Description
Key Specifications
| Parameter | Specification |
|---|---|
| Output Channels | 16 Form A (normally open) relay outputs |
| Contact Rating | 6 A @ 250 VAC / 30 VDC (resistive load) |
| Inrush Capability | 12 A for 150 ms (inductive/capacitive loads) |
| Coil Voltage | 24 VDC nominal (module powered) |
| Switching Frequency | Maximum 10 Hz (mechanical life limitation) |
| Mechanical Life | >10,000,000 operations (no load) |
| Electrical Life | >150,000 operations at rated load |
| Protection | Built-in flyback diodes (DC), integrated snubber circuits (AC) |
| Diagnostic Feedback | Output state feedback (auxiliary contact), contact resistance monitoring |
| Isolation | 1500 VDC (coil-to-contacts), 1000 VDC (contact-to-contact) |
| Diagnostics | 1000-event fault log with timestamps and waveform snapshots |
| Operating Temp | –30 °C to +75 °C (widest range in DRLY family) |
| Humidity | 5–100% condensing (with conformal coating) |
| Coating | Conformal coating (standard) — UV-traceable |
| Manufacturing | 120-hour burn-in, 100% X-Ray/AOI, military-grade components |
| Power Draw | 8 W (+5 V / +3.3 VDC) |
| Connectors | Front-panel 32-pin terminal block with gold-plated contacts and captive washer screws |
Advantages & Distinctive Features
-
High-Capacity Relay Outputs: 16 individually isolated Form A relays with 6 A contact rating.
-
High Inrush Capability: 12 A for 150 ms handles solenoid and motor starting surges.
-
Integrated AC Snubbers: Built-in snubber circuits for AC inductive loads—extends contact life.
-
Contact Resistance Monitoring: Tracks contact resistance over time—identifies pitted or worn contacts before failure.
-
Contact Status Feedback: Auxiliary contact provides actual relay state to the processor.
-
1000-Event Fault Log with waveform snapshots—enables comprehensive post-event analysis.
-
Conformal Coating Standard: Protects against humidity, salt spray, and chemical vapors.
-
Widest Temperature Range: –30 °C to +75 °C operation—suitable for extreme environments.
-
Condensing Humidity Rating: 5–100% condensing—suitable for offshore and unheated installations.
-
Military-Grade Manufacturing: 120-hour burn-in, 100% X-ray/AOI, military-grade components.
-
Gold-Plated Captive Washer Terminals: Corrosion-resistant and vibration-proof connections.
-
Hot-Swappable: No rack power-down for replacement.
-
Direct Retrofit: Replaces IS2020DRLYH1A and older WROB series boards.
Application Fields
-
Gas Turbines: Solenoid control, motor starters, valve actuation, alarm annunciation
-
Steam Turbines: Trip solenoid control, motor starters, drain valve control
-
Compressors: Motor starters, solenoid control, surge control valves
-
Generators: Alarm annunciation, motor starters, synchronizing control
-
Balance of Plant: Pump control, fan starters, filter differential pressure alarms
-
Offshore platforms: Salt-spray and condensing environments
-
Arctic installations: Extreme cold (–30 °C) environments
-
Desert power plants: Extreme heat (+75 °C) environments
-
Chemical processing: Corrosive environments
-
Nuclear power plants: Safety-critical relay control
Comparison with IS2020DRLYH1A and Competitors
| Feature | GE IS2020DRLYH1AA | GE IS2020DRLYH1A | Competitor A | Competitor B |
|---|---|---|---|---|
| Output Channels | 16 | 16 | 8 | 8 |
| Contact Rating | 6 A | 6 A | 2 A | 2 A |
| Inrush Capability | 12 A (150 ms) | 12 A (150 ms) | No | No |
| Contact Resistance Monitoring | Yes | Yes | No | No |
| Coating Type | Conformal | Conformal | Optional | Optional |
| Temp Range | –30 to +75 °C | –25 to +70 °C | 0 to +55 °C | 0 to +55 °C |
| Humidity | 5–100% condensing | 5–95% non-condensing | 5–90% | 5–90% |
| Burn-in | 120 hours | 96 hours | 24 hours | 24 hours |
| Fault Logging | 1000 events + waveforms | 750 events | No | No |
The GE IS2020DRLYH1AA offers superior environmental tolerance, extended burn-in, and expanded diagnostics compared to the base H1A variant—making it the definitive choice for critical relay control in extreme environments.
Selection Guidelines
-
When to choose:
-
Critical relay control applications requiring maximum reliability
-
Extreme environments (–30 to +75 °C, condensing, chemical exposure, salt spray)
-
Applications needing contact resistance monitoring and waveform logging
-
Maximum reliability (nuclear, critical infrastructure)
-
-
When to choose “H1A” instead: For less extreme environments (non-condensing, –25 to +70 °C) where standard conformal coating suffices—the “H1AA” variant is typically more expensive; select only when environmental conditions warrant it.
-
Load Verification: Verify each load ≤6 A continuous; ≤12 A inrush. Use integrated AC snubbers for inductive AC loads.
-
Contact Resistance Monitoring: Use Toolbox ST to establish baseline—replace relays when resistance doubles.
-
Coating Verification: Inspect under UV (365 nm)—uniform fluorescence indicates proper coating.
-
Compatibility: Fits all Mark VIe VME64x racks. Requires ControlST v6.5 or higher for full features.
Operational Precautions
-
Wiring: Follow GE wiring diagrams—correct polarity for DC loads. AC loads use integrated snubbers—no external components needed.
-
Load Testing: Test each output with actual load during commissioning—verify contact resistance baseline.
-
Contact Resistance Monitoring: Review contact resistance trends in Toolbox ST—replace relays when resistance doubles from baseline.
-
Inrush Current: Ensure inrush current does not exceed 12 A per channel—excessive inrush can weld contacts.
-
LED Diagnostics: Green = commanded ON; Amber = commanded OFF; Red = fault. Refer to GEH-6920 for expanded blink codes.
-
Fault Log: Access 1000-event log via Toolbox ST for post-event analysis—waveform snapshots included.
-
Coating Care: Use GE-approved cleaner; inspect annually under UV—rework voids with approved coating per GE FSB.
-
Hot-Swap: Remove/insert slowly under power—processor auto-recognizes new module.
-
Spare Stock: Maintain 1 spare per 3–4 racks; “H1AA” backward-compatible with all DRLY and WROB sockets.
-
Annual Verification: Cycle relays during outages; verify switching times and contact resistance.
-
Firmware Updates: Ensure the GE IS2020DRLYH1AA is in “standby” mode during updates.
-
ESD: Handle by edges only with grounded wrist strap—coating does not protect connectors.
-
Storage: Anti-static bag with desiccant at –40 to +85 °C; rotate every 3 years for coating inspection.

WESTINGHOUSE 1C31224G01
SCHNEIDER 140ACO02000
SIEMENS 7ML5201-0EA0
ABB CM577-ETH