GE IS200TBAIH1B

¥999.00

IS200TBAIH1B is a Terminal Board within the GE Mark VIe Speedtronic control system, designed as a high-density field termination and signal conditioning interface for analog input signals in turbine control applications. This board provides centralized termination for analog sensors such as pressure transmitters, temperature transmitters, flow meters, and position transducers, connecting to the Mark VIe main VME-based controller processors via front-panel I/O cables. The IS200TBAIH1B features integrated termination points for analog inputs with built-in signal conditioning including filtering, isolation, and surge protection. It offers 24 analog input channels—a 50% increase over the IS200TBAIH1A—making it ideal for larger turbine systems with extensive process monitoring requirements.

Category:

Description

Product Parameters

Parameter Specification
Brand / Series GE Mark VIe Speedtronic
Model IS200TBAIH1B
Analog Inputs 24 channels (4–20 mA, 0–10 V, ±10 V selectable)
ADC Resolution 16-bit SAR with programmable sampling rate (10–500 SPS)
Accuracy ±0.1% of full scale (25°C), ±0.2% over full temperature range
Loop Power 24 VDC (externally supplied only — no internal loop power)
Input Impedance 250 Ω (current mode), > 1 MΩ (voltage mode)
Filtering Programmable low-pass filter (1–50 Hz)
Isolation 1500 VAC (field-to-system)
CMRR >100 dB @ 50/60 Hz
Diagnostics Open-circuit detection, over-range/under-range detection, loop power fault monitoring
Status Indication 24 green LEDs (channel active), 2 red LEDs (diagnostic fault summary)
Operating Temperature –30°C to +65°C
Storage Temperature –55°C to +85°C
Mounting VME rack-mount terminal board with front-panel I/O connector
Backplane Interface VME64x (A24/A32, D16/D32/D64)

Advantages & Key Features

  • Higher Channel Density: 24 analog inputs in a single VME slot—50% more than IS200TBAIH1A and triple the density of competing 8-channel modules. Ideal for large turbines with extensive pressure, temperature, and flow monitoring.

  • Flexible Input Configuration: Each channel supports 4–20 mA, 0–10 V, or ±10 V inputs via GE ToolboxST software.

  • Programmable Filtering: Onboard low-pass filter (1–50 Hz) optimizes noise rejection vs. response speed.

  • Comprehensive Diagnostics: Real-time open-circuit, over-range/under-range, and loop power fault monitoring per channel.

  • Wide Input Compatibility: Accommodates both current and voltage sensors without external signal conditioners.

  • ToolboxST Integration: Full configuration, calibration, and diagnostics via GE ToolboxST.

  • Drop-In Replacement: Direct replacement for earlier GE analog input terminal boards.

Application Fields

  • Gas & Steam Turbines (GE Frame 6B/7EA/9E/HA): Fuel gas pressure/flow, steam pressure/temperature, bearing vibration (via transmitters), lube oil pressure/temperature, cooling water pressure, valve position feedback, generator hydrogen pressure.

  • Combined Cycle Plants: HRSG feedwater flow, steam drum pressure, superheater temperature, condensate flow, extraction pressure.

  • Compressor Stations: Suction/discharge pressure, gas flow, vibration transducers, intercooler temperature.

  • Aeroderivative Turbines: Fuel flow, engine oil pressure, inlet guide vane position, exhaust temperature transmitters.

Comparison with Competing Products

Feature GE IS200TBAIH1B GE IS200TBAIH1A Competitor A (Emerson) Competitor B (Siemens)
Analog Inputs 24 16 8 8
Input Types 4–20 mA, 0–10 V, ±10 V 4–20 mA, 0–10 V, ±10 V 4–20 mA only 4–20 mA, 0–10 V
Accuracy ±0.1% FS ±0.1% FS ±0.2% FS ±0.15% FS
Isolation 1500 VAC 1500 VAC 1000 VAC 500 VDC
Operating Temp –30°C to +65°C –30°C to +65°C 0°C to 50°C 0°C to 60°C

Key AdvantageIS200TBAIH1B provides 24 analog inputs—the highest channel density in its class and triple that of competing modules—with flexible input configuration and comprehensive diagnostics, significantly reducing rack space and simplifying system design for large turbine applications.

Selection Guidelines & Recommendations

  • Input Type: Configure 4–20 mA, 0–10 V, or ±10 V per channel in GE ToolboxST.

  • Loop Power: External 24 VDC supplies required—plan cabinet power distribution accordingly.

  • Filtering: Use 1–10 Hz for temperature/pressure, 20–50 Hz for dynamic signals.

  • Controller Firmware: Requires Mark VIe processor firmware v7.0 or later.

  • Spare Strategy: Keep one spare per turbine; lead times 6–10 weeks.

  • Retrofit: Direct replacement—regenerate configuration in GE ToolboxST for 24-channel mapping.

Important Cautions

  1. No Hot-Swap: De-energize rack before insertion/removal.

  2. External Loop Power Required: No internal loop power—ensure 24 VDC supplies are connected.

  3. Input Overload: Sustained input >30 V or >50 mA may damage input circuitry.

  4. Grounding: Connect AGND to Mark VIe system ground at single star point.

  5. Shield Termination: Ground shields only at cabinet end.

  6. ESD Handling: Use grounded wrist straps; field repair not possible.

  7. Filtering Trade-Off: Lower cutoff = better noise rejection but more signal delay.

  8. Channel Mapping: With 24 channels, verify wiring maps to correct ToolboxST channel assignments.

  9. Power Supply Sizing: Ensure external 24 VDC supplies are sized for all connected transmitters (20–30 mA per channel × 24 channels = 0.48–0.72 A minimum).