Description
Key Parameters
-
Channels: 8 differential, individually configurable
-
Inputs: 4–20 mA, 0–20 mA, 0–5 V, 0–10 V, ±10 V (software-selectable per channel)
-
Sampling Mode: Simultaneous (all channels sampled at same instant)
-
Resolution: 16-bit ADC
-
Sampling Rate: Up to 1 kHz per channel (simultaneous, global)
-
Accuracy: ±0.1% FS (25°C); ±0.3% over –40°C to +70°C
-
Phase Mismatch: < 0.1° at 50/60 Hz (between channels)
-
Isolation: 1500 V RMS field-to-logic (group isolated)
-
Power: 24 V DC, ≤6 W
-
Diagnostics: Open-circuit, over/under-range, watchdog timer
-
CMRR: >100 dB
Advantages
-
Simultaneous sampling – captures all 8 channels at precisely the same moment; eliminates phase errors between signals.
-
Software configurable per channel – each channel independently set for current or voltage.
-
High-speed sampling – up to 1 kHz per channel, suitable for dynamic process monitoring.
-
Hot-swappable – replace without rack power-down.
-
Minimal phase mismatch – < 0.1° at 50/60 Hz ensures accurate power and vector calculations.
-
Built-in diagnostics – alerts for broken wires and out-of-range conditions.
Applications
-
Power monitoring – 3-phase voltage and current measurements for power quality analysis (V, A, W, VAR, PF)
-
Motor control – simultaneous current and voltage monitoring for torque and efficiency calculations
-
Vibration analysis – multi-axis accelerometer data capture for predictive maintenance
-
Hydraulic systems – pressure and flow monitoring requiring time-correlated data
-
Test & measurement – dynamic process characterization and transient recording
-
Renewable energy – solar inverter and wind turbine output monitoring
Competitor Comparison
| Feature | DS3820AISA | Standard Analog AI (Sequential) | Competitor Simultaneous AI |
|---|---|---|---|
| Sampling Mode | Simultaneous | Sequential (per channel) | Simultaneous |
| Phase Mismatch | < 0.1° | Up to 5° (at 60 Hz) | < 0.2° |
| Max Sampling Rate | 1 kHz/ch | 250 Hz/ch | 1 kHz/ch |
| Config | Software per-channel | Software/Jumper | Software |
| Isolation | Group | Group | Per-channel (premium) |
| Cost | Mid-high | Mid | High |
The DS3820AISA provides premium simultaneous sampling performance at a fraction of the cost of per-channel isolated competitors. Compared to standard sequential-scan modules, the DS3820AISA eliminates the phase delay that can cause significant errors in power calculations and dynamic control loops – errors that often go undetected until system instability occurs. For applications requiring precise time-correlation, the DS3820AISA is the clear choice over sequentially scanned alternatives. Against competitor simultaneous modules, the DS3820AISA offers comparable performance at a lower price point, making it the best value for power quality and dynamic monitoring applications.
Selection Tips
-
Choose DS3820AISA when you need time-coherent measurements across multiple channels – essential for power, vibration, and dynamic process control.
-
Ideal for 3-phase power systems (use 3 channels for voltage, 3 for current, 2 spare).
-
Verify your CPU scan rate can handle the 1 kHz data throughput.
-
Not suitable for applications where per-channel isolation is mandatory – consider the DS3820AIQA family instead.
-
If your application only requires static process monitoring (slow temperature/pressure), a standard sequential AI module will be more cost-effective.
Precautions
-
Wiring: Use shielded twisted-pair cables to maintain signal integrity at higher sampling rates.
-
Grounding: Maintain single-point grounding to avoid noise at high frequencies.
-
Power sequencing: Apply backplane power before field power.
-
Cooling: Ensure adequate airflow in dense racks – the DS3820AISA dissipates up to 6 W.
-
Data throughput: High sampling rates generate significant data traffic – ensure your controller and communication bus have sufficient bandwidth.
-
Spare: Keep one spare DS3820AISA for critical monitoring loops to minimize downtime.
-
Configuration: Set all channel input types before enabling simultaneous mode – changing a channel type may disrupt sampling timing.



Reviews