Description
Key Parameters
-
Channels: 4 analog outputs
-
Output Type: 4–20 mA (current loop)
-
Loop Power: Internal 24 V DC, 30 mA per channel (loop-powered; no external supply needed for 2-wire devices)
-
Output Resolution: 16-bit (0.0015% of full scale)
-
Accuracy: ±0.06% of full scale (25°C); ±0.2% over –40°C to +85°C
-
Loop Resistance: Maximum 600 Ω (at 24 V internal supply)
-
Settling Time: < 5 ms (to 0.1% of final value)
-
Diagnostics: Per-channel short-circuit detection, open-wire detection, over-temperature alarm, per-channel LED status
-
Fail-Safe States: Software-configurable per channel (hold last value, go to 4 mA, go to 20 mA, or user-defined preset) on communication loss
-
Isolation: 1500 V RMS (field-to-backplane); 500 V RMS between channels
-
Operating Temperature: –40°C to +85°C (extended range)
-
Terminal Type: Fixed screw-type (per suffix “1A1A”)
-
Power: 24 V DC backplane power, ≤4 W (logic + internal loop power)
Advantages
-
Pre-configured – fixed screw-type terminal configuration; reduces setup time and engineering effort.
-
Extended temperature range – operates reliably in extreme ambient conditions (up to +85°C); ideal for outdoor, desert, or unheated enclosures.
-
Integrated loop power – internal 24 V loop power per channel; eliminates external power supplies for 2-wire transmitters and smart devices.
-
High 16-bit resolution – provides precise analog control for demanding process applications.
-
Open-wire detection – detects broken output wiring or disconnected loads; alerts operators for proactive maintenance.
-
Per-channel short-circuit protection – auto-restart protection; eliminates external fuses and reduces downtime.
-
Software-configurable fail-safe – define output behavior (hold, 4 mA, 20 mA, or preset) on communication loss for safe system shutdown.
-
Fast settling time – < 5 ms for dynamic control loops.
-
High channel density – 4 outputs in a single slot; saves rack space.
-
LED status indicators – per-channel visual indication for quick troubleshooting.
-
Hot-swappable – replace without rack power-down.
-
Optical isolation – protects backplane from field transients.
Applications
-
Oil & gas pipelines – VFD speed control and valve positioning in desert (hot) or arctic (cold) locations
-
Outdoor power substations – process setpoint control in direct sunlight or extreme cold
-
Steel mills & foundries – analog control near high-heat zones
-
Wind turbines – pitch and yaw control with extended temperature rating
-
Marine & offshore – engine room control in high-temperature environments
-
VFD speed control – providing 4–20 mA reference signals to variable frequency drives
-
Proportional valve control – precise positioning of hydraulic and pneumatic valves
-
Process control – setpoint output for temperature, pressure, and flow controllers
-
Smart transmitter communication – powering and controlling HART-enabled smart transmitters
Competitor Comparison
| Feature | DS3820LIMC1A1A | DS3820LIMC (Configurable, Extended Temp) | Standard Analog Output Module (12-bit) |
|---|---|---|---|
| Resolution | 16-bit | 16-bit | 12-bit |
| Accuracy | ±0.06% | ±0.06% | ±0.1% |
| Operating Temp | –40°C to +85°C | –40°C to +85°C | –25°C to +70°C |
| Integrated Loop Power | Yes (24 V, 30 mA/ch) | Yes | No |
| Open-Wire Detection | Yes | Yes | No |
| Short-Circuit Protection | Yes | Yes | Limited |
| Configuration | Fixed (suffix) | Software-configurable | Fixed |
| Setup Time | Instant | Moderate | Instant |
| Cost | High | High | Low |
The DS3820LIMC1A1A is the fixed-configuration, extended-temperature, high-resolution current-output module. Compared to the configurable DS3820LIMC, it eliminates setup time while maintaining the same ruggedized performance and integrated loop power. Against standard 12-bit output modules, the DS3820LIMC1A1A provides 16× finer resolution, eliminates external loop power supplies, adds open-wire detection and per-channel fail-safe configuration, and extends operating temperature to +85°C – all with plug-and-play simplicity. For demanding 4–20 mA process control applications in extreme environments requiring minimal engineering effort, the DS3820LIMC1A1A delivers the most comprehensive and deployment-ready solution.
Selection Tips
-
Choose DS3820LIMC1A1A when you need high-precision 4–20 mA outputs with integrated loop power, extended temperature operation (–40°C to +85°C), and plug-and-play simplicity.
-
Ideal for oil & gas, outdoor substations, steel mills, wind turbines, and marine applications.
-
Verify the loop resistance does not exceed 600 Ω per channel – the internal 24 V supply supports up to 600 Ω at 20 mA.
-
Confirm the screw-type terminal configuration matches your panel wiring requirements.
-
Consider the fail-safe behavior – configure each channel for the safe state on communication loss.
-
Note the slight accuracy reduction at extreme temperatures (±0.2% vs. ±0.15% for standard range) – a trade-off for extended operation.
-
Not suitable for 0–10 V voltage-output devices – use the DS3820LFRA variant for voltage outputs.
-
Ensure your PLC/DCS can read and process diagnostic data from the DS3820LIMC1A1A.
Precautions
-
Temperature derating: At sustained +85°C ambient, ensure adequate airflow – the DS3820LIMC1A1A dissipates up to 4 W and may require forced cooling in dense racks.
-
Loop resistance: Do not exceed 600 Ω per channel (including wiring and load). Higher resistance may cause output current saturation.
-
Wiring: Use shielded twisted-pair cables for analog outputs to reduce EMI. Ground shield at module end only.
-
Inductive loads: The DS3820LIMC1A1A is not designed for direct inductive loads – use external buffers or isolators for inductive actuators.
-
Fail-safe testing: Test fail-safe behavior during commissioning – confirm outputs go to the desired state on communication loss.
-
Open-wire detection: Requires a minimum load current – very high-impedance loads (>1 MΩ) may not trigger open-wire detection.
-
Loop power capacity: Each channel provides 24 V, 30 mA – ensure total loop current does not exceed 30 mA.
-
HART compatibility: Supports HART communication – ensure proper impedance (250 Ω) for HART modem connection.
-
Grounding: Maintain proper grounding to avoid ground loops that could affect output accuracy.
-
Calibration: Perform periodic calibration using a precision current meter to maintain accuracy – extended temperature operation may accelerate drift.
-
Spare: Keep one spare DS3820LIMC1A1A for critical control applications – the fixed configuration is typically stocked for quick replacement, but extended-temperature modules may have longer lead times.

Motorola MVME117A
TRICONEX 3625
ENTERASYS A4H124-24FX