GE DS3800XTFT1B1B

¥999.00

The DS3800XTFT1B1B is an advanced multi-function board for the GE Mark IV turbine control system that combines temperature measurement (thermocouple/RTD) with frequency transmitter (signal conversion) capabilities, featuring the latest firmware revision (1B1B) . It is designed for applications requiring both precise temperature monitoring and the conversion of frequency signals into standard analog or digital outputs for integration with external systems. The 1B1B firmware provides refined diagnostic reportingenhanced fault logging, and improved output scaling resolution over the 1B1A variant. It works alongside boards such as the DS3800NVIA1G1CDS3800NVIA1G1D, and DS3800XTBA series.

Category:

Description

Key Parameters

Temperature Section:

  • Input Channels: 8 differential thermocouple/RTD inputs

  • Input Types: Thermocouple (J, K, T, E, R, S, B, N), RTD (Pt100, Ni100), millivolt

  • Resolution: 16-bit ADC with ±0.05% accuracy

  • Cold-Junction Compensation: Enhanced built-in per channel with improved accuracy

  • Diagnostics: Burnout detection, open-circuit detection, over-range/under-range detection, enhanced fault logging (firmware 1B1B) , self-test on power-up

Frequency Transmitter Section:

  • Input Channels: 2 independent frequency input channels

  • Input Types: Magnetic pickup, proximity, TTL (5V), or 24V DC (jumper-selectable)

  • Maximum Input Frequency: 250 kHz

  • Output Types: Analog (4–20mA or 0–10V) or digital (frequency/pulse) output (software-selectable)

  • Output Accuracy: ±0.05% of full scale (analog) or ±0.005% (digital)

  • Output Scaling: Expanded programmable scaling options with improved resolution (1B1B)

  • Transmitter Function: Converts frequency input to scaled analog signal or retransmits frequency for external systems

  • Diagnostics: LED status per channel, input signal loss detection, output fault detection, signal quality monitoringrefined diagnostic detail over 1B1A

Common Section:

  • Isolation: 2500V RMS channel-to-backplane

  • Temp Range: –40°C to +85°C (extended)

  • Power Supply: +5V, ±15V from VME backplane

  • Physical: 6U VME single-slot board

  • Key Features: Combined temperature and frequency transmitter, enhanced CJC, 250 kHz input, expanded scaling with improved resolution, 2500V isolation, self-test, firmware rev 1B1B


Advantages

  • Multi-function capability – the DS3800XTFT1B1B combines temperature measurement and frequency-to-analog/digital conversion in a single slot, reducing board count and rack space requirements.

  • Enhanced cold-junction compensation – improved CJC accuracy with advanced compensation algorithms ensures precise temperature readings across a wider ambient range.

  • Higher frequency capability – supports up to 250 kHz frequency inputs, suitable for high-speed turbine pickups and high-resolution encoders.

  • Improved digital output accuracy – ±0.005% accuracy provides precise frequency retransmission for external systems.

  • Refined output scaling – the 1B1B firmware provides improved scaling resolution and more precise configuration options over the 1B1A variant.

  • Enhanced diagnostics – the General Electric DS3800XTFT1B1B provides refined diagnostic reporting, improved fault logging, self-test on power-up, and signal quality monitoring for predictive maintenance.

  • Burnout detection – automatically detects broken thermocouple wires and flags the channel.

  • Improved isolation – 2500V RMS isolation protects the backplane from field-side noise and transients.

  • Extended temperature range – operates from –40°C to +85°C for harsh environments.

  • Drop-in compatible – works with all Mark IV backplanes and processor configurations.


Applications

  • Turbine EGT and speed transmitter – measures exhaust gas temperature (EGT) and converts turbine speed frequency to a 4–20mA signal for external monitoring systems.

  • Temperature plus flow transmitter – monitors thermocouple or RTD temperatures while converting flowmeter frequency pulses to analog signals for plant DCS.

  • Bearing temperature and speed transmitter – combines bearing RTD inputs with speed pickup frequency-to-analog conversion.

  • High-speed applications – the 250 kHz frequency input capability of the DS3800XTFT1B1B is suitable for high-speed turbines and encoders.

  • Signal conditioning for external systems – provides isolated analog outputs for vibration monitors, speed controllers, or plant historians.

