)
Diagnostics 1000-event fault log with timestamps and waveform snapshots (expanded)
Operating Temp –30 °C to +75 °C (widest range in DSVO family)
Humidity 5–100% condensing (silicone coating standard)
Coating Silicone conformal coating + enhanced edge encapsulation (UV-traceable)
Manufacturing 120-hour burn-in, 100% X-Ray/AOI, military-grade components
Form Factor 6U VME64x (160 × 233 mm), single-slot width
Power 10 W (+5 V / +3.3 VDC) + external 24 VDC field power
Connectors 32-pin terminal block with gold-plated contacts and captive washer screws

Advantages & Distinctive Features

  • 16 High-Capacity Outputs: Controls up to 16 solenoids, valves, or contactors.

  • Higher Inrush Capability: 6 A for 150 ms (improved over H1A).

  • Higher Continuous Current: 2.5 A (improved over H1A).

  • Per-Channel Load Monitoring: ±5% accuracy for precise solenoid degradation detection.

  • Wire-Break Detection: Identifies open circuits in field wiring.

  • Inductive Load Clamping: Built-in flyback diodes protect outputs.

  • Short-Circuit Protection: Auto-shutdown with auto-retry.

  • Silicone Conformal Coating + Edge Encapsulation: Maximum environmental protection.

  • Widest Temperature Range: –30 °C to +75 °C.

  • Condensing Humidity Rating: 5–100% condensing.

  • Expanded Diagnostic Log: 1000-event fault log with waveform snapshots.

  • Gold-Plated Captive Washer Terminals: Corrosion-resistant and vibration-proof.

  • Hot-Swappable: No rack power-down for replacement.

  • Direct Retrofit: Replaces DSVOH1A series boards.


Application Fields

  • Gas Turbines: Trip solenoids, fuel shut-off valves, purge/drain valves, bleed valves

  • Steam Turbines: Emergency stop valves, control valve trip solenoids, drain valves

  • Compressors: Anti-surge blow-off valves, suction/discharge isolation valves

  • Generators: H2 supply shut-off valves, seal oil system valves

  • Offshore platforms: Salt-spray and condensing environments

  • Arctic/Desert Installations: Extreme temperature environments

  • Nuclear Power Plants: Safety-critical solenoid control


Comparison with DSVOH1AA and Competitors

Feature GE IS210DSVOH2BA GE IS210DSVOH1AA Competitor A Competitor B
Output Channels 16 16 16 16
Continuous Current 2.5 A 2 A 0.5 A 2 A
Inrush Current 6 A (150 ms) 5 A (100 ms) No No
Load Monitoring ±5% accuracy ±10% accuracy No No
Wire-Break Detection Yes No No No
Coating Type Silicone + edge encaps. Acrylic Optional Optional
Temp Range –30 to +75 °C –25 to +70 °C 0 to +55 °C 0 to +55 °C
Humidity 5–100% condensing 5–95% non-condensing 5–90% 5–90%
Fault Logging 1000 events + waveforms 750 events No No

Selection Guidelines

  • When to choose:

    • Critical solenoid and valve control requiring higher current and environmental protection

    • Extreme environments (–30 to +75 °C, condensing, salt spray)

    • Applications needing wire-break detection and waveform snapshots

    • Maximum reliability (nuclear, critical infrastructure)

  • When to choose “H1AA” instead: For less extreme environments with lower current requirements.

  • Load Verification: Verify solenoid inrush ≤6 A, holding ≤2.5 A per channel.

  • Field Power Supply: Provide dedicated 24 VDC field power supply with capacity for all solenoids.

  • Coating Verification: Inspect under UV (365 nm)—silicone shows distinct fluorescence; verify edge encapsulation bead.

  • Compatibility: Fits all Mark VIe VME64x racks. Requires ControlST v6.5 or higher.


Operational Precautions

  1. Wiring: Follow GE wiring diagrams—correct polarity for external field power.

  2. Field Power: Properly size and fuse external 24 VDC supply (20 A fuse recommended).

  3. Load Monitoring: Use Toolbox ST to view per-channel current readings—trending increasing current indicates solenoid wear.

  4. Wire-Break Testing: Simulate open circuit to verify wire-break detection.

  5. Short-Circuit Testing: Simulate short to verify auto-shutdown and auto-retry.

  6. LED Diagnostics: Green = output on; Amber = output off with fault; Red = module fault.

  7. Fault Log: Access 1000-event log via Toolbox ST—review waveform snapshots.

  8. Coating Care: Use GE-approved silicone-safe cleaner; inspect annually under UV—rework voids with approved silicone coating per GE FSB-MKVIe-112.

  9. Hot-Swap: Remove/insert slowly under power.

  10. Spare Stock: Maintain 1 spare per 3–4 racks; “H2BA” backward-compatible with all DSVO sockets.

  11. Firmware Updates: Ensure the GE IS210DSVOH2BA is in “standby” mode during updates.

  12. ESD: Handle by edges with grounded wrist strap—coating does not protect connectors.

  13. Storage: Anti-static bag with desiccant at –40 to +85 °C; rotate every 3 years for coating inspection.

BERGHOF QDIO 16/16-0,5
FANUC A20B-2902-0412
A-B 1761-L32AWA