| Parameter | Specification |
|---|---|
| Brand / Series | GE Mark VIe Speedtronic |
| Model | IS200TRPGH3B |
| Redundant Power Channels | 16 redundant pairs (32 total power outputs) — upgraded from 12 pairs |
| Output Voltage | 24 VDC (regulated, programmable per channel) |
| Output Current | 100 mA per channel (3.2 A total maximum) — upgraded from 2.4 A |
| Input Voltage Range | 24/48/125 VDC (auto-ranging, from Mark VIe rack) |
| Voltage Regulation | ±0.05% |
| Ripple/Noise | < 5 mV peak-to-peak |
| Redundancy Logic | Automatic failover (hardware-based, < 5 ms) |
| Isolation | 2000 VAC (channel-to-channel and field-to-system) |
| Diagnostics | Overcurrent detection, short-circuit detection, under/over-voltage monitoring, open-circuit detection, primary/secondary power status monitoring, reference validation |
| Status Indication | 16 green LEDs (primary active), 16 green LEDs (redundant active), 32 red LEDs (fault), 2 red summary fault LEDs, 1 yellow LED (reference/calibration status) |
| Operating Temperature | –40°C to +70°C |
| Storage Temperature | –55°C to +85°C |
| Mounting | VME rack-mount terminal board with front-panel I/O connectors |
| Backplane Interface | VME64x (A24/A32, D16/D32/D64) |
| EMC Compliance | IEC 61000-4 Level 4 |
Advantages & Key Features
-
Absolute Maximum Redundant Capacity: 16 redundant transducer power pairs (32 total outputs) in a single VME slot—the highest capacity in the Mark VIe redundant transducer power terminal family, providing 33% more capacity than IS200TRPGH2B (12 pairs) and double that of IS200TRPGH1BDD (8 pairs). Ideal for the largest turbine systems with extensive critical transducer power requirements.
-
Highest Total Current: 100 mA per channel with 3.2 A total capacity—33% more total current than IS200TRPGH2B (2.4 A) and double that of IS200TRPGH1BDD (1.6 A).
-
Highest Accuracy Regulation: ±0.05% voltage regulation ensures ultra-stable transducer operation.
-
Ultra-Low Ripple/Noise: < 5 mV peak-to-peak ripple ensures clean power for sensitive transducers.
-
Fast Failover: < 5 ms hardware failover ensures minimal power interruption.
-
Extended Temperature Range: –40°C to +70°C operation makes IS200TRPGH3B suitable for extreme environments.
-
Enhanced Isolation: 2000 VAC isolation provides superior protection for the Mark VIe backplane.
-
Comprehensive Diagnostics: Overcurrent, short-circuit, under/over-voltage, open-circuit, power status monitoring, and reference validation.
-
Ultra-High-Density Status Indication: 16 primary and 16 redundant status LEDs enable rapid on-site troubleshooting.
-
ToolboxST Integration: Full configuration, monitoring, and diagnostics via GE ToolboxST.
-
Drop-In Replacement: Direct replacement for IS200TRPGH2B, IS200TRPGH1BDD, and earlier redundant transducer power terminal boards.
Application Fields
-
Gas & Steam Turbines (GE Frame 6B/7EA/9E/HA): Redundant power for critical pressure transmitters (fuel gas, steam pressure), temperature transmitters, and position transducers for the largest turbine systems.
-
Combined Cycle Plants: Redundant power for HRSG critical pressure and temperature transmitters.
-
Compressor Stations: Redundant power for critical suction/discharge pressure transmitters.
-
Nuclear Power Plants: Critical transducer power where redundancy and high reliability are mandated.
-
Safety-Critical Applications: Powering transducers in safety instrumented systems (SIS).
-
Arctic & Desert Installations: Extreme-environment critical transducer power applications.
