GE DS4815COME

¥999.00

The GE DS4815COME is a high-performance communication and digital I/O module for the GE Mark VIe control system, offering the highest communication density in the DS4815 series. The suffix -COME indicates Communication with Enhanced Ethernet and Serial Capabilities, adding dual Ethernet ports to the combined I/O and serial functionality. This module provides 8 digital input channels, 8 digital output channels, 2 serial communication ports (RS-232/RS-485), and 2 Ethernet ports (10/100BASE-T) in a single slot. The GE DS4815COME is optimized for turbine auxiliary control applications requiring both discrete I/O and networked communication (Modbus TCP, OPC UA, or DNP3) alongside serial device connections. Each digital channel is rated for 125VDC or 240VAC operation, while the Ethernet ports support Modbus TCP, OPC UA, and GE-proprietary protocols. The module features hardware-level isolation between the communication sections and I/O, ensuring reliable operation in electrically noisy environments.

Category:

Description

Parameters

Parameter Specification
Digital Input Channels 8, optically isolated
Digital Output Channels 8, solid-state (MOSFET/thyristor)
Digital Input Voltage 0–250VAC/VDC (threshold: 24V min for ON)
Digital Output Voltage 24–250VAC/VDC (sourcing or sinking, configurable per channel)
Output Current per Channel 2A continuous; 5A surge (1s)
Total Output Current 8A (max)
Ethernet Ports 2x 10/100BASE-T (RJ45, dual-stack, switchable)
Ethernet Protocols Modbus TCP (client/server), OPC UA (server), DNP3 (outstation), SNMP (agent), HTTPS
Serial Ports 2x RS-232/RS-485 (software selectable, DB9)
Serial Baud Rate 300–115200 bps
Serial Protocols Modbus RTU (master/slave), DNP3 (outstation), ASCII
Input Debounce Programmable: 0.1ms–100ms
Input Wetting Current 5–20mA (programmable per channel)
Diagnostics Open-wire detection, short-circuit detection, over-temperature, communication errors, link status, input state readback
Protection Short-circuit protection (current limit), thermal shutdown (95°C), transient suppression (MOV + TVS)
Update Rate 1ms (digital I/O); 10ms (serial data); 10ms (Ethernet data)
Isolation 2500Vrms (digital I/O to backplane); 1500Vrms (Ethernet/serial to backplane); 500VDC (communication to I/O)
Power Supply 5VDC (backplane), 550mA; 24VDC aux (I/O and wetting), 400mA + output load
Operating Temp -40°C to +70°C
Mounting 6U VME Eurocard, 160mm depth
Certifications UL, CSA, ATEX Zone 2, SIL 1 capable

Advantages & Features

  • Ethernet + Serial + I/O in One Slot – The GE DS4815COME combines 8 digital inputs, 8 digital outputs, 2 serial ports, and 2 Ethernet ports in a single module, replacing up to four separate modules and significantly reducing rack space.

  • Dual Ethernet with Protocol Flexibility – The GE DS4815COME supports Modbus TCP, OPC UA, and DNP3, enabling direct integration with plant DCS, SCADA, and remote monitoring systems without additional gateways.

  • High-Voltage Digital I/O – The GE DS4815COME directly interfaces with 125VDC and 240VAC field circuits, eliminating external relays for most applications.

  • Configurable Communication Protocols – All communication ports on the GE DS4815COME can be independently configured, supporting mixed protocols (e.g., Ethernet = Modbus TCP, Serial = Modbus RTU, Serial 2 = DNP3).

  • Isolation Between Sections – The GE DS4815COME provides 500VDC isolation between communication (Ethernet/serial) and digital I/O sections, preventing ground loops and noise coupling.

  • Built-in Web Server – The GE DS4815COME includes a secure HTTPS web interface for module configuration and status monitoring.


Application Cases

  • Turbine Auxiliary System with Network Integration – The GE DS4815COME connects to a gas chromatograph via serial (Modbus RTU), monitors valve position switches (8 inputs), controls solenoid valves (8 outputs), and provides data to plant SCADA via Modbus TCP over Ethernet.

  • Compressor Station with Remote Monitoring – The GE DS4815COME reads pressure and temperature alarms (8 inputs), controls anti-surge valves (8 outputs), communicates with VFDs via serial (Modbus RTU), and transmits performance data to a control center via OPC UA over Ethernet.

