Description
Product Parameters
| Parameter | Specification |
|---|---|
| Brand / Series | GE Mark VIe Speedtronic |
| Model | IS200VATFG1A |
| Vibration Channels | 4 channels (accelerometer, velocity pickup, proximity probe selectable) |
| Temperature Channels | 8 channels (thermocouple J/K/T/E/R/S/B or RTD Pt100/Ni120 selectable) |
| Vibration Frequency Range | 1 Hz – 10 kHz |
| Vibration Input Range | ±10 V (programmable scaling) |
| Vibration Sampling Rate | 1–20 kHz |
| Vibration Accuracy | ±0.1% FS |
| Temperature Range (TC) | ±100 mV |
| Temperature Range (RTD) | 0–400 Ω (Pt100: –200°C to +850°C; Ni120: –60°C to +250°C) |
| RTD Excitation | Programmable 0.5/1.0/2.0 mA |
| Cold-Junction Compensation | Built-in CJC sensor (accuracy ±0.5°C) |
| ADC Resolution | 24-bit delta-sigma (temperature), 16-bit SAR (vibration) |
| Isolation | 1500 VAC (field-to-system) |
| CMRR | >100 dB @ 50/60 Hz |
| Diagnostics | Vibration: open/short, out-of-range; Temperature: open-circuit, CJC fault, lead-wire imbalance |
| Status Indication | 4 green LEDs (vibration active), 8 green LEDs (temperature active), 2 red summary fault LEDs |
| Operating Temperature | –30°C to +65°C |
| Storage Temperature | –55°C to +85°C |
| Mounting | VME rack-mount terminal board with front-panel I/O connectors |
| Backplane Interface | VME64x (A24/A32, D16/D32/D64) |
| EMC Compliance | IEC 61000-4 Level 4 |
Advantages & Key Features
-
Mixed Vibration & Temperature Integration: Combines vibration and temperature monitoring on a single board, eliminating separate termination boards.
-
High Channel Density: 4 vibration + 8 temperature channels in a single VME slot.
-
Versatile Sensor Compatibility: Supports accelerometers, velocity pickups, proximity probes, thermocouples, and RTDs.
-
High-Speed Vibration Sampling: Up to 20 kHz sampling rate for high-frequency vibration analysis.
-
High-Precision CJC: Built-in CJC sensor with automatic compensation ensures thermocouple measurement accuracy.
-
Programmable RTD Excitation: Selectable 0.5/1.0/2.0 mA to optimize for sensor self-heating and cable length.
-
Comprehensive Diagnostics: Vibration and temperature diagnostics per channel.
-
Opto-Isolation: 1500 VAC isolation protects the Mark VIe backplane.
-
ToolboxST Integration: Full configuration, monitoring, and diagnostics via GE ToolboxST.
-
Drop-In Replacement: Direct replacement for earlier GE vibration/temperature terminal boards.
Application Fields
-
Gas & Steam Turbines (GE Frame 6B/7EA/9E/HA): Shaft vibration monitoring combined with exhaust gas temperature (thermocouple) and bearing temperature (RTD).
-
Combined Cycle Plants: Vibration monitoring and temperature monitoring for HRSG and steam turbines.
-
Compressor Stations: Compressor vibration monitoring with discharge temperature monitoring.
-
Aeroderivative Turbines: Vibration and temperature monitoring.
Comparison with Competing Products
| Feature | GE IS200VATFG1A | Competitor A (Vibration + Temp Module) | Competitor B (Separate Vibration + Temp) |
|---|---|---|---|
| Vibration Channels | 4 | 2 | 4 |
| Temperature Channels | 8 | 4 | 8 |
| Vibration Sampling | 20 kHz | 10 kHz | 20 kHz |
| CJC Accuracy | ±0.5°C | ±1.2°C | ±0.5°C |
| Isolation | 1500 VAC | 1000 VAC | 1500 VAC |
| Operating Temp | –30°C to +65°C | 0°C to 50°C | –30°C to +65°C |
Key Advantage: IS200VATFG1A provides 4 vibration and 8 temperature channels in a single board—double the density of competing mixed modules—with high-speed vibration sampling, comprehensive diagnostics, and reduced rack space.
Selection Guidelines & Recommendations
-
Channel Configuration: Determine required mix of vibration and temperature channels.
-
Vibration Sensor Type: Configure per channel for accelerometer, velocity pickup, or proximity probe.
-
Temperature Sensor Type: Configure per channel for thermocouple type or RTD.
-
Controller Firmware: Requires Mark VIe processor firmware v7.5 or later.
-
Spare Strategy: Keep one spare per turbine; lead times 6–10 weeks.
-
Retrofit: Direct replacement—regenerate configuration in GE ToolboxST.
Important Cautions
-
No Hot-Swap: De-energize rack before insertion/removal.
-
Sensor Polarity: Observe correct polarity for vibration sensors and thermocouples.
-
CJC Protection: Do not apply conformal coating or tape over the terminal block area.
-
Grounding: Connect AGND to Mark VIe system ground at single star point.
-
Shield Termination: Ground sensor cable shields only at cabinet end.
-
ESD Handling: Use grounded wrist straps; field repair not possible.
-
Channel Mapping: Verify field wiring maps to correct ToolboxST channel numbers.

SCHNEIDER 140ACI03000
IMAJE A35355/B
A-B 1756-PA75
SCHNEIDER 140ACI03000