Description
Key Parameters
-
Channels: 4 isolated analog inputs
-
Sensor Type: Pt100 (2-wire, 3-wire, or 4-wire – software-configurable per channel)
-
Resolution: 24-bit ADC
-
Accuracy: ±0.04°C (Pt100, 25°C); ±0.15°C over –40°C to +70°C
-
Excitation Current: Software-selectable 0.1 mA, 0.5 mA, 1 mA (per channel)
-
Lead Resistance Compensation: Automatic for 3-wire and 4-wire configurations
-
Measurement Range: –200°C to +850°C
-
EMC Protection: Enhanced filtering, CMRR > 120 dB, surge protection (4 kV)
-
Diagnostics: Open-circuit detection, short-circuit detection, over-range/under-range, signal-loss detection, per-channel LED status
-
Isolation: 1500 V RMS (field-to-backplane); 500 V RMS between channels (per-channel isolation)
-
Sampling Rate: Up to 50 Hz per channel (with 50/60 Hz noise rejection)
-
Terminal Type: Screw-type – per suffix “D1A”
-
Power: 24 V DC backplane power, ≤4 W
-
Operating Temperature: –40°C to +70°C
Advantages
-
Pre-configured – fixed terminal configuration; reduces setup time and engineering effort.
-
Enhanced EMC protection – superior noise rejection (CMRR > 120 dB) and 4 kV surge protection; ideal for VFD-heavy and high-EMI environments.
-
Premium accuracy – ±0.04°C; high precision for demanding applications.
-
24-bit resolution – provides superior measurement fidelity.
-
Per-channel isolation – 500 V between channels; prevents ground loops and cross-channel interference.
-
Automatic lead compensation – for 3-wire/4-wire RTDs, cancels lead resistance errors.
-
Software-configurable per channel – wire configuration and excitation current independently settable.
-
Built-in linearization – provides direct temperature readout in °C or °F.
-
Enhanced diagnostics – includes signal-loss detection for proactive maintenance.
-
Open/short detection – detects broken wires or sensor shorts instantly.
-
Hot-swappable – replace without rack power-down.
-
Screw terminals – familiar and secure wiring for traditional panel installations.
Applications
-
VFD-controlled motor systems – bearing and winding temperature monitoring near variable frequency drives
-
Steel mills & foundries – temperature monitoring near high-power equipment
-
Power generation – turbine bearing and generator temperature monitoring in substation environments
-
Oil & gas – pipeline and compressor temperature monitoring with surge protection
-
Semiconductor manufacturing – precision chamber temperature control
-
Research & development – experimental thermal analysis in high-EMI labs
-
Chemical processing – reactor and pipeline temperature monitoring
-
Water/wastewater – pump and motor temperature monitoring
Competitor Comparison
| Feature | DS3820PS5D1A | DS3820PS5D (Configurable Premium) | Standard Pt100 Module (16-bit) |
|---|---|---|---|
| Channels | 4 | 4 | 4 |
| Resolution | 24-bit | 24-bit | 16-bit |
| Accuracy | ±0.04°C | ±0.04°C | ±0.05°C |
| EMC Protection | Enhanced (CMRR > 120 dB, 4 kV surge) | Enhanced | Basic |
| Terminal Type | Screw-type | Screw-type | Screw-type |
| Configuration | Fixed (suffix) | Software-configurable | Software-configurable |
| Setup Time | Instant | Moderate | Moderate |
| Cost | High | High | Low |
The DS3820PS5D1A is the fixed-configuration, screw-terminal variant of the EMC-hardened premium Pt100 input module. Compared to the configurable DS3820PS5D, it offers plug-and-play simplicity while maintaining the same superior noise rejection (CMRR > 120 dB), 4 kV surge protection, and ±0.04°C accuracy. Against standard Pt100 modules, it provides superior resolution (24-bit vs. 16-bit), enhanced EMC protection, and comprehensive diagnostics. For demanding Pt100 applications in high-interference environments requiring minimal engineering effort, the DS3820PS5D1A delivers the most ruggedized, reliable, and deployment-ready solution.
Selection Tips
-
Choose DS3820PS5D1A when you need high-precision Pt100 measurement with enhanced EMC protection, screw-terminal wiring, and plug-and-play simplicity.
-
Ideal for VFD-heavy, substation, steel mill, power generation, oil & gas, and chemical processing applications with significant electrical noise.
-
Verify the wire configuration (2-wire, 3-wire, or 4-wire) – software-configurable per channel.
-
Confirm the terminal configuration (1A) matches your panel wiring requirements.
-
For 2-wire sensors, lead resistance adds error – use 3-wire or 4-wire for accurate measurements.
-
Not suitable for Pt1000, Ni RTDs, or thermocouples – use dedicated modules.
-
Ensure your PLC/DCS can handle 24-bit data resolution from the DS3820PS5D1A.
Precautions
-
Lead resistance: For 2-wire sensors, lead resistance directly adds error – use 3-wire or 4-wire for accurate measurements. The DS3820PS5D1A compensates for 3-wire/4-wire automatically.
-
Excitation current: Higher currents (1 mA) produce self-heating errors – use 0.1 mA or 0.5 mA for sensitive sensors.
-
Wiring: Use shielded twisted-pair cables; ground shield at module end only. Enhanced EMC protection requires proper grounding to function effectively.
-
Surge protection: The DS3820PS5D1A provides 4 kV surge protection – ensure proper grounding to achieve this rating.
-
Signal-loss detection: Requires minimum sensor impedance – very low-impedance sensors may not trigger detection.
-
Power sequencing: Apply backplane power before field power.
-
Calibration: Perform periodic calibration using precision resistors to maintain accuracy.
-
Spare: Keep one spare DS3820PS5D1A for critical high-precision loops – the fixed configuration is typically stocked for quick replacement.

A-B 1747-BA
MVI56-MCMˮ ͷ
SCHNEIDER 140XTS00200




Reviews