  • Generator Hydrogen Monitoring System – The GE DS4815COME monitors hydrogen purity analyzer status, controls purge valves, and provides data to the Mark VIe controller via Ethernet, while also serving as a Modbus TCP gateway to external condition monitoring systems.

  • Small Skid Control – The GE DS4815COME provides all necessary I/O and communication for a small pump skid, including valve control, status monitoring, and serial communication to a flow computer, all in one slot.


Competitor Comparison

Feature GE DS4815COME GE DS4815COMD GE DS4815COMC Siemens CP + DI/DO ABB CI + DI/DO
Combined I/O + Ethernet + Serial Yes No No No No
Ethernet Ports 2 0 0 1 (via CP) 1 (via CI)
Serial Ports 2 (RS-232/RS-485) 4 (2x RS-232, 2x RS-485) 2 (RS-232/RS-485) 1 1
Digital Inputs 8 8 8 8 (separate) 8 (separate)
Digital Outputs 8 8 8 8 (separate) 8 (separate)
Ethernet Protocols Modbus TCP, OPC UA, DNP3 N/A N/A Modbus TCP, Profinet Modbus TCP, Profibus
Web Server Yes No No No No
SIL Rating SIL 1 SIL 1 SIL 1 SIL 1 SIL 2
Slot Count 1 1 1 3–4 3

The GE DS4815COME is the only module in the Mark VIe family combining Ethernet, dual serial, and digital I/O in a single slot — a capability not offered by any competitor in a single module.


Selection Suggestions

  • Choose the GE DS4815COME when your application requires digital I/O (8 in, 8 out) plus both Ethernet and serial communication within a single rack slot. It is ideal for turbine auxiliaries requiring SCADA integration and serial device connections.

  • If your application requires Ethernet only (no serial), consider the DS4815COE variant. For serial-only, choose DS4815COMD (4 ports) or DS4815COMC (2 ports).

  • For SIL 2 safety applications, the GE DS4815COME is not rated SIL 2 — use separate safety-rated modules.

  • Assign Ethernet protocols based on your plant network infrastructure: Modbus TCP for DCS integration, OPC UA for SCADA/condition monitoring, DNP3 for utility communication.

  • Pair the GE DS4815COME with TB500-HV for digital I/O connections, standard Ethernet cables for network ports, and DB9 cables for serial connections.


Precautions

  • Ethernet Network Configuration – Assign unique IP addresses to each Ethernet port. The GE DS4815COME supports dual-stack operation (both ports can be on different subnets). Configure appropriate subnet masks and gateways.

  • Ethernet Redundancy – The dual Ethernet ports do not support PRP/HSR redundancy (this is reserved for DS3860 series modules). They can be used as separate communication channels to different networks.

  • Serial Port Configuration – Each serial port can be independently configured for RS-232 or RS-485 (software selectable). Verify the correct mode before cabling.

  • RS-485 Termination – Use 120Ω termination resistors at both ends of the bus. The GE DS4815COME includes selectable termination per RS-485 port (software configurable).

  • Serial Cable Length – RS-232: max 15m. RS-485: max 1200m (at 9600 baud).

  • Output Grouping – All outputs on the GE DS4815COME share a common return. All outputs must be powered from the same voltage source.

  • Output Current Limit – Total output current is limited to 8A (combined across all 8 channels). Ensure the total load does not exceed this limit.

  • Wetting Current – For dry contact inputs, enable wetting current (5–20mA) to ensure reliable switching.

  • Firewall Considerations – If the GE DS4815COME communicates across firewalls, ensure required ports are open: Modbus TCP (502), OPC UA (4840), HTTPS (443).

  • Power Supply – The GE DS4815COME draws 550mA from 5V plus output load current. Ensure the power supply module has sufficient capacity.

  • Firmware – The GE DS4815COME requires Mark VIe controller firmware v7.5 or higher for full Ethernet and serial protocol support.

  • Cybersecurity – The GE DS4815COME includes a web server. Change default passwords and use HTTPS for secure access. Disable unused protocols to reduce the attack surface.

  • ESD Handling – Use ESD-safe practices when handling the GE DS4815COME. Ethernet ports, serial ports, and output stages are sensitive to electrostatic discharge.

A-B 1747-BA
ABB SDCS-PIN-20XB DCS500
A-B 1746-NI8ϵ и

Reviews

There are no reviews yet.

Be the first to review “GE DS4815COME”

Your email address will not be published. Required fields are marked *