GE DS3800XTFP1E1C

¥999.00

The DS3800XTFP1E1C is an advanced multi-function board for the GE Mark IV turbine control system that combines temperature measurement (thermocouple/RTD) with frequency input capabilities, featuring the latest firmware revision (1E1C) . It is designed for applications requiring both precise temperature monitoring and frequency-based speed or flow measurement in a single slot, with enhanced diagnosticsimproved accuracy, and self-test on power-up. It is a direct successor to the standard DS3800XTFP, with refined diagnostic reporting and improved performance. It works alongside boards such as the DS3800NVIA1G1CDS3800NVIA1G1D, and DS3800XTBA series.

Category:

Description

Key Parameters

Temperature Section:

  • Input Channels: 8 differential thermocouple/RTD inputs

  • Input Types: Thermocouple (J, K, T, E, R, S, B, N), RTD (Pt100, Ni100), millivolt

  • Resolution: 16-bit ADC with ±0.05% accuracy

  • Cold-Junction Compensation: Enhanced built-in per channel with improved accuracy

  • Diagnostics: Burnout detection, open-circuit detection, over-range/under-range detection, enhanced fault logging (firmware 1E1C) , self-test on power-up

Frequency Section:

  • Input Channels: 2 independent counter/frequency channels

  • Input Types: Magnetic pickup, proximity, TTL (5V), or 24V DC (jumper-selectable)

  • Maximum Input Frequency: 250 kHz (improved over standard 100 kHz)

  • Measurement Method: Pulse counting or period-averaging (software-selectable)

  • Accuracy: ±0.005% of reading (improved over standard)

Common Section:

  • Isolation: 2500V RMS channel-to-backplane (enhanced)

  • Temp Range: –40°C to +85°C (extended)

  • Power Supply: +5V, ±15V from VME backplane

  • Physical: 6U VME single-slot board

  • Key Features: Combined temperature and frequency measurement, enhanced CJC, 250 kHz freq input, 2500V isolation, extended temp range, self-test, firmware rev 1E1C


Advantages

  • Multi-function capability – the DS3800XTFP1E1C combines temperature and frequency measurement in a single slot, reducing board count and rack space requirements.

  • Enhanced cold-junction compensation – improved CJC accuracy with advanced compensation algorithms ensures precise temperature readings across a wider ambient range.

  • Higher frequency capability – supports up to 250 kHz frequency inputs (improved over standard 100 kHz), suitable for high-speed turbine pickups and high-resolution encoders.

  • Improved frequency accuracy – ±0.005% accuracy provides precise speed and flow measurement.

  • Enhanced diagnostics – the 1E1C firmware provides improved fault logging, self-test on power-up, and refined diagnostic reporting for predictive maintenance.

  • Burnout detection – automatically detects broken thermocouple wires and flags the channel.

  • Improved isolation – 2500V RMS isolation protects the backplane from field-side noise and transients.

  • Extended temperature range – operates from –40°C to +85°C for harsh environments.

  • Drop-in compatible – works with all Mark IV backplanes and processor configurations.


Applications

  • Turbine EGT and speed monitoring – measures exhaust gas temperature (EGT) and turbine speed from a single board, ideal for compact systems.

  • Temperature plus flow – monitors thermocouple or RTD temperatures while simultaneously reading frequency pulses from flowmeters.

  • Compact turbine control systems – the General Electric DS3800XTFP1E1C is suitable for installations with limited rack slots.

  • Bearing temperature and speed monitoring – combines bearing RTD inputs with speed pickup frequency measurements.

  • Offshore and harsh environments – extended temperature range makes it suitable for demanding applications.

  • Retrofits – replaces separate temperature and frequency boards with a single, integrated solution.


vs Competitors & Previous Variants

Feature DS3800XTFP1E1C Standard DS3800XTFP DS3800XTBA + DS3800XCIA Generic Combo Board
Temperature channels 8 8 16 + 4 8
Frequency channels 2 2 0 + 4 2
Max freq input 250 kHz 100 kHz 100 kHz (XCIA) 50–100 kHz
Freq accuracy ±0.005% ±0.01% <0.01% ±0.05–0.1%
CJC accuracy Enhanced Standard Standard External
Isolation 2500V 1500V 1500V + 1500V 500–1500V
Extended temp range –40°C to +85°C –30°C to +70°C –30°C to +70°C 0°C to +60°C
Self-test on power-up Yes (1E1C) No No No
Fault logging Enhanced (1E1C) Standard Standard No
Firmware revision 1E1C Varies Varies N/A

Selection Tips

  • Multi-function plus advanced features – choose the DS3800XTFP1E1C when you need both temperature and frequency measurement in a single slot, combined with higher frequency capability, enhanced diagnostics, and extended temperature range.

  • Slot-limited installations – ideal for compact systems with limited rack slots.

  • High-speed frequency applications – the 250 kHz capability of the General Electric DS3800XTFP1E1C is suitable for high-speed turbine pickups and high-resolution encoders.

  • Harsh environments – the extended temperature range makes it suitable for offshore, desert, or unheated cabinet installations.

  • Enhanced diagnostics – the 1E1C firmware provides improved fault logging and self-test, aiding predictive maintenance.

  • Sensor compatibility – verify that your thermocouple/RTD types and frequency sensors (magnetic, proximity, TTL, 24V) are supported by the DS3800XTFP1E1C.

  • Firmware compatibility – confirm your Mark IV main processor firmware supports the enhanced diagnostic features of the DS3800XTFP1E1C.

  • Spare strategy – keep one DS3800XTFP1E1C per 5–8 installed units, especially in compact systems where it serves multiple critical functions.

  • Calibration – periodically verify temperature accuracy using a precision calibrator and frequency accuracy using a signal generator.


Critical Precautions

  • Thermocouple wiring – use the correct extension-grade thermocouple wire (not copper) for temperature inputs to the DS3800XTFP1E1C; incorrect wire types introduce cold-junction errors.

  • Thermocouple polarity – observe correct polarity when connecting thermocouples; reversed polarity produces inverted readings.

  • RTD wiring – use 3-wire or 4-wire RTD connections to cancel lead resistance; 2-wire connections introduce measurement errors.

  • CJC location – the DS3800XTFP1E1C cold-junction compensation measures the temperature at the terminal block. Ensure the terminal block is not exposed to drafts or radiant heat.

  • Frequency input voltage limits – never apply voltage above 30V to the frequency inputs; magnetic pickups can generate high voltages at high speeds – use appropriate attenuation.

  • Cable shielding – use shielded twisted-pair cables for all thermocouple, RTD, and frequency inputs. Ground the shield only at the General Electric DS3800XTFP1E1C end to prevent ground loops.

  • Ground loops – use single-point grounding for all sensors connected to the DS3800XTFP1E1C to avoid ground-loop noise.

  • Frequency update rate – when using period-averaging, ensure the update rate is set appropriately for the input frequency; low frequencies require longer averaging.

  • Self-test – allow the DS3800XTFP1E1C to complete its power-up self-test (~2 seconds) before relying on measurements.

  • Hot-swap – never insert or remove the DS3800XTFP1E1C while the rack is powered; this can cause bus errors or component damage.

  • ESD handling – always use a grounded wrist strap when handling the DS3800XTFP1E1C; CMOS and precision analog components are ESD-sensitive.

  • Storage – store spare DS3800XTFP1E1C boards in anti-static bags in a dry, temperature-controlled environment.

SCHNEIDER KCF3PZC
A-B 1756-N2
A-B 1756-N2

Reviews

There are no reviews yet.

Be the first to review “GE DS3800XTFP1E1C”

Your email address will not be published. Required fields are marked *