Description
Key Specifications
| Parameter | Specification |
|---|---|
| Output Channels | 16 discrete outputs (high-side or low-side configurable) |
| Output Type | Solid-state (MOSFET) |
| Output Voltage Rating | 24 VDC nominal (18–32 VDC) |
| Output Current | 2.5 A per channel (continuous), 6 A per channel (inrush, 150 ms) — improved over H1A |
| Total Output Current | 16 A maximum (module total) |
| Output Protection | Short-circuit, overcurrent, over-temperature, inductive load clamp |
| Diagnostic Feedback | Load current monitoring per channel (±5% accuracy), output state feedback, wire-break detection |
| Inductive Load Support | Built-in flyback diodes for inductive loads |
| Isolation | 1500 VDC (output-to-backplane) |
| Diagnostics | 1000-event fault log with timestamps and waveform snapshots (expanded) |
| Operating Temp | –30 °C to +75 °C (widest range in DSVO family) |
| Humidity | 5–100% condensing (silicone coating standard) |
| Coating | Silicone conformal coating + enhanced edge encapsulation (UV-traceable) |
| Manufacturing | 120-hour burn-in, 100% X-Ray/AOI, military-grade components |
| Form Factor | 6U VME64x (160 × 233 mm), single-slot width |
| Power | 10 W (+5 V / +3.3 VDC) + external 24 VDC field power |
| Connectors | 32-pin terminal block with gold-plated contacts and captive washer screws |
Advantages & Distinctive Features
-
16 High-Capacity Outputs: Controls up to 16 solenoids, valves, or contactors.
-
Higher Inrush Capability: 6 A for 150 ms (improved over H1A).
-
Higher Continuous Current: 2.5 A (improved over H1A).
-
Per-Channel Load Monitoring: ±5% accuracy for precise solenoid degradation detection.
-
Wire-Break Detection: Identifies open circuits in field wiring.
-
Inductive Load Clamping: Built-in flyback diodes protect outputs.
-
Short-Circuit Protection: Auto-shutdown with auto-retry.
-
Silicone Conformal Coating + Edge Encapsulation: Maximum environmental protection.
-
Widest Temperature Range: –30 °C to +75 °C.
-
Condensing Humidity Rating: 5–100% condensing.
-
Expanded Diagnostic Log: 1000-event fault log with waveform snapshots.
-
Gold-Plated Captive Washer Terminals: Corrosion-resistant and vibration-proof.
-
Hot-Swappable: No rack power-down for replacement.
-
Direct Retrofit: Replaces DSVOH1A series boards.
Application Fields
-
Gas Turbines: Trip solenoids, fuel shut-off valves, purge/drain valves, bleed valves
-
Steam Turbines: Emergency stop valves, control valve trip solenoids, drain valves
-
Compressors: Anti-surge blow-off valves, suction/discharge isolation valves
-
Generators: H2 supply shut-off valves, seal oil system valves
-
Offshore platforms: Salt-spray and condensing environments
-
Arctic/Desert Installations: Extreme temperature environments
-
Nuclear Power Plants: Safety-critical solenoid control
Comparison with DSVOH1AA and Competitors
| Feature | GE IS210DSVOH2BA | GE IS210DSVOH1AA | Competitor A | Competitor B |
|---|---|---|---|---|
| Output Channels | 16 | 16 | 16 | 16 |
| Continuous Current | 2.5 A | 2 A | 0.5 A | 2 A |
| Inrush Current | 6 A (150 ms) | 5 A (100 ms) | No | No |
| Load Monitoring | ±5% accuracy | ±10% accuracy | No | No |
| Wire-Break Detection | Yes | No | No | No |
| Coating Type | Silicone + edge encaps. | Acrylic | Optional | Optional |
| Temp Range | –30 to +75 °C | –25 to +70 °C | 0 to +55 °C | 0 to +55 °C |
| Humidity | 5–100% condensing | 5–95% non-condensing | 5–90% | 5–90% |
| Fault Logging | 1000 events + waveforms | 750 events | No | No |
Selection Guidelines
-
When to choose:
-
Critical solenoid and valve control requiring higher current and environmental protection
-
Extreme environments (–30 to +75 °C, condensing, salt spray)
-
Applications needing wire-break detection and waveform snapshots
-
Maximum reliability (nuclear, critical infrastructure)
-
-
When to choose “H1AA” instead: For less extreme environments with lower current requirements.
-
Load Verification: Verify solenoid inrush ≤6 A, holding ≤2.5 A per channel.
-
Field Power Supply: Provide dedicated 24 VDC field power supply with capacity for all solenoids.
-
Coating Verification: Inspect under UV (365 nm)—silicone shows distinct fluorescence; verify edge encapsulation bead.
-
Compatibility: Fits all Mark VIe VME64x racks. Requires ControlST v6.5 or higher.
Operational Precautions
-
Wiring: Follow GE wiring diagrams—correct polarity for external field power.
-
Field Power: Properly size and fuse external 24 VDC supply (20 A fuse recommended).
-
Load Monitoring: Use Toolbox ST to view per-channel current readings—trending increasing current indicates solenoid wear.
-
Wire-Break Testing: Simulate open circuit to verify wire-break detection.
-
Short-Circuit Testing: Simulate short to verify auto-shutdown and auto-retry.
-
LED Diagnostics: Green = output on; Amber = output off with fault; Red = module fault.
-
Fault Log: Access 1000-event log via Toolbox ST—review waveform snapshots.
-
Coating Care: Use GE-approved silicone-safe cleaner; inspect annually under UV—rework voids with approved silicone coating per GE FSB-MKVIe-112.
-
Hot-Swap: Remove/insert slowly under power.
-
Spare Stock: Maintain 1 spare per 3–4 racks; “H2BA” backward-compatible with all DSVO sockets.
-
Firmware Updates: Ensure the GE IS210DSVOH2BA is in “standby” mode during updates.
-
ESD: Handle by edges with grounded wrist strap—coating does not protect connectors.
-
Storage: Anti-static bag with desiccant at –40 to +85 °C; rotate every 3 years for coating inspection.

BERGHOF QDIO 16/16-0,5
FANUC A20B-2902-0412
A-B 1761-L32AWA


Reviews
There are no reviews yet.