GE IS200TTURH1B

¥999.00

IS200TTURH1B is an advanced Terminal Board within the GE Mark VIe Speedtronic control system, designed as a high-density field termination and signal conditioning interface for thermocouple and universal analog inputs with enhanced diagnostics, extended temperature range, and comprehensive calibration management. This board provides centralized termination for thermocouple sensors (J, K, T, E, R, S, B) as well as 4–20 mA, RTD, or voltage signals, combining multiple sensor types in a single board. The IS200TTURH1B features integrated termination points with built-in signal conditioning including dual cold-junction compensation (CJC) for thermocouples, excitation for RTDs, filtering, enhanced isolation, and diagnostics. It offers 16 universal input channels (configurable as thermocouple, RTD, 4–20 mA, or voltage), with enhanced accuracy, diagnostics, and extended temperature range.

Category:

Description

Product Parameters

Parameter Specification
Brand / Series GE Mark VIe Speedtronic
Model IS200TTURH1B
Total Channels 16 universal inputs (configurable per channel)
Thermocouple Inputs Up to 16 channels (J, K, T, E, R, S, B)
RTD Inputs Up to 16 channels (Pt100, Ni120, 3-wire or 4-wire)
Analog Transducer Inputs Up to 16 channels (4–20 mA, 0–10 V, ±10 V selectable)
Thermocouple Range ±100 mV
RTD Range 0–400 Ω (Pt100: –200°C to +850°C; Ni120: –60°C to +250°C)
Transducer Range 0–20 mA, 4–20 mA, 0–5 V, 0–10 V, ±10 V
RTD Excitation Programmable 0.5/1.0/2.0 mA
Cold-Junction Compensation Dual redundant CJC sensors (accuracy ±0.2°C) — upgraded from ±0.5°C
ADC Resolution 24-bit delta-sigma (thermocouple/RTD), 16-bit SAR (transducer)
Sampling Rate 2–250 SPS (thermocouple/RTD), 10–500 SPS (transducer)
Accuracy (TC) ±0.03% of reading + ±0.3°C — upgraded from ±0.1% + ±1°C
Accuracy (RTD) ±0.03% of reading + ±0.15°C — upgraded from ±0.1% + ±0.3°C
Accuracy (Transducer) ±0.03% FS — upgraded from ±0.1% FS
Lead-Wire Compensation Automatic (3-wire and 4-wire RTD) with advanced imbalance correction
Transducer Loop Power 24 VDC (externally supplied only)
Isolation 2000 VAC (field-to-system) — upgraded from 1500 VAC
CMRR >110 dB @ 50/60 Hz — upgraded from >100 dB
Diagnostics Open-circuit detection, short-circuit detection, dual CJC fault monitoring and auto-failover, lead-wire imbalance monitoring and correction, over/under-range detection, loop power fault monitoring, reference validation, calibration status tracking, sensor drift detection
Status Indication 16 green LEDs (channel active), 2 red LEDs (diagnostic fault summary), 1 yellow LED (reference/calibration status), 1 blue LED (CJC redundancy active)
Calibration Features Onboard calibration memory with traceable records, software-triggered self-calibration, factory calibration certificate stored onboard
Operating Temperature –40°C to +70°C — upgraded from –30°C to +65°C
Storage Temperature –55°C to +85°C
Mounting VME rack-mount terminal board with front-panel I/O connectors
Backplane Interface VME64x (A24/A32, D16/D32/D64)
EMC Compliance IEC 61000-4 Level 4

Advantages & Key Features

  • Universal Input FlexibilityIS200TTURH1B combines thermocouple, RTD, and transducer inputs on a single board, eliminating the need for separate terminal boards for different sensor types.

  • Configurable Channel Allocation: Each channel can be independently configured as thermocouple, RTD, or transducer via GE ToolboxST.

  • Highest Accuracy: TC: ±0.03% + ±0.3°C; RTD: ±0.03% + ±0.15°C; Transducer: ±0.03% FS provides ultimate measurement precision.

  • Dual-Redundant CJC: Two independent cold-junction sensors with automatic cross-validation and failover ensure uninterrupted thermocouple measurement accuracy.

  • Advanced Lead-Wire Compensation: Automatic compensation with advanced imbalance correction for 3-wire and 4-wire RTDs.

  • Extended Temperature Range: –40°C to +70°C operation makes IS200TTURH1B suitable for extreme environments.

  • Enhanced Isolation: 2000 VAC isolation and >110 dB CMRR provide superior protection.

  • Sensor Drift Detection: Tracks sensor performance over time to predict failures.

  • Advanced Calibration: Onboard calibration memory with traceable records, factory certificate, and software-triggered self-calibration.

  • Comprehensive Diagnostics: Open-circuit, short-circuit, dual CJC auto-failover, lead-wire imbalance monitoring and correction, over/under-range, loop power fault, reference validation, calibration status, and sensor drift detection.

  • ToolboxST Integration: Full configuration, calibration, and diagnostics via GE ToolboxST.

  • Drop-In Replacement: Direct replacement for IS200TTURH1A and earlier universal input terminal boards.

