GE IS200TRPGH1BDD

¥999.00

IS200TRPGH1BDD is an advanced Terminal Board within the GE Mark VIe Speedtronic control system, designed as a field termination and signal conditioning interface for redundant transducer power supply with enhanced current capacity, extended temperature range, advanced diagnostics, and comprehensive calibration management. This board provides centralized termination for powering and monitoring field-mounted transducers with redundancy requirements, such as pressure transmitters, temperature transmitters, position transducers, and other 2-wire or 4-wire sensors where high reliability is essential. The IS200TRPGH1BDD features integrated termination points for redundant transducer power supply with built-in voltage regulation, filtering, enhanced isolation, and diagnostics. It offers dual-redundant transducer power channels with higher current capacity, automatic failover, and comprehensive diagnostics including reference validation and calibration tracking.

Category:

Description

Product Parameters

Parameter Specification
Brand / Series GE Mark VIe Speedtronic
Model IS200TRPGH1BDD
Redundant Power Channels 8 redundant pairs (16 total power outputs)
Output Voltage 24 VDC (regulated, programmable per channel)
Output Current 100 mA per channel (1.6 A total maximum)
Input Voltage Range 24/48/125 VDC (auto-ranging, from Mark VIe rack)
Voltage Regulation ±0.05%
Ripple/Noise < 5 mV peak-to-peak
Redundancy Logic Automatic failover (hardware-based, < 5 ms) — upgraded from < 10 ms
Isolation 2000 VAC (channel-to-channel and field-to-system)
Diagnostics Overcurrent detection, short-circuit detection, under/over-voltage monitoring, open-circuit detection, primary/secondary power status monitoring, reference validation, calibration status tracking
Status Indication 8 green LEDs (primary active), 8 green LEDs (redundant active), 16 red LEDs (fault), 2 red summary fault LEDs, 1 yellow LED (reference/calibration status)
Calibration Features Onboard calibration memory with traceable records, software-triggered self-calibration
Operating Temperature –40°C to +70°C
Storage Temperature –55°C to +85°C
Mounting VME rack-mount terminal board with front-panel I/O connectors
Backplane Interface VME64x (A24/A32, D16/D32/D64)
EMC Compliance IEC 61000-4 Level 4

Advantages & Key Features

  • Redundant Transducer PowerIS200TRPGH1BDD provides 8 redundant transducer power pairs with automatic failover (< 5 ms), ensuring uninterrupted power to critical field devices.

  • Higher Current Capacity: 100 mA per channel—double the capacity of IS200TRPGH1A, enabling support for higher-power transducers or multiple devices per redundant pair.

  • Faster Failover: < 5 ms hardware failover—upgraded from < 10 ms—ensures minimal power interruption.

  • Highest Accuracy Regulation: ±0.05% voltage regulation ensures ultra-stable transducer operation.

  • Ultra-Low Ripple/Noise: < 5 mV peak-to-peak ripple ensures clean power for sensitive transducers.

  • Extended Temperature Range: –40°C to +70°C operation makes IS200TRPGH1BDD suitable for extreme environments.

  • Enhanced Isolation: 2000 VAC isolation provides superior protection for the Mark VIe backplane.

  • Advanced Calibration: Onboard calibration memory with traceable records and software-triggered self-calibration.

  • Comprehensive Diagnostics: Overcurrent, short-circuit, under/over-voltage, open-circuit, power status monitoring, reference validation, and calibration status tracking.

  • ToolboxST Integration: Full configuration, monitoring, diagnostics, and calibration management via GE ToolboxST.

  • Drop-In Replacement: Direct replacement for IS200TRPGH1BIS200TRPGH1A, and earlier redundant transducer power terminal boards.

Application Fields

  • Gas & Steam Turbines (GE Frame 6B/7EA/9E/HA): Redundant power for critical pressure transmitters (fuel gas, steam pressure), temperature transmitters, and position transducers.

  • Combined Cycle Plants: Redundant power for HRSG critical pressure and temperature transmitters.

  • Compressor Stations: Redundant power for critical suction/discharge pressure transmitters.

  • Nuclear Power Plants: Critical transducer power where redundancy, calibration traceability, and high reliability are mandated.

  • Safety-Critical Applications: Powering transducers in safety instrumented systems (SIS).

  • Arctic & Desert Installations: Extreme-environment critical transducer power applications.

