Description
Key Parameters
-
Channels: 4 isolated analog inputs
-
Sensor Type: Pt100 (2-wire, 3-wire, or 4-wire – software-configurable per channel)
-
Resolution: 24-bit ADC
-
Accuracy: ±0.03°C (Pt100, 25°C); ±0.12°C over –40°C to +70°C
-
Excitation Current: Software-selectable 0.1 mA, 0.5 mA, 1 mA (per channel)
-
Lead Resistance Compensation: Automatic for 3-wire and 4-wire configurations
-
Measurement Range: –200°C to +850°C
-
Diagnostics: Open-circuit detection, short-circuit detection, over-range/under-range detection, signal-loss detection, per-channel LED status
-
Isolation: 1500 V RMS (field-to-backplane); 500 V RMS between channels (per-channel isolation)
-
Sampling Rate: Up to 50 Hz per channel (with 50/60 Hz noise rejection)
-
Terminal Type: Fixed mixed configuration (per suffix “1A1B”)
-
Power: 24 V DC backplane power, ≤3.5 W
-
Operating Temperature: –40°C to +70°C
Advantages
-
Pre-configured – fixed terminal configuration; reduces setup time and engineering effort.
-
Premium accuracy – ±0.03°C; the highest precision Pt100 module in the family; ideal for critical temperature control.
-
24-bit resolution – provides superior measurement fidelity for demanding applications.
-
Per-channel isolation – 500 V between channels; prevents ground loops and cross-channel interference.
-
Automatic lead compensation – for 3-wire/4-wire RTDs, cancels lead resistance errors for accurate temperature readings.
-
Software-configurable per channel – wire configuration and excitation current independently settable.
-
Built-in linearization – provides direct temperature readout in °C or °F; no scaling required.
-
Enhanced diagnostics – includes signal-loss detection for proactive maintenance.
-
Open/short detection – detects broken wires or sensor shorts instantly.
-
Hot-swappable – replace without rack power-down.
-
Wide measurement range – –200°C to +850°C covers most industrial applications.
Applications
-
Metrology & calibration labs – high-precision temperature measurement and sensor verification
-
Semiconductor manufacturing – diffusion furnace and wafer processing with tight temperature tolerances
-
Aerospace testing – component thermal profiling with highest accuracy
-
Pharmaceutical – critical reactor temperature control with strict regulatory requirements
-
Research & development – experimental thermal analysis and material testing
-
Power generation – turbine inlet and bearing temperature monitoring
-
HVAC – precision environmental chamber temperature control
Competitor Comparison
| Feature | DS3820PIMB1A1B | DS3820P1MB (16-bit Pt100) | Competitor Premium Pt100 Module |
|---|---|---|---|
| Channels | 4 | 4 | 4 |
| Resolution | 24-bit | 16-bit | 24-bit |
| Accuracy | ±0.03°C | ±0.05°C | ±0.03°C |
| Diagnostics | Enhanced (signal-loss) | Basic | Basic |
| Per-channel Isolation | Yes (500 V) | Yes (500 V) | Yes (500 V) |
| Lead Compensation | 3/4-wire auto | 3/4-wire auto | 3/4-wire auto |
| Configuration | Fixed (suffix) | Software-configurable | Software-configurable |
| Setup Time | Instant | Moderate | Moderate |
| Cost per channel | Mid-high | Low | High |
The DS3820PIMB1A1B is the fixed-configuration premium Pt100 input module with 24-bit resolution and ±0.03°C accuracy. Compared to the DS3820P1MB (16-bit), it provides superior resolution and accuracy – essential for laboratory-grade and critical process applications – with plug-and-play simplicity. Against competitor premium Pt100 modules, the DS3820PIMB1A1B offers comparable performance with superior diagnostics (signal-loss detection) at a lower cost. For applications demanding the highest Pt100 temperature measurement accuracy with minimal engineering effort, the DS3820PIMB1A1B delivers the best-in-class, deployment-ready solution.
Selection Tips
-
Choose DS3820PIMB1A1B when you need maximum precision for Pt100 temperature measurement with plug-and-play simplicity – ideal for lab, R&D, semiconductor, and pharmaceutical applications.
-
Verify the wire configuration (2-wire, 3-wire, or 4-wire) – software-configurable per channel.
-
Confirm the terminal configuration (1A1B) matches your panel wiring requirements.
-
For 2-wire sensors, lead resistance adds error – use 3-wire or 4-wire for accurate measurements.
-
Not suitable for Pt1000, Ni RTDs, or thermocouples – use dedicated modules.
-
Ensure your PLC/DCS can handle 24-bit data resolution from the DS3820PIMB1A1B.
Precautions
-
Lead resistance: For 2-wire sensors, lead resistance directly adds error – use 3-wire or 4-wire for accurate measurements. The DS3820PIMB1A1B compensates for 3-wire/4-wire automatically.
-
Excitation current: Higher currents (1 mA) produce self-heating errors in small Pt100 elements – use 0.1 mA or 0.5 mA for sensitive sensors.
-
Wiring: Use shielded twisted-pair cables; ground shield at module end only. For 4-wire, use separate pairs for excitation and sense leads.
-
Signal-loss detection: Requires minimum sensor impedance – very low-impedance sensors may not trigger detection.
-
Power sequencing: Apply backplane power before field power.
-
Calibration: Perform periodic calibration using precision resistors to maintain ±0.03°C accuracy – the DS3820PIMB1A1B requires regular verification to maintain specification.
-
Spare: Keep one spare DS3820PIMB1A1B for critical high-precision loops – the fixed configuration is typically stocked for quick replacement, but premium modules may have longer lead times.

A-B 1756-BA2
A-B 2711-T9C9 Ĵ
A-B 1747-BA


Reviews