Comparison with Competing Products
| Feature | GE IS200TRPGH3B | GE IS200TRPGH2B (12 pairs) | GE IS200TRPGH1BDD (8 pairs) | Competitor A (Redundant Power) | Competitor B (Power Supply) |
|---|---|---|---|---|---|
| Redundant Pairs | 16 (32 outputs) | 12 (24 outputs) | 8 (16 outputs) | 4 (8 outputs) | 0 |
| Output Current | 100 mA/channel | 100 mA/channel | 100 mA/channel | 40 mA/channel | 50 mA/channel |
| Total Current | 3.2 A | 2.4 A | 1.6 A | 0.32 A | 0.4 A |
| Failover Time | < 5 ms | < 5 ms | < 5 ms | < 50 ms | N/A |
| Voltage Regulation | ±0.05% | ±0.05% | ±0.05% | ±1% | ±0.5% |
| Isolation | 2000 VAC | 2000 VAC | 2000 VAC | 1000 VAC | 500 VDC |
| Operating Temp | –40°C to +70°C | –40°C to +70°C | –40°C to +70°C | 0°C to 50°C | 0°C to 60°C |
| Reference Validation | Yes | Yes | Yes | No | No |
Key Advantage: IS200TRPGH3B delivers 16 redundant transducer power pairs (32 outputs)—the absolute maximum channel density in the Mark VIe redundant transducer power terminal family, with 33% more capacity than IS200TRPGH2B and double that of IS200TRPGH1BDD—combined with 100 mA per channel, < 5 ms failover, ±0.05% regulation, 2000 VAC isolation, extended –40°C to +70°C temperature range, and comprehensive diagnostics including reference validation—making it the ultimate solution for the largest turbine systems requiring maximum-density, high-current, uninterrupted transducer power in extreme environments.
Selection Guidelines & Recommendations
-
Redundancy Configuration: Determine critical transducers requiring redundant power—up to 16 redundant pairs per board.
-
Output Voltage: Configure per-channel output voltage (default 24 VDC) in GE ToolboxST.
-
Current Requirements: Verify each transducer’s current draw does not exceed 100 mA per channel.
-
Total Power: Ensure total current across all channels does not exceed 3.2 A.
-
Diagnostic Configuration: Enable overcurrent, short-circuit, power status monitoring, and reference validation for critical transducers.
-
Failover Testing: Test failover operation by simulating primary power loss—verify automatic switchover within < 5 ms.
-
Controller Firmware: Requires Mark VIe processor firmware v9.5 or later.
-
Wiring Guidelines: Use shielded twisted-pair cables. Maintain shield grounding only at the Mark VIe cabinet end.
-
Spare Strategy: Keep one spare per turbine; lead times 8–14 weeks.
-
Retrofit: Direct replacement for IS200TRPGH2B, IS200TRPGH1BDD, and IS200TRPGH1B—regenerate configuration in GE ToolboxST for 16-pair mapping.
Important Cautions
-
No Hot-Swap: De-energize rack before insertion/removal.
-
Power Polarity: Observe correct polarity for transducer connections—reverse polarity may damage field devices.
-
Current Limit: Do not exceed 100 mA per channel—overcurrent protection will trip and latch.
-
Total Power: Do not exceed 3.2 A total across all channels.
-
Short-Circuit: If a short is detected, the channel will latch off. Clear the fault and reset via GE ToolboxST.
-
Failover Testing: Test failover operation by simulating primary power loss—verify automatic switchover within < 5 ms.
-
Grounding: Connect AGND to Mark VIe system ground at single star point.
-
Shield Termination: Ground transducer cable shields only at cabinet end.
-
ESD Handling: Use grounded wrist straps; field repair not possible.
-
Temperature Rating: Verify cabinet ambient does not exceed +70°C or fall below –40°C.
-
Reference Validation: Yellow LED indicates reference drift—schedule factory recalibration if illuminated.
-
Channel Mapping: With 16 redundant pairs (32 channels), verify field wiring maps to correct ToolboxST channel numbers.
-
Redundancy Verification: Confirm both primary and secondary power sources are operational after installation.
-
Wiring Density: With 32 transducer power connections, ensure adequate cabinet space and cable management to maintain proper airflow.

A-B 1756-PA75/B