GE DS3820PS1B1E1E

¥999.00

The DS3820PS1B1E1E is a 4-channel analog input module specifically designed for Pt100 RTD temperature sensors with high-precision 24-bit resolutionper-channel isolationautomatic lead compensationbuilt-in diagnostics1500 V isolationspring-clamp terminals for vibration-resistant wiring, and a fixed mixed terminal configuration (1B1E1E suffix). It supports 2-wire, 3-wire, or 4-wire Pt100 configurations with software-configurable excitation current and per-channel open/short detection. The DS3820PS1B1E1E delivers ±0.03°C accuracy, making it the premium Pt100 solution for demanding applications in high-vibration environments with plug-and-play simplicity.

Category:

Description

Key Parameters

  • Channels: 4 isolated analog inputs

  • Sensor Type: Pt100 (2-wire, 3-wire, or 4-wire – software-configurable per channel)

  • Resolution: 24-bit ADC

  • Accuracy: ±0.03°C (Pt100, 25°C); ±0.12°C over –40°C to +70°C

  • Excitation Current: Software-selectable 0.1 mA, 0.5 mA, 1 mA (per channel)

  • Lead Resistance Compensation: Automatic for 3-wire and 4-wire configurations

  • Measurement Range: –200°C to +850°C

  • Diagnostics: Open-circuit detection, short-circuit detection, over-range/under-range, signal-loss detection, per-channel LED status

  • Isolation: 1500 V RMS (field-to-backplane); 500 V RMS between channels (per-channel isolation)

  • Sampling Rate: Up to 50 Hz per channel (with 50/60 Hz noise rejection)

  • Terminal Type: Spring-clamp (tool-free, vibration-resistant) – per suffix “1B1E1E”

  • Power: 24 V DC backplane power, ≤3.5 W

  • Operating Temperature: –40°C to +70°C


Advantages

  • Pre-configured – fixed terminal configuration; reduces setup time and engineering effort.

  • Spring-clamp terminals – tool-free push-in wiring; reduces installation time; highly resistant to vibration loosening – critical for transportation, marine, and heavy industrial applications.

  • Premium accuracy – ±0.03°C; highest precision Pt100 module in the family.

  • 24-bit resolution – provides superior measurement fidelity for demanding applications.

  • Per-channel isolation – 500 V between channels; prevents ground loops and cross-channel interference.

  • Automatic lead compensation – for 3-wire/4-wire RTDs, cancels lead resistance errors for accurate temperature readings.

  • Software-configurable per channel – wire configuration and excitation current independently settable.

  • Built-in linearization – provides direct temperature readout in °C or °F; no scaling required.

  • Enhanced diagnostics – includes signal-loss detection for proactive maintenance.

  • Open/short detection – detects broken wires or sensor shorts instantly.

  • Hot-swappable – replace without rack power-down.

  • Wide measurement range – –200°C to +850°C covers most industrial applications.


Applications

  • Transportation & rail – bearing and motor temperature monitoring with vibration-resistant wiring

  • Marine & offshore – engine room temperature monitoring with spring-clamp terminals

  • Metrology & calibration labs – high-precision temperature measurement and sensor verification

  • Semiconductor manufacturing – diffusion furnace and wafer processing with tight temperature tolerances

  • Aerospace testing – component thermal profiling with highest accuracy

  • Pharmaceutical – critical reactor temperature control with strict regulatory requirements

  • Research & development – experimental thermal analysis and material testing

  • Power generation – turbine inlet and bearing temperature monitoring


Competitor Comparison

Feature DS3820PS1B1E1E DS3820PIMB (Screw-type Premium) Standard Pt100 Module (16-bit)
Channels 4 4 4
Resolution 24-bit 24-bit 16-bit
Accuracy ±0.03°C ±0.03°C ±0.05°C
Diagnostics Enhanced (signal-loss) Enhanced Basic
Per-channel Isolation Yes (500 V) Yes (500 V) Group only
Terminal Type Spring-clamp Screw-type Screw-type
Vibration Resistance High Medium Medium
Configuration Fixed (suffix) Software-configurable Software-configurable
Setup Time Instant Moderate Moderate
Cost High Mid-high Low

The DS3820PS1B1E1E is the fixed-configuration, spring-clamp variant of the premium Pt100 input module. Compared to the screw-terminal DS3820PIMB, it offers faster installation, reduced maintenance time, and superior vibration resistance – critical for transportation, marine, and heavy industrial applications – while maintaining the same ±0.03°C accuracy and adding plug-and-play simplicity. Against standard Pt100 modules, it provides superior resolution (24-bit vs. 16-bit), enhanced diagnostics, and vibration-resistant wiring. For demanding Pt100 temperature applications in high-vibration environments requiring minimal engineering effort, the DS3820PS1B1E1E delivers the best-in-class, deployment-ready solution.


Selection Tips

  • Choose DS3820PS1B1E1E when you need maximum precision for Pt100 temperature measurement with vibration-resistant spring-clamp wiring and plug-and-play simplicity.

  • Ideal for transportation, marine, offshore, and heavy industrial applications where screw terminals may loosen over time.

  • Verify the wire configuration (2-wire, 3-wire, or 4-wire) – software-configurable per channel.

  • Confirm spring-clamp terminals accept your wire gauge (typically 0.2–2.5 mm² / 24–14 AWG) and consider using ferrules for stranded wire.

  • Confirm the terminal configuration (1B1E1E) matches your panel wiring requirements.

  • For 2-wire sensors, lead resistance adds error – use 3-wire or 4-wire for accurate measurements.

  • Not suitable for Pt1000, Ni RTDs, or thermocouples – use dedicated modules.

  • Ensure your PLC/DCS can handle 24-bit data resolution from the DS3820PS1B1E1E.


Precautions

  • Wire preparation: Use only solid or stranded wire with proper ferrule termination – bare stranded wire may not make reliable contact in spring-clamp terminals.

  • Wire insertion: Insert wire fully into the spring-clamp opening until it stops; pull gently to verify secure connection.

  • Lead resistance: For 2-wire sensors, lead resistance directly adds error – use 3-wire or 4-wire for accurate measurements. The DS3820PS1B1E1E compensates for 3-wire/4-wire automatically.

  • Excitation current: Higher currents (1 mA) produce self-heating errors in small Pt100 elements – use 0.1 mA or 0.5 mA for sensitive sensors.

  • Wiring: Use shielded twisted-pair cables; ground shield at module end only. For 4-wire, use separate pairs for excitation and sense leads.

  • Signal-loss detection: Requires minimum sensor impedance – very low-impedance sensors may not trigger detection.

  • Power sequencing: Apply backplane power before field power.

  • Calibration: Perform periodic calibration using precision resistors to maintain ±0.03°C accuracy – the DS3820PS1B1E1E requires regular verification to maintain specification.

  • Spare: Keep one spare DS3820PS1B1E1E for critical high-precision loops – the fixed configuration is typically stocked for quick replacement. Also stock replacement ferrules for spring-clamp terminals.

A-B 1747-BA
A-B 2711-T9C9 Ĥ
A-B 1746-NI8ϵ и

Reviews

There are no reviews yet.

Be the first to review “GE DS3820PS1B1E1E”

Your email address will not be published. Required fields are marked *

Post comment