Description
Key Specifications
| Parameter | Specification |
|---|---|
| RTD Input Channels | 8 dual-RTD channels (16 total RTD inputs) |
| RTD Types Supported | Pt100 (α = 0.00385), Pt500, Pt1000, Ni120 — software-selectable |
| Connection Configuration | 3-wire or 4-wire (software-selectable per channel) |
| Measurement Range | –200 °C to +850 °C (Pt100) |
| Resolution | 0.05 °C |
| Accuracy | ±0.08% of reading + ±0.2 °C (improved over H1A) |
| Sample Rate | 10 Hz (sequential scanning) |
| Excitation Current | Programmable (0.5 mA, 1 mA, 2 mA) per channel |
| Dual-Sensor Redundancy | Each channel supports two independent RTD sensors |
| Redundancy Logic | On-board average, difference, maximum, and minimum calculation |
| Input Protection | Overvoltage (±30 VDC), ESD (IEC Level 4) |
| Isolation | 1500 VDC (channel-to-backplane) |
| Diagnostics | 750-event fault log with timestamps (expanded) |
| Operating Temp | –25 °C to +70 °C (extended range) |
| Humidity | 5–95% non-condensing (with conformal coating) |
| Coating | Conformal coating (standard) — UV-traceable |
| Manufacturing | 120-hour burn-in, 100% X-Ray/AOI, military-grade components |
| Form Factor | 6U VME64x (160 × 233 mm), single-slot width |
| Power | 12 W (+5 V / +3.3 VDC) |
| Connectors | 48-pin terminal block with gold-plated contacts and captive washer screws |
Advantages & Distinctive Features
-
Dual-Sensor Redundancy: Each channel supports two independent RTD sensors for redundant measurement.
-
On-Board Redundancy Logic: Average, difference, maximum, and minimum calculations—reduces processor load.
-
Improved Accuracy: ±0.08% reading + ±0.2 °C for critical monitoring.
-
Flexible RTD Support: Pt100, Pt500, Pt1000, and Ni120.
-
Lead-Wire Compensation: Automatic for 3-wire and 4-wire RTDs.
-
Conformal Coating Standard: Protects against humidity, salt spray, and chemicals.
-
Extended Temperature Range: –25 °C to +70 °C.
-
Expanded Diagnostic Log: 750-event fault log.
-
Military-Grade Manufacturing: 120-hour burn-in, military-grade components.
-
Gold-Plated Captive Washer Terminals: Corrosion-resistant and vibration-proof.
-
Hot-Swappable: No rack power-down for replacement.
-
Direct Retrofit: Replaces older DRTD series boards.
Application Fields
-
Gas Turbines: Bearing temperature (dual RTDs), exhaust temperature
-
Steam Turbines: Bearing temperature (dual RTDs), casing temperature
-
Generators: Stator winding temperature, bearing temperature
-
Compressors: Bearing temperature, discharge temperature
-
Offshore platforms: Salt-spray environments requiring conformal coating
-
Nuclear Power Plants: Redundant temperature monitoring for safety
Comparison with DRTDH1A and Competitors
| Feature | GE IS210DRTDH1AA | GE IS210DRTDH1A | Competitor A | Competitor B |
|---|---|---|---|---|
| Channels | 8 (dual) / 16 inputs | 8 (dual) / 16 inputs | 8 (single) | 8 (dual) |
| Accuracy | ±0.08% + ±0.2 °C | ±0.1% + ±0.3 °C | ±0.2% + ±1 °C | ±0.1% + ±0.5 °C |
| Coating | Standard | Optional | Optional | Optional |
| Temp Range | –25 to +70 °C | 0 to +60 °C | 0 to +55 °C | –10 to +55 °C |
| Fault Logging | 750 events | 500 events | No | No |
Selection Guidelines
-
When to choose: Critical redundant temperature monitoring requiring high accuracy and environmental protection.
-
When to choose “H1A” instead: For clean, controlled environments where conformal coating is not required.
-
Redundancy Logic: Configure average for normal operation; difference for fault detection.
-
Coating Verification: Inspect under UV (365 nm) upon receipt—uniform fluorescence indicates proper coating.
-
Compatibility: Fits all Mark VIe VME64x racks. Requires ControlST v6.0 or higher.
Operational Precautions
-
Wiring: Follow GE wiring diagrams—correct polarity and shield grounding essential.
-
Dual-Sensor Wiring: Ensure both sensors are correctly wired per channel.
-
Redundancy Logic Testing: Simulate one sensor failure to verify redundancy logic.
-
Calibration: Factory calibrated—verify against known temperature references during commissioning.
-
LED Diagnostics: Green = normal; Amber = sensor fault/difference; Red = module fault.
-
Fault Log: Access 750-event log via Toolbox ST.
-
Coating Care: Use GE-approved cleaner; inspect annually under UV.
-
Hot-Swap: Remove/insert slowly under power.
-
Spare Stock: Maintain 1 spare per 3–4 racks.
-
ESD: Handle by edges with grounded wrist strap.
-
Storage: Anti-static bag with desiccant at –40 to +85 °C; rotate every 3 years.