GE DS3800XAID

¥999.00

The DS3800XAID is a high-density, configurable variant of the GE Mark IV analog I/O extender board. It provides 32 analog inputs and 16 analog outputs, combining the high channel count of the DS3800XAIB series with the per-channel configurability of the DS3800XAIC series. This board is designed for large, complex turbine installations that require both maximum I/O density and the flexibility to handle mixed signal types (voltage and current) on a per-channel basis. It works alongside boards such as the DS3800NVIA1G1CDS3800NVIA1G1D, and DS3800NVOC to provide comprehensive analog signal handling.

Category:

Description

Key Parameters

  • Analog Input Channels: 32 differential or 64 single-ended (software-configurable)

  • Analog Input Types: 0–10V, ±10V, 4–20mA (per-channel jumper-selectable – not bank-based)

  • Analog Output Channels: 16 independent (0–10V, ±10V, or 4–20mA)

  • Resolution: 14-bit ADC (inputs), 12-bit DAC (outputs)

  • Accuracy: ±0.1% of full scale (inputs), ±0.2% of full scale (outputs)

  • Isolation: 1500V RMS channel-to-backplane

  • Diagnostics: Per-channel LED status, over-range/under-range detection, open-circuit detection, output short-circuit detection

  • Temp Range: –30°C to +70°C

  • Power Supply: +5V, ±15V from VME backplane (higher current draw)

  • Physical: 6U VME single-slot board

  • Key Variant Features: 32 inputs / 16 outputs with per-channel configurability, 1500V isolation, per-channel diagnostics


Advantages

  • Maximum flexibility + density – combines the per-channel configurability of the DS3800XAIC with the high I/O count of the DS3800XAIB, making it the most versatile high-density analog board in the Mark IV lineup.

  • Per-channel configurability – each of the 32 input channels can be individually set for voltage or current, ideal for installations with diverse sensor types that cannot be grouped.

  • High channel count – 32 inputs and 16 outputs per board reduce the number of boards and rack slots required.

  • Per-channel diagnostics – each input and output has its own status LED and fault detection (open-circuit, over-range, short-circuit) for rapid troubleshooting.

  • Improved isolation – 1500V RMS isolation reduces ground loop issues and protects the backplane.

  • Drop-in compatible – works with all Mark IV backplanes and processor configurations.


Applications

  • Large combined-cycle plants – monitors multiple turbines, HRSGs, and balance-of-plant equipment with diverse signal types.

  • Mixed signal environments – the General Electric DS3800XAID is ideal for installations with a variety of sensors (voltage, current, thermocouple via transmitters) that require individual configuration.

  • Frame 9 and above gas turbines – provides inputs for multiple exhaust thermocouple zones, fuel flow meters, compressor discharge sensors, and actuator feedback.

  • Offshore platforms – reduces rack space requirements in space-constrained cabinets.

  • Retrofits – adds significant I/O capacity with maximum flexibility to legacy Mark IV systems.


vs Competitors & Previous Variants

Feature DS3800XAID DS3800XAIC DS3800XAIB Generic VME Board
Analog inputs 32 diff / 64 SE 16 diff / 32 SE 32 diff / 64 SE 8–16 diff
Analog outputs 16 8 16 2–4
Configurability Per-channel Per-channel Bank-based (8 ch) Fixed or per-channel
Input resolution 14-bit 14-bit 14-bit 12–14-bit
Isolation 1500V 1500V 1000V 500–1000V
Per-channel LED Yes Yes Bank-level Rarely
Output short detect Yes Yes No Rarely
Temp range –30°C to +70°C –30°C to +70°C –30°C to +70°C 0°C to +60°C

Selection Tips

  • Mixed signal types + high density – choose the DS3800XAID when you need both a large number of channels and the ability to mix voltage and current sensors on a per-channel basis (e.g., multiple turbine installations with diverse instrumentation).

  • Rack space optimization – the DS3800XAID replaces multiple lower-density boards, making it ideal for space-constrained cabinets.

  • Power budget verification – the DS3800XAID draws significant current due to its high density and per-channel configuration. Verify your power supply capacity before installing multiple units.

  • Jumper documentation – each of the 32 input channels requires its own jumper for voltage/current selection. Record all jumper positions before removal for easy reinstallation.

  • Spare strategy – keep one General Electric DS3800XAID per 8 installed units; its combination of density and flexibility makes it a critical component.

  • Calibration – perform two-point calibration (zero and span) on critical channels after installation using a precision calibrator.


Critical Precautions

  • Power supply loading – do not exceed backplane power ratings when installing multiple DS3800XAID boards; monitor voltage levels at test points during commissioning.

  • Jumper configuration – each of the 32 input channels has its own jumper. Document all settings; incorrect jumper positions will produce erroneous readings.

  • Over-voltage on inputs – never apply voltage above ±30V to any analog input; this can damage the ADC front-end.

  • Output short circuit – while the DS3800XAID has short-circuit detection, repeated shorts can degrade output accuracy. Clear faults promptly.

  • Ground loops – use single-point grounding for field transmitters to avoid common-mode voltage exceeding ±10V on inputs.

  • Wiring separation – keep analog signal wiring away from AC power lines and high-voltage cables to prevent noise coupling.

  • Heat dissipation – due to high component density, ensure adequate cabinet cooling (>250 CFM) if multiple high-density boards are installed.

  • Calibration intervals – schedule periodic calibration verification (every 6–12 months) to maintain accuracy, especially for critical 4–20mA loops.

  • ESD handling – always use a grounded wrist strap; the high-density design has many exposed components and is ESD-sensitive.

  • Humidity – avoid condensation; high humidity can affect analog accuracy even though the DS3800XAID has conformal coating.

  • Hot-swap – never insert or remove the DS3800XAID while the rack is powered; high current draw increases the risk of arcing and damage.

A-B 1747-BA
A-B 1756-BA2
SCHNEIDER 140XTS00200

Reviews

There are no reviews yet.

Be the first to review “GE DS3800XAID”

Your email address will not be published. Required fields are marked *

Post comment