Application Fields

  • Gas & Steam Turbines (GE Frame 6B/7EA/9E/HA): Exhaust gas temperature (thermocouple), bearing temperature (RTD), fuel gas pressure (4–20 mA), steam pressure (4–20 mA), and valve position feedback (0–10 V).

  • Combined Cycle Plants: HRSG superheater temperature (thermocouple), feedwater temperature (RTD), steam drum pressure (4–20 mA), and flow (4–20 mA).

  • Compressor Stations: Discharge temperature (thermocouple), bearing temperature (RTD), and suction/discharge pressure (4–20 mA).

  • Nuclear Power Plants: Critical monitoring with documented calibration and maximum precision.

  • Arctic & Desert Installations: Extreme-environment monitoring applications.

  • Offshore Platforms: Marine enclosures with salt-spray and wide temperature swings.

Comparison with Competing Products

Feature GE IS200TTURH1B GE IS200TTURH1A Competitor A (Universal Input) Competitor B (Separate TC + RTD + Transducer)
Total Inputs 16 universal 16 universal 8 universal 16 (4 + 4 + 8)
CJC Accuracy ±0.2°C (dual redundant) ±0.5°C (single) ±1.2°C ±0.5°C
CJC Redundancy Yes (auto-failover) No No No
TC Accuracy ±0.03% + ±0.3°C ±0.1% + ±1°C ±0.2% + ±2°C ±0.1% + ±1°C
RTD Accuracy ±0.03% + ±0.15°C ±0.1% + ±0.3°C ±0.1% + ±0.3°C
Transducer Accuracy ±0.03% FS ±0.1% FS ±0.2% FS ±0.1% FS
Isolation 2000 VAC 1500 VAC 1000 VAC 1500 VAC
Operating Temp –40°C to +70°C –30°C to +65°C 0°C to 50°C –30°C to +65°C
Calibration Records Yes (traceable + certificate) No No No
Sensor Drift Detection Yes No No No

Key AdvantageIS200TTURH1B delivers 16 universal inputs with dual-redundant CJC (±0.2°C), the highest accuracy, extended –40°C to +70°C temperature range, 2000 VAC isolation, comprehensive diagnostics including sensor drift detection and calibration management with traceable records and factory certificates—making it the ultimate solution for applications requiring diverse sensor monitoring with maximum precision and documented calibration.

Selection Guidelines & Recommendations

  • Channel Configuration: Determine required mix—configure each channel in GE ToolboxST.

  • Input Type: Select thermocouple type, RTD type, or transducer type per channel.

  • Dual CJC Sensors: Automatic failover—blue LED indicates redundancy is active.

  • RTD Excitation: Use 0.5 mA for small sensors or 2.0 mA for long cable runs.

  • RTD Wiring: Configure 3-wire or 4-wire per channel.

  • Transducer Type: Configure 4–20 mA, 0–10 V, or ±10 V per channel.

  • Transducer Loop Power: External 24 VDC supplies required.

  • Sensor Drift Detection: Enable to predict sensor failures.

  • Calibration Management: Use GE ToolboxST to review factory certificate and perform self-calibration.

  • Controller Firmware: Requires Mark VIe processor firmware v9.5 or later.

  • Spare Strategy: Keep one spare per turbine; lead times 8–14 weeks.

  • Retrofit: Direct replacement for IS200TTURH1A—regenerate configuration in GE ToolboxST to access enhanced features.

Important Cautions

  1. No Hot-Swap: De-energize rack before insertion/removal.

  2. Thermocouple Polarity: Reverse connection produces negative readings.

  3. RTD Polarity: For 3-wire RTDs, ensure leads are correctly connected.

  4. Transducer Polarity: Observe correct polarity for 4–20 mA loops and voltage inputs.

  5. CJC Protection: Do not apply conformal coating or tape over the terminal block area.

  6. Transducer Loop Power: External 24 VDC required.

  7. Grounding: Connect AGND to Mark VIe system ground at single star point.

  8. Shield Termination: Ground shields only at cabinet end.

  9. ESD Handling: Use grounded wrist straps; field repair not possible.

  10. Temperature Rating: Verify cabinet ambient does not exceed +70°C or fall below –40°C.

  11. Reference Validation: Yellow LED indicates reference drift—perform self-calibration or schedule factory recalibration.

  12. Self-Calibration: Perform only when board is de-energized and free from field wiring faults.

  13. Calibration Records: Factory certificate stored onboard—do not modify via external tools.

  14. CJC Redundancy Status: Blue LED flashing indicates one CJC sensor failed—schedule service.

  15. Lead-Wire Imbalance: Monitor alerts—investigate wiring mismatches.

  16. Sensor Drift Alerts: Investigate drift alerts to replace aging sensors before failure.

  17. Channel Mapping: With 16 universal channels, verify field wiring maps to correct ToolboxST assignments.

  18. Input Overload: Sustained transducer input >30 V or >50 mA may damage input circuitry.

.

NI PCI-6224
A-B 1747-SDN/B
GE IC693ALG391
A-B 1746-P4

Reviews

There are no reviews yet.

Be the first to review “GE IS200TTURH1B”

Your email address will not be published. Required fields are marked *