GE IS210DSVOH1A

¥999.00

The GE IS210DSVOH1A is a VMEbus terminal board manufactured by General Electric for the Mark VIe distributed control system (DCS). This board is a dedicated Discrete Solenoid and Valve Output module, designed to provide high-current discrete outputs for controlling solenoids, valves, contactors, and actuators in turbine control applications. The GE IS210DSVOH1A converts digital control signals from the processor board (VPRO series) into robust high-current outputs, enabling reliable switching of inductive and resistive loads. The “H1A” designation indicates a first-generation discrete solenoid and valve output module with robust protection and diagnostic features.

Category:

Description

Key Specifications

Parameter Specification
Output Channels 16 discrete outputs (high-side or low-side configurable)
Output Type Solid-state (MOSFET)
Output Voltage Rating 24 VDC nominal (18–32 VDC)
Output Current 2 A per channel (continuous), 5 A per channel (inrush, 100 ms)
Total Output Current 16 A maximum (module total)
Output Protection Short-circuit protection, overcurrent limiting, over-temperature protection, inductive load clamp (flyback diode)
Diagnostic Feedback Load current monitoring per channel (open/short detection), output state feedback
Inductive Load Support Built-in flyback diodes for inductive loads (solenoids, relays, contactors)
Isolation 1500 VDC (output-to-backplane)
Diagnostics 500-event fault log with timestamps
Communication I/O Net (dual Ethernet ports for redundancy)
Form Factor 6U VME64x (160 × 233 mm), single-slot width
Indicators Per-channel LED (output state/fault), module health, communication status
Operating Temp 0 °C to +60 °C
Power Draw 10 W (+5 V / +3.3 VDC) + external 24 VDC field power
Connectors Front-panel 32-pin terminal block with gold-plated contacts and captive washer screws

Advantages & Distinctive Features

  • 16 High-Capacity Outputs: Controls up to 16 solenoids, valves, or contactors per module.

  • High Inrush Capability: 5 A per channel for 100 ms handles solenoid inrush currents.

  • Per-Channel Load Monitoring: Detects open/short circuits and identifies degraded solenoids (increased current draw).

  • Output State Feedback: Provides actual output state to the processor for sequence verification.

  • Inductive Load Clamping: Built-in flyback diodes protect outputs from voltage spikes.

  • Short-Circuit Protection: Auto-shutdown with auto-retry prevents module damage.

  • Gold-Plated Captive Washer Terminals: Corrosion-resistant and vibration-proof.

  • Hot-Swappable: No rack power-down for replacement.

  • Direct Retrofit: Replaces older DSVO series boards.


Application Fields

  • Gas Turbines: Trip solenoids, fuel shut-off valves, purge/drain valves, bleed valves

  • Steam Turbines: Emergency stop valves (ESV), control valve trip solenoids, drain valves

  • Compressors: Anti-surge blow-off valves, suction/discharge isolation valves

  • Generators: H2 supply shut-off valves, seal oil system valves

  • Balance of Plant: Motor starters, solenoid valves, alarm annunciation

  • Marine: Fuel isolation valves, ballast valve controls


Comparison with VSVOH1B and Competitors

Feature GE IS210DSVOH1A GE IS200VSVOH1B Competitor A Competitor B
Output Channels 16 16 16 16
Continuous Current 2 A 2.5 A 0.5 A 2 A
Inrush Current 5 A (100 ms) 6 A (150 ms) No No
Load Monitoring Per-channel Per-channel No No
Inductive Clamp Built-in Built-in External Built-in
Hot-Swappable Yes Yes No Yes

Selection Guidelines

  • When to choose: Solenoid and valve control applications requiring 2 A continuous, 5 A inrush capability.

  • Load Verification: Verify solenoid/actuator inrush and holding currents do not exceed 5 A inrush or 2 A continuous.

  • Field Power Supply: Provide dedicated 24 VDC field power supply with sufficient capacity for all solenoids simultaneously.

  • Wiring: Use appropriate wire gauge (18 AWG minimum for 2 A loads).

  • Compatibility: Fits all Mark VIe VME64x racks. Requires ControlST v6.0 or higher.


Operational Precautions

  1. Wiring: Follow GE wiring diagrams—correct polarity for external field power.

  2. Field Power: Properly size and fuse external 24 VDC supply (20 A fuse recommended).

  3. Load Monitoring: Use Toolbox ST to view per-channel current readings—trending increasing current indicates solenoid wear.

  4. Short-Circuit Testing: Simulate short to verify auto-shutdown and auto-retry functionality.

  5. LED Diagnostics: Green = output on; Amber = output off with fault; Red = module fault.

  6. Fault Log: Access 500-event log via Toolbox ST.

  7. Hot-Swap: Remove/insert slowly under power.

  8. Spare Stock: Maintain 1 spare per 3–4 racks.

  9. Firmware Updates: Ensure the GE IS210DSVOH1A is in “standby” mode during updates.

  10. ESD: Handle by edges with grounded wrist strap.

A-B 1756-IF8
BENTLEY 330780-50-00
A-B 1794-ACNR15
ABB CI801

Reviews

There are no reviews yet.

Be the first to review “GE IS210DSVOH1A”

Your email address will not be published. Required fields are marked *