GE IS200TBAIH2C

¥999.00

IS200TBAIH2C is a high-capacity Terminal Board within the GE Mark VIe Speedtronic control system, designed as a high-density field termination and signal conditioning interface for analog input signals with enhanced capabilities. This board provides centralized termination for analog sensors such as pressure transmitters, temperature transmitters, flow meters, and position transducers, connecting to the Mark VIe main VME-based controller processors via front-panel I/O cables. The IS200TBAIH2C features integrated termination points for analog inputs with built-in signal conditioning including filtering, isolation, and surge protection. It offers 32 analog input channels with support for internal loop power on select channels, making it ideal for large turbine systems with extensive process monitoring requirements.

Category:

Description

Product Parameters

Parameter Specification
Brand / Series GE Mark VIe Speedtronic
Model IS200TBAIH2C
Analog Inputs 32 channels (4–20 mA, 0–10 V, ±10 V selectable)
Internal Loop Power 24 VDC (available on 16 channels, software-enabled) — upgraded from external-only
ADC Resolution 16-bit SAR with programmable sampling rate (10–500 SPS)
Accuracy ±0.1% of full scale (25°C), ±0.2% over full temperature range
Input Impedance 250 Ω (current mode), > 1 MΩ (voltage mode)
Filtering Programmable low-pass filter (1–50 Hz)
Isolation 1500 VAC (field-to-system)
CMRR >100 dB @ 50/60 Hz
Diagnostics Open-circuit detection, over-range/under-range detection, loop power fault monitoring
Status Indication 32 green LEDs (channel active), 2 red LEDs (diagnostic fault summary)
Operating Temperature –30°C to +65°C
Storage Temperature –55°C to +85°C
Mounting VME rack-mount terminal board with front-panel I/O connector
Backplane Interface VME64x (A24/A32, D16/D32/D64)

Advantages & Key Features

  • Maximum Channel Density: 32 analog inputs in a single VME slot—double the density of IS200TBAIH1B (24 channels) and four times that of competing 8-channel modules.

  • Integrated Loop Power: 24 VDC loop power available on 16 channels (software-enabled), reducing the need for external power supplies for 2-wire transmitters.

  • Flexible Input Configuration: Each channel supports 4–20 mA, 0–10 V, or ±10 V inputs via GE ToolboxST software.

  • Programmable Filtering: Onboard low-pass filter (1–50 Hz) optimizes noise rejection vs. response speed.

  • Comprehensive Diagnostics: Real-time open-circuit, over-range/under-range, and loop power fault monitoring per channel.

  • High-Density Status Indication: 32 green LEDs (one per channel) and 2 red summary fault LEDs enable rapid on-site channel status identification.

  • ToolboxST Integration: Full configuration, calibration, and diagnostics via GE ToolboxST.

  • Drop-In Replacement: Direct replacement for earlier GE analog input terminal boards.

Application Fields

  • Gas & Steam Turbines (GE Frame 6B/7EA/9E/HA): Fuel gas pressure/flow, steam pressure/temperature, bearing vibration (via transmitters), lube oil pressure/temperature, cooling water pressure, valve position feedback, generator hydrogen pressure.

  • Combined Cycle Plants: HRSG feedwater flow, steam drum pressure, superheater temperature, condensate flow, extraction pressure.

  • Compressor Stations: Suction/discharge pressure, gas flow, vibration transducers, intercooler temperature.

  • Aeroderivative Turbines: Fuel flow, engine oil pressure, inlet guide vane position, exhaust temperature transmitters.

Comparison with Competing Products

Feature GE IS200TBAIH2C GE IS200TBAIH1C Competitor A (Emerson) Competitor B (Siemens)
Analog Inputs 32 32 8 8
Internal Loop Power Yes (16 channels) No No No
Input Types 4–20mA, 0–10V, ±10V 4–20mA, 0–10V, ±10V 4–20mA only 4–20mA, 0–10V
Accuracy ±0.1% FS ±0.1% FS ±0.2% FS ±0.15% FS
Isolation 1500 VAC 1500 VAC 1000 VAC 500 VDC
Operating Temp –30°C to +65°C –30°C to +65°C 0°C to 50°C 0°C to 60°C

Key AdvantageIS200TBAIH2C provides 32 analog inputs with integrated loop power on 16 channels—reducing external power supply requirements and simplifying wiring compared to IS200TBAIH1C and competing modules.

Selection Guidelines & Recommendations

  • Channel Count: 32 channels per board—sufficient for most large turbines.

  • Loop Power Selection: Enable internal 24 VDC loop power for 2-wire transmitters on the 16 supported channels. Use external supplies for the remaining 16 channels or for devices requiring >30 mA.

  • Input Type: Configure 4–20 mA, 0–10 V, or ±10 V per channel in GE ToolboxST.

  • Filtering: Use 1–10 Hz for temperature/pressure, 20–50 Hz for dynamic signals.

  • Controller Firmware: Requires Mark VIe processor firmware v7.0 or later.

  • Spare Strategy: Keep one spare per turbine; lead times 6–10 weeks.

  • Retrofit: Direct replacement—regenerate configuration in GE ToolboxST.

Important Cautions

  1. No Hot-Swap: De-energize rack before insertion/removal.

  2. Loop Power Polarity: For channels using internal loop power, observe correct polarity—reverse polarity prevents transmitter operation.

  3. Loop Power Current Limit: Internal loop power limited to 30 mA per channel—use external supply for higher-current transmitters.

  4. Input Overload: Sustained input >30 V or >50 mA may damage input circuitry.

  5. Grounding: Connect AGND to Mark VIe system ground at single star point.

  6. Shield Termination: Ground shields only at cabinet end.

  7. ESD Handling: Use grounded wrist straps; field repair not possible.

  8. Filtering Trade-Off: Lower cutoff = better noise rejection but more signal delay.

  9. Channel Mapping: With 32 channels, verify wiring maps to correct ToolboxST channel assignments.

ABB 3HAC024144-001
A-B 1756-L8SP
FOXBORO P0926KH
BENTLY 146031-01