  • Offshore and harsh environments – extended temperature range makes it suitable for demanding applications.


vs Competitors & Previous Variants

Feature DS3800XTFT1B1B DS3800XTFT1B1A Standard DS3800XTFT Generic Combo Board
Temperature channels 8 8 8 8
Frequency input channels 2 2 2 2
Max freq input 250 kHz 250 kHz 100 kHz 50–100 kHz
Digital output accuracy ±0.005% ±0.005% ±0.01% ±0.05–0.1%
Scaling resolution Improved (1B1B) Standard Standard Limited
Diagnostic detail Refined (1B1B) Standard Standard Basic
Fault logging Enhanced (1B1B) Enhanced Standard No
Isolation 2500V 2500V 1500V 500–1500V
Extended temp range –40°C to +85°C –40°C to +85°C –30°C to +70°C 0°C to +60°C
Self-test on power-up Yes (1B1B) Yes (1B1A) No No
Firmware revision 1B1B 1B1A Varies N/A

Selection Tips

  • Signal transmission with refined diagnostics – choose the DS3800XTFT1B1B when you need both temperature measurement and frequency-to-analog/digital conversion, combined with the latest firmware for refined diagnostic reporting and improved scaling resolution.

  • High-frequency applications – the 250 kHz capability of the General Electric DS3800XTFT1B1B is suitable for high-speed turbine pickups and high-resolution encoders.

  • Precise scaling – the 1B1B firmware provides improved scaling resolution, making it ideal for applications requiring fine-tuned frequency-to-analog conversion.

  • Slot-limited installations – ideal for compact systems with limited rack slots where both measurement and transmission are required.

  • Harsh environments – the extended temperature range makes it suitable for offshore, desert, or unheated cabinet installations.

  • Output type selection – supports 4–20mA, 0–10V, or digital pulse outputs; verify which output type is required by your external system.

  • Firmware compatibility – confirm your Mark IV main processor firmware supports the enhanced features of the DS3800XTFT1B1B.

  • Spare strategy – keep one DS3800XTFT1B1B per 5–8 installed units, especially in systems where it serves multiple critical functions.

  • Calibration – periodically verify temperature accuracy and frequency-to-output scaling using precision instruments.


Critical Precautions

  • Thermocouple wiring – use the correct extension-grade thermocouple wire (not copper) for temperature inputs to the DS3800XTFT1B1B; incorrect wire types introduce cold-junction errors.

  • Thermocouple polarity – observe correct polarity when connecting thermocouples; reversed polarity produces inverted readings.

  • RTD wiring – use 3-wire or 4-wire RTD connections to cancel lead resistance; 2-wire connections introduce measurement errors.

  • CJC location – the DS3800XTFT1B1B cold-junction compensation measures the temperature at the terminal block. Ensure the terminal block is not exposed to drafts or radiant heat.

  • Frequency input voltage limits – never apply voltage above 30V to the frequency inputs; magnetic pickups can generate high voltages at high speeds – use appropriate attenuation.

  • Output load limits – do not exceed the maximum load resistance for 4–20mA outputs (typically 600Ω) or the minimum load resistance for 0–10V outputs (typically 2kΩ) on the General Electric DS3800XTFT1B1B.

  • Cable shielding – use shielded twisted-pair cables for all thermocouple, RTD, frequency inputs, and analog outputs. Ground the shield only at the DS3800XTFT1B1B end to prevent ground loops.

  • Ground loops – use single-point grounding for all sensors and outputs connected to the DS3800XTFT1B1B to avoid ground-loop noise.

  • Output scaling – ensure the scaling parameters (frequency range to output range) are correctly configured in the DS3800XTFT1B1B before commissioning.

  • Self-test – allow the DS3800XTFT1B1B to complete its power-up self-test (~2 seconds) before relying on measurements or outputs.

  • Hot-swap – never insert or remove the DS3800XTFT1B1B while the rack is powered; this can cause bus errors or component damage.

  • ESD handling – always use a grounded wrist strap when handling the DS3800XTFT1B1B; CMOS and precision analog components are ESD-sensitive.

  • Storage – store spare DS3800XTFT1B1B boards in anti-static bags in a dry, temperature-controlled environment.

schneider BMXFTB2010
schneider BMXFTB2820
SIEMENS FDT181

Reviews

There are no reviews yet.

Be the first to review “GE DS3800XTFT1B1B”

Your email address will not be published. Required fields are marked *