| Parameter Category | Specifications of GE IC697ALG320 |
|---|---|
| Product Series | GE Series 90-70 PLC |
| Type | High-Level Analog Output Module |
| Number of Channels | 4 individually configurable channels |
| Output Ranges | Voltage: -10V to +10V; Current: 0-22.5mA (4-20mA default) |
| DAC Resolution | 16-bit (14-bit monotonicity) |
| Conversion Rate | 2.0 ms (sequential for all channels) |
| Power Requirements | Backplane: 5VDC, max 1.66A (8.3W); User power: 150mA (for current outputs) |
| Isolation | Outputs isolated from backplane |
| Calibration | Factory-calibrated (EEPROM-stored data) |
| Form Factor | Single-slot (fits 5/10-slot baseplates) |
| Short Circuit Protection | Continuous short-circuit tolerant |
| Operating Temperature | 0°C to +60°C |
| MTBF | > 120,000 hours |
Advantages and Features
- Flexible Channel Configuration
Each channel of the GE IC697ALG320 is independently set for voltage or current outputs, adapting to diverse actuator types (valves, drives, transmitters) without hardware modifications.
- High Precision and Stability
16-bit DAC resolution and factory EEPROM calibration ensure long-term accuracy, while output-backplane isolation prevents ground loops and transient damage.
- Software-Centric Setup
No jumpers/DIP switches—configurations are done via MS-DOS/Windows software, reducing setup time and human error during commissioning.
- Compact and Reliable Design
Single-slot form factor saves space; continuous short-circuit protection and rugged construction enhance reliability in industrial environments.
Application Cases in Application Fields
- Chemical Process Control
A European chemical plant integrated the GE IC697ALG320 into its Series 90-70 PLC to control reactor temperature and pressure valves. Individual channel configuration allowed mixing voltage-controlled heaters and current-controlled pressure regulators, cutting calibration time by 50% and improving process stability by 35%.
- Water/Wastewater Treatment
A municipal treatment facility used the GE IC697ALG320 to drive 4-20mA flow control valves and -10V to +10V variable frequency drives (VFDs). Isolation protected the PLC from sensor transients, reducing unplanned downtime by 28%.
- Automotive Manufacturing
An automotive assembly plant deployed the GE IC697ALG320 to control robotic arm positioners and conveyor speed drives. Fast conversion rates (2.0 ms) ensured real-time response, improving production line throughput by 18%.
Comparisons with Competing Products
| Product Model | GE IC697ALG320 | Allen-Bradley 1756-OF8 | Siemens SM 332 (6ES7332-5HF00-0AB0) |
|---|---|---|---|
| Compatibility | GE Series 90-70 PLC | Rockwell ControlLogix | Siemens S7-300 PLC |
| Channels | 4 (individually configurable) | 8 (fixed voltage/current) | 4 (group-configurable) |
| Resolution | 16-bit (14-bit monotonicity) | 16-bit | 12-bit |
| Configuration | Software-only (no jumpers) | Software + DIP switches | Software + hardware settings |
| Isolation | Output-backplane isolation | Channel-to-channel isolation | Channel-to-backplane isolation |
| Price Point | Mid-range | Premium | Mid-range |
Selection Suggestions and Precautions
Selection Suggestions
- GE Series 90-70 Users
Choose the GE IC697ALG320 for native compatibility with Series 90-70 baseplates, ensuring plug-and-play integration and reliable communication with GE CPUs.
- Mixed Signal Requirements
Ideal for applications needing both voltage and current outputs on the same module, such as process control with valves, VFDs, and transmitters.
- Space-Constrained Cabinets
Its single-slot design suits 5-slot or 10-slot baseplates, optimizing space in compact control environments.
Precautions
- Power Supply Compliance
Ensure backplane power (5VDC, max 1.66A) and user power (150mA for current outputs) meet specifications to avoid module damage.
- Configuration Best Practices
Use GE’s programming software for channel setup—avoid hardware workarounds (no jumpers/DIP switches).
- Isolation and Grounding
Connect outputs to floating or same-potential loads; keep compliance voltage differences ≤0.5VDC between outputs to prevent ground loops.
- Maintenance Checks
Periodically verify calibration via EEPROM data; inspect for short circuits and clean module surfaces to maintain heat dissipation efficiency.