GE DS3826AS1D06AA

¥999.00

The DS3826AS1D06AA is a high-performance analog input module designed for industrial process control with 16-bit resolution8 isolated channelssoftware-configurable input types (4–20 mA, 0–10 V, ±10 V), built-in diagnostics1500 V isolationscrew-type terminals, and a fixed terminal configuration. It features high-speed samplingper-channel open/short detection, and over-range/under-range alarms. The DS3826AS1D06AA is the ruggedized analog input module for demanding industrial applications requiring high channel density, accuracy, and reliability in harsh environments.

Category:

Description

Key Parameters

  • Channels: 8 isolated analog inputs

  • Input Types: 4–20 mA, 0–10 V, ±10 V (software-configurable per channel)

  • Resolution: 16-bit ADC

  • Accuracy: ±0.1% of full scale (25°C); ±0.3% over –40°C to +70°C

  • Input Impedance: >1 MΩ (voltage), 250 Ω (current)

  • Sampling Rate: Up to 500 Hz per channel (high-speed mode; filtering disabled)

  • EMC/Noise Rejection: CMRR > 100 dB, built-in 50/60 Hz digital filtering

  • Diagnostics: Open-circuit detection, short-circuit detection, over-range/under-range, signal-loss detection, per-channel LED status

  • Isolation: 1500 V RMS (field-to-backplane); 500 V RMS between channels (per-channel isolation)

  • Operating Temperature: –40°C to +70°C

  • Terminal Type: Screw-type – per suffix “D06AA”

  • Power: 24 V DC backplane power, ≤5 W

  • Dimensions: Standard double-width Eurocard form factor


Advantages

  • High channel density – 8 isolated channels in a single module; saves rack space.

  • Software-configurable per channel – each channel independently set for current or voltage; eliminates hardware jumpers.

  • Per-channel isolation – 500 V between channels; prevents ground loops, cross-channel interference, and channel-to-channel faults.

  • High-speed 500 Hz sampling – captures fast-changing process signals for dynamic control applications.

  • 16-bit resolution – provides precise measurement fidelity.

  • Open/short detection – detects broken wires or sensor shorts instantly.

  • Enhanced diagnostics – includes signal-loss detection for proactive maintenance.

  • Hot-swappable – replace without rack power-down.

  • Wide measurement range – supports standard industrial signal types.

  • Optical isolation – protects backplane from field transients.


Applications

  • Oil & gas pipelines – pressure, flow, and temperature monitoring with long cable runs

  • Chemical processing – reactor and tank level/pressure monitoring

  • Power generation – turbine and generator monitoring with high-speed sampling

  • Water/wastewater – pump station and treatment plant monitoring

  • Pharmaceutical manufacturing – critical process variable monitoring

  • Food processing – temperature, pressure, and flow monitoring

  • HVAC – building-wide analog signal monitoring

  • Mining – equipment and process monitoring


Competitor Comparison

Feature DS3826AS1D06AA Standard Analog Input Module (8-ch, 12-bit) Competitor 8-ch Isolated AI Module
Channels 8 8 8
Resolution 16-bit 12-bit 16-bit
Sampling Rate 500 Hz 100 Hz 500 Hz
Per-channel Isolation Yes (500 V) No (group only) Yes (500 V)
Configuration Software per-channel Hardware (jumpers) Software per-channel
Diagnostics Enhanced (signal-loss) Basic Basic
Cost per channel Low Very low High

The DS3826AS1D06AA is the high-density, per-channel isolated analog input module – offering 8 channels with 16-bit resolution, 500 Hz sampling, and full per-channel isolation. Compared to standard 8-channel modules, it provides superior isolation, higher resolution, and faster sampling – essential for critical process control applications. For demanding analog input applications requiring high channel density, isolation, and speed, the DS3826AS1D06AA delivers the best-in-class solution.


Selection Tips

  • Choose DS3826AS1D06AA when you need high-density analog inputs (8 channels) with per-channel isolationhigh-speed sampling (500 Hz), and software-configurable input types.

  • Ideal for oil & gas, chemical processing, power generation, and water/wastewater applications.

  • Verify the input type for each channel – software-configurable for 4–20 mA, 0–10 V, or ±10 V.

  • Confirm the terminal configuration (D06AA) matches your panel wiring requirements.

  • For maximum speed (500 Hz), disable input filtering – enabling 50/60 Hz rejection reduces sampling rate.

  • Ensure your PLC/DCS can handle the data throughput from DS3826AS1D06AA at 500 Hz.

  • Not suitable for thermocouple or RTD sensors – use dedicated modules for those sensor types.


Precautions

  • Sampling rate vs. filtering: Maximum 500 Hz achieved with filtering disabled. Enable filtering only if noise rejection is required – it will reduce the sampling rate.

  • Isolated grounds: Do not tie the isolated commons of different channels together – this defeats the isolation and can create ground loops. The DS3826AS1D06AA maintains 500 V isolation between channels only when commons are kept separate.

  • Wiring: Use shielded twisted-pair cables for analog inputs, especially at high sampling rates. Ground shield at module end only.

  • Input overload: Do not exceed the input range (max ±30 V or 50 mA) – exceeding may damage the input circuitry.

  • Data throughput: 500 Hz × 8 channels × 16-bit data requires significant communication bandwidth – ensure your PLC/DCS can process the data rate.

  • Power sequencing: Apply backplane power before field power.

  • Calibration: Perform periodic calibration using precision sources to maintain accuracy – high-speed operation may accelerate drift.

  • Spare: Keep one spare DS3826AS1D06AA for critical high-channel-count loops – the high-density, isolated variant may have longer lead times.

A-B MVI56-MCM
A-B MVI56-MCM
A-B 1756-N2

Reviews

There are no reviews yet.

Be the first to review “GE DS3826AS1D06AA”

Your email address will not be published. Required fields are marked *

Post comment