Comparison with Competing Products

Feature GE IS200TRPGH1BDD GE IS200TRPGH1B GE IS200TRPGH1A Competitor A (Redundant Power) Competitor B (Power Supply)
Redundant Pairs 8 (16 outputs) 8 (16 outputs) 8 (16 outputs) 4 (8 outputs) 0
Output Current 100 mA/channel 100 mA/channel 50 mA/channel 40 mA/channel 50 mA/channel
Failover Time < 5 ms < 10 ms < 10 ms < 50 ms N/A
Voltage Regulation ±0.05% ±0.05% ±0.1% ±1% ±0.5%
Ripple/Noise < 5 mV < 5 mV < 10 mV < 20 mV < 15 mV
Diagnostics Overcurrent, short, under/over-voltage, open, status, reference, calibration Overcurrent, short, under/over-voltage, open, status, reference Overcurrent, short, under/over-voltage, open, status Overcurrent only Overcurrent only
Isolation 2000 VAC 2000 VAC 1500 VAC 1000 VAC 500 VDC
Operating Temp –40°C to +70°C –40°C to +70°C –30°C to +65°C 0°C to 50°C 0°C to 60°C
Calibration Records Yes (traceable) No No No No
Self-Calibration Yes No No No No

Key AdvantageIS200TRPGH1BDD delivers 8 redundant transducer power pairs with double the current capacity (100 mA), fastest failover (< 5 ms), highest regulation accuracy (±0.05%), ultra-low ripple, 2000 VAC isolation, extended –40°C to +70°C temperature range, comprehensive diagnostics, and advanced calibration management with traceable records—making it the ultimate solution for critical turbine applications requiring high-current, uninterrupted transducer power with documented calibration in extreme environments.

Selection Guidelines & Recommendations

  • Redundancy Configuration: Determine critical transducers requiring redundant power—up to 8 redundant pairs per board.

  • Output Voltage: Configure per-channel output voltage (default 24 VDC) in GE ToolboxST.

  • Current Requirements: Verify each transducer’s current draw does not exceed 100 mA per channel.

  • Diagnostic Configuration: Enable overcurrent, short-circuit, power status monitoring, and reference validation for critical transducers.

  • Calibration Management: Use GE ToolboxST to perform software-triggered self-calibration during scheduled maintenance.

  • Failover Testing: Test failover operation by simulating primary power loss—verify automatic switchover within < 5 ms.

  • Controller Firmware: Requires Mark VIe processor firmware v9.5 or later.

  • Wiring Guidelines: Use shielded twisted-pair cables. Maintain shield grounding only at the Mark VIe cabinet end.

  • Spare Strategy: Keep one spare per turbine; lead times 8–14 weeks.

  • Retrofit: Direct replacement for IS200TRPGH1B and IS200TRPGH1A—regenerate configuration in GE ToolboxST to access enhanced features.

Important Cautions

  1. No Hot-Swap: De-energize rack before insertion/removal.

  2. Power Polarity: Observe correct polarity for transducer connections—reverse polarity may damage field devices.

  3. Current Limit: Do not exceed 100 mA per channel—overcurrent protection will trip and latch.

  4. Short-Circuit: If a short is detected, the channel will latch off. Clear the fault and reset via GE ToolboxST.

  5. Failover Testing: Test failover operation by simulating primary power loss—verify automatic switchover within < 5 ms.

  6. Grounding: Connect AGND to Mark VIe system ground at single star point.

  7. Shield Termination: Ground transducer cable shields only at cabinet end.

  8. ESD Handling: Use grounded wrist straps; field repair not possible.

  9. Temperature Rating: Verify cabinet ambient does not exceed +70°C or fall below –40°C.

  10. Reference Validation: Yellow LED indicates reference drift—perform software self-calibration or schedule factory recalibration if illuminated.

  11. Self-Calibration: Perform only when board is de-energized and free from field wiring faults.

  12. Calibration Records: Do not modify calibration memory via external tools—use only GE ToolboxST.

  13. Channel Mapping: Verify field wiring maps to correct ToolboxST channel numbers.

  14. Redundancy Verification: Confirm both primary and secondary power sources are operational after installation.

SCHNEIDER 140CPU11302
FANUC A02B-0092-C161
EPRO UES815S-24A
SCHNEIDER 140CRP93100

Reviews

There are no reviews yet.

Be the first to review “GE IS200TRPGH1BDD”

Your email address will not be published. Required fields are marked *